Error type
Error text
11011
27
Unclear error
B
D
11100
28
Reserved
B
D
11101
29
Error 1 in actua‐
B
D
tor/sensor
11110
30
Error 2 in actua‐
B
D
tor/sensor
11111
31
Channel/
B
D
module tempo‐
rarily unavaila‐
ble
See also
Structure of slave diagnosis (Page 91)
8.3.9

H-status, only in redundant configurations

Requirement
The IM 650 supplies the H-status only when it is operated on a CPU 410 in a redundant
configuration.
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB
Meaning
Unclear errors are those that cannot be specified in more de‐
tail
For HART modules: "Configuration Changed" signaled by the
HART field device
Error 1 in a field device that is connected to a module
For HART modules: HART primary variable outside the limits
Error 2 in a field device that is connected to a module
For HART modules: At least one HART secondary variable
outside the limits
e.g. due to calibration, firmware update, manual mode, etc.
Interrupt, error and system messages
8.3 S7 diagnostics
Remedy
Different, depending
on cause of error
Correction in actuator/
sensor depending on
error message
Correction in actuator/
sensor depending on
error message
Different, depending
on the cause;
e.g., wait until the initi‐
ated function (calibra‐
tion, FW update) is fin‐
ished.
103