8.4 After connecting the electrical wiring to the indoor unit

Installer reference guide
102
A
B
A
B
5 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat for the additional zone
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, we
recommend the following:
The safety thermostat is automatically resettable.
The safety thermostat has a maximum temperature variation rate of 2°C/min.
There is a minimum distance of 2  m between the safety thermostat and the
3‑way valve.
INFORMATION
After it is installed, do NOT forget to configure the safety thermostat for the
additional zone. Without configuration, the indoor unit will ignore the safety
thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat for the additional zone. It is only possible for
the system to have EITHER preferential kWh rate power supply OR a safety
thermostat for the additional zone.
To prevent water ingress to the switch box, seal the low voltage wiring intake using
the sealing tape (delivered as accessory).
Q4L
9
10
9 10
X5M
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07