The purpose of this document is to explain the setup steps in "point to point" mode on a Diris Digiware
system:
1 DIGIWARE C-31 control interface
1 DIGIWARE U-30 voltage module (same steps as for U-10 and U-20)
3 DIGIWARE I-35 current modules (same steps as for I-30, I-31 and I-33)
Prerequisite hardware for using this guide:
-
You must have the latest version of Easy Config, the setup software for these products
-
You must have a PC equipped with USB ports and a micro USB cable
-
You must be able to guarantee the implementation, connection and the power of the system to be
configured as shown in the first section.
We recommend that you first configure the U voltage module before the I modules on a
DIGIWARE bus.
Module U-30 must be placed on the DIGIWARE bus first, i.e. just after C-31 and just before
current modules I-xx
Product startup C31-U30-I35-I35-I35 ADY.docx
From: ADY
Verified by:
Page 1/14
loading

Summary of Contents for socomec Digiware U-30

  • Page 1  1 DIGIWARE C-31 control interface  1 DIGIWARE U-30 voltage module (same steps as for U-10 and U-20)  3 DIGIWARE I-35 current modules (same steps as for I-30, I-31 and I-33) Prerequisite hardware for using this guide:...
  • Page 2 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP 1) Architecture to configure Synthesis of the electrical and communication parameters: Electrical Loads Product Modbus N° TCP/IP Parameters Network Type Address nominal Type Name Type Usage Phase(s) current C-31 U-30 Cool Water Prod. 3-phases balanced 400V Air Con 60 A...
  • Page 3  Connect the micro USB cable from the module you want to configure and the PC  Open Easy Config  Switch to the "Super User" profile in Easy Config (default password: sOcOmec)  Click "Get from device": The module is automatically detected by Easy Config (if not, try disconnecting/reconnecting the cable and click "Refresh USB devices").
  • Page 4  Click "Connect to device": The example above shows how to connect a U-30 module to the PC with Easy Config. If you connect a different module, its name is shown in Easy Config instead of "Diris Digiware U-30" Product startup C31-U30-I35-I35-I35 ADY.docx...
  • Page 5 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP 3) Configuring module U-30 by architecture  Connect to module U-30 as shown in section 2.  On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE has a unique address.
  • Page 6 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP Example setup with one voltage measurement on a 4-wire network: To view the network configuration automatically detected by the product, click "Refresh". Please remember that this automatic detection only works if there is voltage on the network and if the grounding plug is connected to module U-30.
  • Page 7 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP  Apply the setup changes to the product by clicking "Final action" then "Send to device"  Make sure U-30 USB is selected in the list then click "Connect to device": Product startup C31-U30-I35-I35-I35 ADY.docx Page 7/14...
  • Page 8 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP  By default, Easy Config only checks those settings that were changed. This avoids having to resend the entire configuration to the device:  The U-30 module setup is applied to all I-xx current modules connected at the back of the same DIGIWARE bus.
  • Page 9 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP 4) Configuring the first I-35 module by architecture  Connect to the first I-35 module as shown in section 2.  On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE has a unique address.
  • Page 10 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP  On the "Loads" tab, make the following settings: The number of loads measured by module I-35 For each load, the type of measured load For each load, the phase(s) on which the sensor(s) are connected For each sensor, you may need to adjust the direction of current in case of a wiring fault The maximum number of loads for an I-3x current module is 3, because there are 3 sensor inputs on this module.
  • Page 11 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP  Example configuration with a DIGIWARE I-35 module used to measure: An air conditioning three-phase balanced load, with a nominal current of 60A per phase A lighting single-phase load, on phase 1, with a nominal current of 20A A heating single-phase load, on phase 3, with a nominal current of 35A ...
  • Page 12 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP  Apply the setup changes to the product by clicking "Final action" then "Send to device"  A warning message appears, showing that the operation completed successfully: Product startup C31-U30-I35-I35-I35 ADY.docx Page 12/14...
  • Page 13 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP 5) Configuring the second I-35 module by architecture  Connect to the second I-35 module as shown in section 2.  On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE has a unique address.
  • Page 14 MARKETING EE / TECHNICAL SUPPORT PRODUCT STARTUP 6) Configuring the third I-35 module by architecture  Connect to the third I-35 module as shown in section 2.  On the "Product" tab, change the JBUS/MODBUS address so that each device on the bus DIGIWARE has a unique address.