p2162[0...2]
Hysteresis freq. for overspeed / Overspd. hyst.freq
CU240S
Access level: 2
CU240S DP
Quick comm. NO
CU240S DP-F
Can be changed: U, T
CU240S PN
Min
0.00 [Hz]
Description:
Hysteresis speed (frequency) for overspeed-detection.
For vector control modes (P1300 = 20 - 23), the hysteresis acts above the max. frequency as illustrated in the dia-
gram below.
For v/f control modes (P1300 = 0 - 6), the hysteresis acts below the max. frequency.
f_act > f_max
f_act
p2163[0...2]
Entry freq. for perm. deviation / Entry freq. deviat
Access level: 2
Quick comm. NO
Can be changed: U, T
Min
0.00 [Hz]
Description:
Threshold for detecting speed deviation from setpoint.
Note:
See diagram in P2164.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Messages
Active: YES
Max
25.00 [Hz]
Max. frequency
0.00 ... 650.00 [Hz]
p1082.D (50.00)
1
0
Overspd. hyst.freq
0.00 ... 650.00 [Hz]
p2162.D (3.00)
Delay time
0...10000 [ms]
P2152.D (200)
P-Group: Messages
Active: YES
Max
20.00 [Hz]
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Factory setting
3.00 [Hz]
f_act > f_max
r2197 Bit06
f_act > f_max
0 T
r2197 Bit12
Data type: Floating Point
Data set: DDS
Factory setting
3.00 [Hz]
1-225