2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available in Technical guide No. 3 EMC compliant installation and configuration for a
power drive system (3AFE61348280 (English)).
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.

UL and CSA checklist

WARNING!
Operation of this drive requires detailed installation and operation instructions
provided in the hardware and software manuals. The manuals are provided in
electric format in the drive package or on the Internet. Retain the manuals with
the drive at all times. Hard copies of the manuals can be ordered through the
manufacturer.
Make sure that the drive type designation label includes the cULus Listed marking.
DANGER - Risk of electric shock. After disconnecting the input power, always wait
for 5 minutes to let the intermediate circuit capacitors discharge before you start working
on the drive, motor or motor cable.
The drive is to be used in a heated, indoor controlled environment. The drive must be
installed in clean air according to the enclosure classification. Cooling air must be clean,
free from corrosive materials and electrically conductive dust.
The maximum ambient air temperature is 40 °C (104 °F) at rated current. The current
is derated for 40 to 50 °C (104 to 122 °F).
1
3
4
5
6
7
8
4
9
6
6
Equipment
7
Supply transformer
8
Static screen
9
Drive
Technical data 123