1.3 SPECIFICATIONS

1.3 SPECIFICATIONS
1
PHASE CURRENT INPUTS
CT Primary:
5 to 2000 A
CT Secondary:
5 A
Conversion Range: 0.05 to 6 × CT
Frequency:
50 / 60 Hz
at < 2 × CT: ±0.5% of 2 × CT true RMS
Accuracy:
at ≥ 2 × CT: ±1% of 6 × CT true RMS
FIELD CURRENT INPUTS
CT Primary:
5 to 1000 A
Conversion Range: 0.05 to 1 × CT
Accuracy:
±2%
EXCITER VOLTAGE INPUTS
Conversion:
0 to 350 V DC (prior to VDN)
Accuracy:
±1%
POWER FACTOR
Range:
0.01 to 1 to –0.01
Time Delay:
0.1 to 10 seconds
Accuracy:
±5%
SWITCH INPUTS (MX & NX)
Type:
Dry contact
Internal Interrogation Voltage: 85 to 265 V AC (control voltage)
PF ANALOG OUTPUT
Type:
Active
Output:
0 to 10 V DC max. at R
Accuracy:
±10% (0.1 V)
Isolation:
36 V pk
CONTROL VOLTAGE
Input:
85 to 265 V AC at 48 to 60 Hz
Power:
10 VA nominal
Holdup:
100 ms typical at 120 V AC
1-
4
≥ 1 KΩ (min. load)
L
Specifications subject to change without notice
SPM Synchronous Motor Protection & Control

1.3.1 SPM SPECIFICATIONS

RELAY CONTACT
Type:
FAR, TRP
FCX
Rated Load:
10 A AC continuous
1 A DC continuous
Break:
10 A at 250 V AC or 30 V DC
Max. Operating Voltage: 250 V AC
ENVIRONMENT
Humidity:
0 to 95% non-condensing
Operating Temp.:
–20°C to +70°C
Storage Temp.:
–40°C to +85°C
TYPE TESTS
Dielectric Strength: Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 min. from relays, CTs, VTs
power supply to Safety Ground
Insulation
Resistance:
IEC255-5 500 VDC, from relays, CTs, VTs
power supply to Safety Ground
Transients:
ANSI C37.90.1 Oscillography (2.5kV/1MHz)
ANSI C37.90.1 Fast Rise (5kV/10ns)
Ontario Hydro A-28M-82
IEC255-4 Impulse/High Frequency Disturbance,
Class III Level
Impulse Test:
IEC 255-5 0.5J 5kV
EMI:
C37.90.2 Electromagnetic Interference at
150 MHz and 450 MHz, 10V/m
Static:
IEC801-2 Static Discharge
Vibration:
Sinusoidal Vibration 8.0g for 72 hrs.
CERTIFICATION
UL:
UL listed
CSA:
CSA approved
PHYSICAL
12.50" × 10.50" × 9.75" (L × H × D)
Shipping Box:
318 mm × 267 mm × 248 mm (L × H × D)
Ship Weight:
14.25 lb. / 6.45 kg