GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series Instruction Manual page 79

Table of Contents
3 SETUP AND USE
23
POWER FACTOR LAG
POWER FACTOR LAG
TRIP LEVEL = X.XX
TRIP LEVEL = X.XX
This setpoint is used to set the power factor "lag" trip threshold level for a power factor trip condition.
0.05-0.99 (increments of 0.01) or OFF
Factory Value = OFF
24
POWER FACTOR TRIP
POWER FACTOR TRIP
TIME DELAY = XXX
TIME DELAY = XXX
This setpoint is used to set the time delay that a power factor trip condition must persist for in order to
facilitate a trip.
1-255 seconds (increments of 1)
Factory Value = 5
25
POSITIVE KVAR ALARM
POSITIVE KVAR ALARM
LEVEL = +XXXXX KVARS
LEVEL = +XXXXX KVARS
This setpoint is used to set the positive kvar limit threshold for a kvar alarm condition.
100-25000 (increments of 100) or OFF
Factory Value = OFF
26
NEGATIVE KVAR ALARM
NEGATIVE KVAR ALARM
LEVEL = -XXXXX KVARS
LEVEL = -XXXXX KVARS
This setpoint is used to set the negative kvar limit threshold for a kvar alarm condition.
100-25000 (increments of 100) or OFF
Factory Value = OFF
27
KVAR ALARM
KVAR ALARM
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
This setpoint is used to set the time that a KVAR alarm condition must persist for in order to facilitate an
alarm.
1-255 seconds (increments of 1)
Factory Value = 5
28
ENABLE VOLTAGE PHASE
ENABLE VOLTAGE PHASE
REVERSAL?
REVERSAL?
This setpoint is used to enable or disable the phase reversal trip feature as detected from the meter
monitoring the line voltages.
YES - enable voltage phase reversal
NO - disable voltage phase reversal
3-40
Setpoints, Pg. 7
XXX
XXX