Manual Creation and Mapping of Reference Points (A)

Example:
Two IRM controllers and a wall module are on the MSTP bus in master-slave configuration:
WEB-RL6N (Master)
WEB-RS5N (Slave)
External BACnet wall module
o The WEB-RL6N master controller:
reads the window contact status [EffWindow] from the slave controller via RefIn
-
reads the room temperature [ExtWmRmTemp] from the BACnet Wall Module via RefIn
-
writes the occupancy status [EffOccMd] to an external BACnet Wall Module via RefOut
-
o The RS5N slave controller:
reads the fan output status [FanStage] of the staged fan (slow, medium, high) from the master
-
controller via RefIn
Reference Inputs
Based on the example above, the reference input functions of the WEB-RL6N master controller are described in the
following.
The WEB-RL6N master controller
reads the window contact status [EffWindow] from the slave controller via RefIn
-
reads the room temperature [ExtWmRmTemp] from the BACnet Wall Module via RefIn
-
NOTE: The read function of the WEB-RS5N slave controller is described using the automatic creation via drag &
drop (see "Automatic Creation and Mapping of Reference Points via Drag & drop (B)" section, p. 76).
Procedure
1. Note the device IDs of the WEB-RL6N master and WEB-RS5N slave controllers, in this case ´5003` and ´5001`
(displayed in the Discovered and Database pane).
2. In the Nav tree, expand the BACnet network and browse to the Points folder of the RS5N slave controller.