Led Functionality; Ok Leds - GE Bently Nevada 3300/16 Operation Manual

Dual vibration monitor
Table of Contents

5.1 OK LEDs

Note: Since each channel in the system controls the OK Relay, either channel can cause
a Not OK Relay condition (deenergized relay).
LED Display
A
B
OK
OK
OK
OK
OK
OK
OK
OK

5. LED Functionality

Channel A and B in operating range.
Respective channel A or B transducer in Not
OK condition or bypassed.
Monitor in self-test, or both transducers in
Not OK condition or bypassed.
Flashing at 5 Hz means that an error was
encountered during cyclic test. To read the
error message, see section 19.
Flashing at 1 Hz means that the transducer
has been Not OK since the last reset.
Section 5 - LED Functionality
Condition
OK Relay Drive
ON
OFF
OFF
ON
ON
7