4 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER

When a fault occurs, the inverter output is shut off to output a fault signal. However, a fault output signal may not be output at
an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi Electric assures best
quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to
machine when the inverter fails for some reason and at the same time consider the system configuration where failsafe from
outside the inverter, without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be
detected.
No.
Interlock Method
Inverter protective
1)
function operation
2) Inverter operating status Operation ready signal check
3) Inverter running status
4) Inverter running status
(2) Backup method outside the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure
status of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter
fault signal, start signal and RUN signal, there is a case where a fault signal is not output and RUN signal is kept output
even if an inverter fault occurs.
Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the
backup system such as checking up as below according to the level of importance of the system.
1)Start signal and actual operation check
Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to
the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor
current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the
start signal turns OFF. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it
is recommended to check the three-phase current when using the current detector.
2)Command speed and actual operation check
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command
and detected speed of the speed detector.
System failure
22
Check Method
Operation check of an alarm contact
Circuit error detection by negative logic
Logic check of the start signal and
running signal
Logic check of the start signal and
output current
Controller
Inverter
To the alarm detection sensor
Used Signals
Fault (ALM) signal
Inverter operation ready (RY) signal
Start (STF/STR) signal
Inverter running (RUN) signal
Start (STF/STR) signal
Output current detection (Y12) signal
Sensor
(speed, temperature,
air volume, etc.)
Refer to Page
Refer to Chapter
4 of the Instruction
Manual (Applied).
Refer to Chapter
4 of the Instruction
Manual (Applied).
Refer to Chapter
4 of the Instruction
Manual (Applied).
Refer to Chapter
4 of the Instruction
Manual (Applied).