  • Page 2 Copyright and trademark ● Panasonic Industrial Devices SUNX Co., Ltd. owns the copyright of this manual. ● We stiffly refuse the reproduction of without permission from this manual. ●Modbus Protocol is a communication protocol that the Modicon Inc. developed for PLC.
  • Page 3 Introduction Thank you very much indeed for purchasing “KW2G Expansion unit (Pulse input)”. In this manual, we explain the usage of “KW2G Expansion unit (Pulse input)” in detail. Please use it correctly after understanding the content enough.
  • Page 4: Table Of Contents

    Table of Contents Chapter 1 Unit’s Outline ...........................3 1.1 Unit’s Name and Model Numbers......................3 1.2 Combination devices ..........................3 1.3 Other tools ............................... 4 1.4 Measurement items ..........................4 Chapter 2 Parts Name and Working......................5 2.1 Parts Name .............................. 5 Chapter 3 Installation ..........................6 3.1 Measured-circuit ............................
  • Page 5 Cautions before using ■ Installation environment ◇Do not use the Unit in the following environments. ・Where the unit will be exposed to direct sunlight and where the ambient temperature is outside the range of -10 to 50 C. ・Where the ambient humidity is outside the range of 30 to 85 % RH (at 20℃, non-condensing) and where condensation might occur by sudden temperature changes ・Where inflammable or corrosive gas might be produced ・Where the unit will be exposed to excessive airborne dust or metal particles...
  • Page 6 ■ Power supply ・Connect a breaker to the voltage input part for safety reasons and to protect the device. The breaker that connects to the voltage input part must arrange at the position easily reached, and display shows it is the breaker of the equipment. ・Do not turn on the power supply or input until all wiring is completed.
  • Page 7: Chapter 1 Unit's Outline

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 1 Unit’s Outline KW2G Eco-POWER METER Expansion unit (Pulse input) measures pulse signal from a sensor by connecting to the main unit. 1.1 Unit’s Name and Model Numbers Product name Model No.
  • Page 8: Other Tools

    KW2G Eco-POWER METER Expansion unit (Pulse input) 1.3 Other tools Product name Functions Model No Download from our ・Monitoring and logging the Data collection software website. KW Monitor measured values. Free of charge Download from our ・It makes graph by using data from Power display tool website.
  • Page 9: Chapter 2 Parts Name And Working

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 2 Parts Name and Working 2.1 Parts Name Front view (with cover) (no cover) Cover Input terminals Side view Connector label Peel off before connecting...
  • Page 10: Chapter 3 Installation

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 3 Installation 3.1 Measured-circuit ・It is impossible to measure by only the expansion unit. Connect expansion units to the main unit. Up to 7 expansion units are connected to 1 main unit. You can use with the combination of AKW2110G, AKW2160G, AKW2152G and AKW2182G as expansion units.
  • Page 11: Terminal Arrangement

    KW2G Eco-POWER METER Expansion unit (Pulse input) 3.3 Terminal arrangement Be sure to wire accordingly to the wiring diagrams. After completing the wiring, attach the cover for your safety. (with cover) (no cover) Function Screw CH0 + ① ① ②...
  • Page 12: For Input Connection

    KW2G Eco-POWER METER Expansion unit (Pulse input) 3.4 For input connection ●Pulse input ・Contact input Use highly reliable metal plated contacts. Since the contact’s bounce time leads directly to error in the count value, use contacts with as short a bounce time as possible. In general, select 30Hz for max.
  • Page 13: Chapter 4 Settings

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 4 Settings 4.1 Setting for Expansion unit (pulse input) 【Unit change】 Before setting, press to shift display of main unit (M) and expansion units (1 to 7) to set. Main unit M...
  • Page 14 KW2G Eco-POWER METER Expansion unit (Pulse input) Setting flow chart for Expansion unit (pulse input) Mode 2…Mode for setting of each parameter for pulse measurement Mode 4…Version check mode You can check the version of each unit. Monitor (Display when power on) ...
  • Page 15: Setting Mode Explanation For Expansion Unit (Pulse Input)

    KW2G Eco-POWER METER Expansion unit (Pulse input) 4.2 Setting Mode Explanation for Expansion unit (pulse input) ■The value with under line “ “ is initial setting among each setting value. ☆Set before measurement. 4.2.1 Mode 2 (Mode for setting of each parameter for pulse measurement) Max.
  • Page 16: Mode 4

    KW2G Eco-POWER METER Expansion unit (Pulse input) 4.2.2 Mode 4 (Version check mode) Version check mode Mode to check version of the software. It displays version of the software. Mode 4 Setting flow chart Monitor ↓ continuous press MODE 2 Lighting ↓...
  • Page 17: Chapter 5 Display Of Each Value

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 5 Display of each Value 5.1 Unit change 【Unit change】 Press to shift display of main unit (M) and expansion units (1 to 7). Main unit M Lighting Expansion unit 7 Lighting 5.2 Pulse count value / Pulse input status...
  • Page 18: Chapter 6 Specifications

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 6 Specifications 6.1 Unit Rated operating voltage 100-240V AC (Add to main unit) Rated frequency 50/60Hz common Rated power consumption 1.0VA / unit (240VAC at 25℃) Inrush current Max. 30A (240VAC at 25℃)
  • Page 19: Pulse Input

    KW2G Eco-POWER METER Expansion unit (Pulse input) 6.2 Pulse input Input channel 2 channels Input method Contact / non-voltage a contact or open-collector Insulation method Non-isolated between channel (Isolated with main unit) Input mode Addition (Fixed) Max. counting speed 50kHz/30Hz (Select with setting mode) Min.
  • Page 20: Chapter 7 Mounting

    KW2G Eco-POWER METER Expansion unit (Pulse input) Chapter 7 Mounting 7.1 Dimensions (Unit: mm)
  • Page 21 Revision History Issue Date Manual no. Content of revision October 2012 WUME-KW2GPLS-01 First issue New issue for the KW2G Expansion unit (Pulse input) by eidition of KW2G User’s manual (ARCT1F520E-2).
  • Page 22 ©...