4.5.5 Settings for Pulse Output
It uses the measurement value of main unit CH1 for pulse output CH1, it uses the measurement value
of main unit CH2 for pulse output CH2.
[Integral power pulse]
1
4
5
6
Item
1
Select CH *
2
Output type
3
Unit for output
4
Direction
5
Target phase
6
Pulse width
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email:
[email protected]
2
3
Select CH to set.
Select pulse output type.
< List >
Integral power pulse, Alarm, General output
(initial: Integral power pulse)
Set unit used for pulse output.
< List >
0.001, 0.01, 0.1, 1, 10, 100kWh (initial:0.001)
Select the direction of power (import or export) for using as a
threshold for pulse output.
< List >
P, -P (initial: P)
Select phase to monitor in order to judge the output.
* Select 'Total' when it measures 3P3W.
< List >
Phase1, Phase2, Phase3, Total (initial: Total)
Set pulse width.
< Range >
1 to 100ms (initial:1)
Description