Emerson Yarway Installation, Operation And Maintenance Instructions

Installing and servicing strainers

Quick Links

YarwaY INSTALLING AND SERVICING STRAINERS
InstallatIon, operatIon and maIntenance InstructIons
Before installation these instructions must be fully read and understood
INstallatION
1. Strainers should be installed ahead of
steam traps, control or pressure reducing
valves and other pipe line equipment to
protect against dirt, chips, scale or other
foreign matter.
2. Fit strainer with nippleand blow down valve
to facilitate frequent inspection and cleaning
of strainer.
3. Fig. 1A shows a Yarway Strainer installed
in a horizontal line ahead of a steam trap.
Fig. 2 A shows the strainer installed in a
vertical down-flow line. Be sure to install
the strainer with the arrow in direction of
flow.
4. Prevent freezing by installing strainer on
its side in horizontal lines or in vertical
downward flow piping. Both strainer and
blow down valve will drain completely and
therefore be freeze proof on shut down.
sErVICING
1. Regular inspection and blowing down of the
strainer (by removing cap plug or opening
blow down valve) will help to keep the
strainer free of debris.
2. To Clean. Valve off the strainer and remove
the screen cap. The screen and cap gasket
will come out with the cap.
Clean the screen with compressed air,
steam, or wash with a rust removing
solvent. Keep spare screens on hand to
reduce maintenance time.
3. To Reassemble. Clean the gasket surfaces
on the cap and body and install a new gasket
on the cap shoulder. Place the screen in the
cap recess and secure the cap assembly to
the strainer body.
4. Same maintenance procedure appliesto
bolted cover strainers.
Emerson.com/FinalControl
sparE parts
For one year service the following parts are
recommended for each strainer installed:
(2) Screen Cap Gaskets
(1) Screen
To order gaskets or screens: Specify (Qty.)
screen cap gasket for (Size), (Fig. No.) Yarway
Strainer. (Qty.), (Perforation or mesh size),
(Material) Screen for (Size), (Fig.No.) Yarway
Strainer.
warNING
Hot discharge from this product may cause severe
burns. Discharge must be piped away or directed
so that persons in the vicinity are not endangered.
This product must be isolated, vented and cool to
the touch before repairing or inspecting.
© 2017 Emerson. All Rights Reserved.
FIG. 1A
FIG. 2A
FIG. 3A
VCIOM-09536-EN 18/09
loading

Summary of Contents for Emerson Yarway

  • Page 1 2. Fit strainer with nippleand blow down valve To order gaskets or screens: Specify (Qty.) to facilitate frequent inspection and cleaning screen cap gasket for (Size), (Fig. No.) Yarway FIG. 1A of strainer. Strainer. (Qty.), (Perforation or mesh size), 3.
  • Page 2 Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.