Degrees Of Protection - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents
ACH580 E-Clipse bypass and packaged drive user manual
Dimensions: ACH580-PxR UL (NEMA) Type 3R
Frame
PxB3R-1
PxB3R-2
Note: UL (NEMA) Type 3R, Px3R-1...Px3R-4 enclosures are designed to be
mounted on a wall.
Note: Keep a minimum of 50 mm (2 in.) of free space on each side and 200 mm
(8 in.) of free space above and below all units from non-heat producing sources.
Double these distances from heat producing sources.

Degrees of protection

Available enclosures:
• UL (NEMA) Type 1 enclosure. The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as condensation, carbon
dust, and metallic particles.
• UL (NEMA) Type 12 enclosure. This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
• UL (NEMA) Type 3R enclosure. This enclosure provides protection from the
ingress of water (rain, sleet, or snow). The external formation of ice does not
damage this enclosure.
W
H
PxB3R-1 to PxB3R-2
Height (H)
Width (W)
in
mm
in
33.30
846
17.70
40.60
1032
20.10
D
Depth (D)
mm
in
mm
449
14.00
355
511
15.00
391
Weight
Dimensional
Drawings
lb
kg
83.8
38.0
3AXD50000236367
193.0
88.0
3AXD50000237531
Technical data
245

Hide quick links:

Table of Contents
loading

Table of Contents