JETMASTER INSET STOVE MKIII
16i, 18i, 50i, 60i, 70i, 60i Low, 70i Low
Installation, Operating and Servicing Instructions
Please leave these instructions with the customer
Table of Contents
loading

Summary of Contents for Jetmaster INSET STOVE MKIII 16i

  • Page 1 JETMASTER INSET STOVE MKIII 16i, 18i, 50i, 60i, 70i, 60i Low, 70i Low Installation, Operating and Servicing Instructions Please leave these instructions with the customer...
  • Page 2: Table Of Contents

    CONTENTS TECHNICAL SPECIFICATIONS ................................5 INSTALLATION INSTRUCTIONS Introduction ......................................6 Dimensions ........................................ 6 Regulations ....................................... 6 The Clean Air Act 1993 and Smoke Control Areas ............................ 6 Air Control Stop (Low Rate Stop) ................................7 Health and Safety Precautions .................................. 7 Important Points to Note before Starting Installation.
  • Page 3 Notice Plate ......................................23 Carbon Monoxide (CO) Alarm ................................. 23 Cleaning Up ......................................23 Lighting after installation ..................................24 Chimney Sweeping ....................................24 Handing Over ......................................24 Data Plate ........................................ 24 USERS INSTRUCTIONS General ........................................25 The Clean Air Act 1993 and Smoke Control Areas ..........................25 Air Control Stop (Low Rate Stop) ................................
  • Page 4 The data can be found on the data badge located at the left side of the inner fire box Fire Details Serial Number Model Installation Date Purchased From Name Address Date Installation By Installer Name Company Address Commissioning Please Circle One Flue type correct Flue swept and soundness checked Smoke draw test (spillage) carried out...
  • Page 5: Technical Specifications

    MINIMUM REFUEL INTERVAL SMOKELESS ZONE REPORT Defra approved for wood † Tested to EN13229:2001. 50i, 60i Low and 70i Low are Jetmaster estimated figures. * An air supply may be required in homes which have high levels of air tightness.
  • Page 6: Installation Instructions

    INSTALLATION INSTRUCTIONS THE 16i, 18i, 50i AND 60i INSET APPLIANCES ARE DESIGNED AND APPROVED TO BURN WOOD IN A SMOKE CONTROLLED AREA WHEN FITTED AND OPERATED IN LINE WITH THESE INSTRUCTIONS. Introduction READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING THE INSTALLATION. CLOSE ATTENTION TO THE DETAILS OF INSTALLATION WILL ENABLE YOU TO GET THE BEST RESULTS FROM YOUR FIRE.
  • Page 7: Air Control Stop (Low Rate Stop)

    Air Control Stop (Low Rate Stop) The 16i, 18i, 50i and 60i have been recommended as suitable for use in smoke control areas when burning wood and are fitted with a low rate stop. This stop prevents the air control lever being slid to the fully closed position.
  • Page 8: Unpacking

    The front face of the fireplace should be reasonably flat over the area covered by the outer firebox top and side flange seals to ensure good sealing. These faces should be made good if necessary. The appliance must not stand on combustible materials or carpets. Unpacking Handling - Adequate facilities must be available for loading, unloading and site handling.
  • Page 9: Chimneys And Flues

    Chimneys and Flues The flue and chimney must be inspected before installation to ensure that it is suitable for the appliance being fitted. Chimney and flue systems must meet the requirements of the Building Regulations Document J. Soundness of Flue The flue must be sound and free from cracks and obstructions.
  • Page 10: If Connecting To An Existing Masonry Flue

    If connecting to an existing masonry chimney, it is recommended that a flue forming pipe (short length of flue pipe) is used and the void between the flue forming pipe and the chimney filled with vermiculite concrete. A suitable access hole will need to be made in the chimney breast to allow the back filling to be carried out and then filled and sealed once the installation is complete.
  • Page 11: Protection Of Heat

    Fire Surrounds and Shelves If in doubt always consult the building regulations regarding the proximity of combustible materials. Some fire surrounds require the fire to be set forward from the chimney breast or to be raised for aesthetic reasons. Ensure that these requirements are taken into account when positioning the fire. Take this into account when forming the recess and front finished face of the fireplace for the fire.
  • Page 12: Air Supplied From Room

    Air Supplied from Room Bring air in to the room close to the fire. The ideal position is just to the sides of the fireplace opening as shown. It can be split and brought up in two positions if required, one each side of the fireplace opening. Careful positioning of the vents is essential so that they are not liable to become blocked and cause cold draughts.
  • Page 13: Fitting The Fire

    If installing the fire in an existing fireplace, first remove all loose material from the recess and measure the opening and recess to ensure that the Jetmaster outer firebox will fit. The opening must be high and wide enough to allow the outer firebox to be pushed into position. Allow extra height if connecting directly to the existing flue to make the connection.
  • Page 14: Door Removal/Replacement

    Open the door fully and carefully support the door, at the same time pull down the spring-loaded pin at the top of the door and lift the door up and outwards away from the lower hinge attachments on the firebox. Set aside in a safe place for refitting later.
  • Page 15: Tertiary Air Tubes

    Tertiary Air Tubes There are two tertiary air tubes located at the top of the inner firebox to bring air into the fire. One is large and one is small. Each tube is held in its position by a swing cam catch attached with a single 8mm bolt to the left hand inner side of the firebox.
  • Page 16: Tertiary Air Tube And Lower Baffle Removal And Replacement

    CAUTION Ensure that the cam catch locator is positioned in the tube hole when the bolt is tightened to trap the tube from sliding out and to ensure that the tertiary air ports are in their correct position within the fire. Ensure that the baffles are fitted the correct way around and centrally left to right.
  • Page 17: Removing And Replacing Ash Pan

    Removing and Replacing Ash Pan Remove the ash pan by sliding it out from under the grid. Fit the ash pan by sliding in under the cast bottom grid. Ensure it is fitted the correct way around with the handle towards the front as shown below.
  • Page 18: Side Board Removal And Replacement

    Side Board Removal and Replacement The left and right-side boards can be removed by gently pulling one edge out first then, slide the boards towards the centre of the stove. Replacement is the reverse procedure. To replace the boards, offer one edge in first and then push the board gently back. Note: - They should be pushed back flat against the steel body of the fire.
  • Page 19: Infilling Above The Outer Box

    Place the outer firebox in front of the prepared opening. Wrap the sides and back of the fire with the fibre insulation and hold this in place with tape. Two layers of white ceramic insulation should be placed across the top of the outer firebox relieving around the area for the flue adaptor. This is to allow for expansion and contraction and to protect the wall above from excess heat.
  • Page 20: External Air Supply Fitting

    External Air Supply Fitting The primary air can be taken from the room or alternatively it can come from an external source from outside the building. If taken from the room then air ducts are required to the room, as the fire will take its primary air from the chamber around the fire that is fed by air from the room.
  • Page 21: Refitting The Internal Components

    Do not push the inner box all the way back as it will block the rear air intake to the fire. If an external air supply is used ensure that the flexible pipe feeds through the rear of the outer box and does not get trapped. The final position should be with the front surface of the inner box 20mm further forward than the front surface of the outer box.
  • Page 22: Commissioning

    The frame is fitted to the outer firebox by locating the flanges inside the outer firebox. The slots in the frame sides should align with the threaded holes. Ensure the frame is the correct way up. If they do not align then, either the frame has been positioned upside down or the outer box has been twisted out of square to the wall during fitting.
  • Page 23: Smoke Draw Test

    Smoke Draw Test. Ensure appliance is not alight. Warm chimney for 10 minutes using a blowlamp or similar heating device. Place a smoke pellet in the wood tray or basket grate towards the front of the opening of the fire and ignite the pellet.
  • Page 24: Lighting After Installation

    Lighting after installation The Jetmaster should not be run hard until all cement and plasterwork is completely dry and cured. When installation has involved building in cement mortar allow: - 7 days drying time if the house has other forms of heating.
  • Page 25: Users Instructions

    This appliance is designed for intermittent operation and is intended for the purposes of room heating. It is designed to burn only the recommended fuels specified by Jetmaster and shall not be used with any liquid fuels or as an incinerator.
  • Page 26: Air Control Stop (Low Rate Stop)

    Air Control Stop (Low Rate Stop) The 16i, 18i, 50i and 60i have been recommended as suitable for use in smoke control areas when burning wood and are fitted with a low rate stop. This stop prevents the air control lever being slid to the fully closed position.
  • Page 27 DO NOT use aerosol sprays near the stove when it is alight. DO NOT modify the appliance in any way. ONLY modifications authorised by Jetmaster may be carried out. Always allow the fire to cool before touching any parts. Note that the residual heat in the fuel will remain hot for a considerable length of time.
  • Page 28: Carbon Monoxide Alarm

    WHEN FITTED AND OPERATED IN LINE WITH THESE NSTRUCTIONS. Lighting after Installation A Jetmaster should not be run hard until all cement and plasterwork is completely dry and cured. As a basic guide the installer should Allow a 7-day drying time if the house has other forms of heating.
  • Page 29: Operating Tool

    Wood Burning and Basket Grates Jetmaster fires may be used to burn a variety of fuels. If burning wood then no additional accessories are required as wood can be burnt on the bottom grate. However, if burning smokeless fuel then basket grates are available to ensure that the fuel is burned in the most effective way.
  • Page 30: Refuelling On To A Low Fire Bed

    Refuelling on to a low fire bed If there is insufficient burning material in the fire bed to light a new fuel charge, excessive smoke emission can occur. Refuelling must be carried out onto sufficient quantity of glowing embers and ash that the new fuel charge will ignite in a reasonable period.
  • Page 31: Seasonal Use

    The maximum amount of fuel specified in this manual should not be exceeded, overloading can cause excess smoke. Recommended Fuel Types The Jetmaster 16i, 18i, 50i and 60i Stoves have been assessed and been considered suitable for exemption under the Clean Air Act 1993 when burning dry wood logs. Wood (Recommended and approved fuel for fire to meet requirement of EN13229:2001) The readiness of wood to burn depends on the density and the size of each piece.
  • Page 32: Cleaning And Maintenance

    Cleaning and Maintenance To maintain the finish on Decorative Surrounds wipe with a soft damp cloth only. Do not use abrasive cleaners, polish or solvents as these can damage the surface finish. The visible front parts of the fire can be repainted with heat resistant black paint. These parts can be repainted every 1 or 2 years as required but generally dusting with a soft brush should keep the fire looking good.
  • Page 33: Air Control Lever

    At this point with the baffles out the flue can easily be swept. If any boards show signs of surface damage or are broken then they should be replaced. Replacement parts are available from your Jetmaster Distributor. For replacement of tertiary air tubes and baffles reverse the removal procedure.
  • Page 34: Door Glass Replacement And Seal Replacement

    Before refitting the inner door frame, check the seal on the back of the frame for damage. If this needs replacing then a seal can be obtained from Jetmaster. This seal has backing tape which should be peeled back and the seal attached to the inner frame around the edge, ensuring that it touches at the corners so as to give a continuous seal.
  • Page 35: Door Tension Adjustment

    Refit the inner door frame and nuts hand tight. Finally tighten each nut a little at a time so as to pull the glass down evenly to avoid it cracking. This will allow the metal to expand when heated to avoid cracking the glass. DO NOT OVERTIGHTEN THE BOLTS AND NUTS OR THE GLASS WILL CRACK.
  • Page 36: Warranty

    Hunter Stoves Group Ltd Extended 5 and 10 Year Warranty 2 Year Standard Warranty Any appliance bought through the showroom of an authorised Hunter Stoves Group dealership will automatically be covered by our standard 2-year conditional guarantee. However, this standard 2-year warranty can be extended to a 5 year or 10 year conditional warranty dependent on the model type (5 years- Boiler models, 10 years- Room heater and Gas models).
  • Page 37 Paint and Surface Coverings The paint or surface covering of the appliance will be covered (for 2 years after installation) provided the warranty conditions are met. However, damage due to the following events will not be covered: 1. Damage to the paint surface caused by the appliance being stored in a damp and cold environment is not covered under warranty.
  • Page 38 Contact Details Hunter Stoves Group, 8 Emperor Way, Exeter Business Park, Exeter, Devon. EX1 3QS Email: [email protected] Web: www.hunterstoves.co.uk JINJMINA – REV A 15/05/18 E&OE...