Card cage (5 slots) FCA2008-A1

Technical data

23.3.2
23.4
Plug-in units
Supply
Connections
Mechanical data
Ambient conditions
Standards and approvals
142
Building Technologies
Fire Safety
X11...X52 connection terminals for the module bus card
The module bus card determines the PIN assignment of the four connectors. You
will find the pin assignments in the description of the corresponding module card.
The assignment of the connector is:
Connections of module bus card 1 are on connectors X11 and X12
Connections of module bus card 2 are on connectors X21 and X22
Connections of module bus card 3 are on connectors X31 and X32
Connections of module bus card 4 are on connectors X41 and X42
Connections of module bus card 5 are on connectors X51 and X52
Technical data
Slots
Operating voltage
Operating current
Permitted cable cross section (plug X9)
screw terminals
Total current of all module bus cards
I/O
Permitted cable cross section of the screw
terminals (connector X11...X52)
Dimensions (L x W x H)
Weight
Shielding
Operating temperature
Storage temperature
Air humidity
VDS
QA Standards
CE conformity mark
LPCP
Max. 5 module bus cards
Vsys DC 20...30 V
Max. 8 A
0.5...2.5 mm²
Max. 8 A
Max. 2 A
0.14...1.5 mm²
298 x 192 x 140 mm
1160 g
Housing with cover: Steel sheet
Min. -5 °C max. +50 °C
Min. -20
max. +60
Max. 93 % rel. air humidity (EN 60068-2)
008837_q_en_--
14.05.2012
Table of Contents
loading

Table of Contents