Grounding The Motor Cable Shield At The Motor End; Connecting The External Power Supply Cable For The Auxiliary Circuit - ABB ACS880-04 Hardware Manual

Industrial drives, single drive module packages
Hide thumbs Also See for ACS880-04:
Table of Contents
Electrical installation 135
5. Crimp suitable cable lugs to the conductors as well as the twisted shield. Connect the
phase conductors to the output busbars. Connect the cable shield to a PE busbar.
6. Secure the cables inside and outside the cabinet mechanically.
7. Tighten the cable gland if present.

Grounding the motor cable shield at the motor end

For minimum radio-frequency interference, ground the cable shield 360 degrees at the
lead-through of the motor terminal box. See also Cabinet design and construction
instructions for ACS880 air-cooled and liquid-cooled multidrive modules
(3AUA0000107668 [English]).
Connecting the external power supply cable for the
auxiliary circuit
Connectors are described on page 37.
Table of Contents
loading