5.4 Preparing detector base FDB22x for installing an
Building Technologies
Fire Safety
34BPreparing detector base FDB22x for installing an FDOOT241-A3 or FDOOT241-A4
FDOOT241-A3 or FDOOT241-A4
The point detectors FDOOT241-A3 and FDOOT241-A4 can be used to replace
detectors from the AnalogPLUS or SIGMALOOP detector families.
You will find details in the 'List of compatibility'.
Use one of the FDB221, FDB221-AA, or FDB222 detector bases.
1. Use the table below to determine the resistance which corresponds to the
existing detector type.
-
-
+
+
+
Resistor connection
R = ∞Ω Do not install a resistor
2. Install the resistor. See figure 'Resistor connection'.
–
If the detector is replacing a DO1131A, SDF1200, or SDF2200, do not
install a resistor.
3. Use the auxiliary terminal DBZ1190-AA for multiple assignment. See figure
'Resistor connection'.
-
R
4BMounting / Installation
DO 1131A
T
SDF
31
R = 27 kΩ ±2 kΩ (0,25 W)
DT1131A
SDT2100
R = 18 kΩ ±2 kΩ (0,25 W)
D 113 A
T
2
R = 10 kΩ ±2 kΩ (0,25 W)
DO113 A
1
1
R =
Ω
007004_t_en_--
2015-11-04
5
00