  • Page 1 FDOOT271-O, FDB271 Radio fire detector, detector base Mounting Building Technologies A6V10425629_en--_e 2016-11-28 Control Products and Systems...
  • Page 2 Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2016-11-28 Document ID: A6V10425629_en--_e © Siemens Switzerland Ltd, 2014 2 | 18 Building Technologies A6V10425629_en--_e Fire Safety 2016-11-28...
  • Page 3: Table Of Contents

    About this document ................5 Mounting / Installation ................6 Required space ..................6 Detector base FDB271 ................6 Mounting radio fire detector FDOOT271-O ..........7 Detector locking device FDBZ293 ............... 9 Designation plate FDBZ291 ...............10 Establishing factory settings ...............11 Details for ordering ................
  • Page 4 4 | 18 Building Technologies A6V10425629_en--_e Fire Safety 2016-11-28...
  • Page 5: About This Document

    You will find information on how to integrate the radio fire detector into a radio cell in the radio gateway manufacturer's documentation. Intended use The radio fire detector FDOOT271-O may only be used in a fire detection system in a detector base FDB271 together with a radio gateway approved by the manufacturer.
  • Page 6: Mounting / Installation

    Mounting / Installation Required space 2 Mounting / Installation 2.1 Required space Upon insertion of the detector, the detector base is stressed by compression, tension and torsion. The fixing must thus be designed accordingly. Detector bases must be placed flat on the ceiling. Avoid mounting on steps, concrete ribs, etc.
  • Page 7: Mounting Radio Fire Detector Fdoot271-O

    Mounting / Installation Mounting radio fire detector FDOOT271-O 2.3 Mounting radio fire detector FDOOT271-O The action of inserting the radio fire detector into the detector base activates it; the detector then logs on to other radio devices immediately. Therefore, start from the radio gateway and work outwards to install the individual radio fire detectors.
  • Page 8 Mounting / Installation Mounting radio fire detector FDOOT271-O 5. Make sure that the holder (3) latches into place correctly. a When the battery connector is connected, the internal alarm indicator lights up red for 5 seconds. a After a further 10 seconds, the radio fire detector signals that it is not installed on the detector base and the internal alarm indicator flashes.
  • Page 9: Detector Locking Device Fdbz293

    Mounting / Installation Detector locking device FDBZ293 2.4 Detector locking device FDBZ293 The detector can be protected against theft with the detector locking device FDBZ293. Figure 3: Mounting of detector locking device FDBZ293 1 Detector base 4 Detector 2 Set screw with a hexagon socket 5 Allen key 3 Hole 1.
  • Page 10: Designation Plate Fdbz291

    Mounting / Installation Designation plate FDBZ291 2.5 Designation plate FDBZ291 Designation plate FDBZ291 is used to assign a location address to the detector. 1. Label the designation plate. 2. Slide the designation plate into the detector base from the side. FDBZ291 FDB271 Figure 4: Installing the designation plate...
  • Page 11: Establishing Factory Settings

    Mounting / Installation Establishing factory settings 2.6 Establishing factory settings All existing settings are deleted and reset to the factory settings. Figure 5: Establishing factory settings 1 Internal alarm indicator 2 'new' opening with button To create the factory settings on the radio fire detector, proceed as follows: w The radio fire detector is being supplied with power.
  • Page 12: Details For Ordering

    Details for ordering Radio fire detector FDOOT271-O 3 Details for ordering 3.1 Radio fire detector FDOOT271-O For the OEM radio fire detection system Attached to detector base FDB271 Power supplied by battery pack BAT3.6-10 Can be configured with FXS2061-O Wireless...
  • Page 13: Detector Locking Device Fdbz293

    Details for ordering Detector locking device FDBZ293 3.4 Detector locking device FDBZ293 For protection against theft Compatible with: – Radio fire detector FDOOT271-O Order number: A5Q00005035 3.5 Designation plate FDBZ291 To identify the location Compatible with: – Detector base FDB271...
  • Page 14: Specifications

    Specifications Technical data 4 Specifications 4.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: Document A6V10431682 Device characteristics Response sensitivity 2.3…12 %/m Compensation speed 1/45 voltage increase for detection/h...
  • Page 15 Specifications Technical data Ambient conditions Operating temperature: -10…+55 °C Storage temperature -30…+75 °C Air humidity 95 % rel. Protection category (IEC 60529): IP44 Electromagnetic compatibility: 100 kHz…2.5 GHz 30 V/m Permissible wind speed: Max. 5 m/s Mechanical data Weight without accessories 0.132 kg Housing material Acrylonitrile-butadiene-styrene (ABS)
  • Page 16: Dimensions

    Specifications Dimensions 4.2 Dimensions Radio fire detector FDOOT271-O with detector base FDB271 16 | 18 Building Technologies A6V10425629_en--_e Fire Safety 2016-11-28...
  • Page 17: Environmental Compatibility And Disposal

    Specifications Environmental compatibility and disposal 4.3 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: Use of reusable materials Use of halogen-free plastics Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043.
  • Page 18 Issued by © Siemens Switzerland Ltd, 2014 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: A6V10425629_en--_e Manual FD20/FD720 Edition: 2016-11-28...