Allen-Bradley POINT I/O 1734-IV2 Installation Instructions Manual page 24

Source input modules
Hide thumbs Also See for POINT I/O 1734-IV2:
Table of Contents
POINT I/O Source Input Modules
Environmental Specifications
Attribute
Temperature, operating
Temperature, storage
Temperature, surrounding air, max 55 °C (131 °F)
Relative humidity
Vibration
Shock
operating
Nonoperating
Emissions
ESD immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
24
Rockwell Automation Publication 1734-IN052F-EN-E - January 2019
Value
IEC 60068-2-1 (Test Ad, operating cold),
IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock):
-20... +55 °C (-4...+131 °F)
IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),
IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat),
IEC 60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40...+85 °C (-40...+185 °F)
IEC 60068-2-30 (Test Db, unpackaged damp heat):
5...95% noncondensing
IEC60068-2-6 (Test Fc, operating):
5 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, unpackaged shock)
30 g
50 g
IEC 61000-6-4
IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth (CM) on signal ports
IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Table of Contents
loading