Allen-Bradley POINT I/O 1734-IV2 Installation Instructions Manual

Source input modules
Hide thumbs Also See for POINT I/O 1734-IV2:

Quick Links

Installation Instructions
Original Instructions
POINT I/O Source Input Modules
Catalog Numbers 1734-IV2,1734-IV4, 1734-IV8, 1734-IV8K, Series C
Catalog numbers with the suffix 'K' are conformal coated and their
specifications are the same as non-conformal coated catalogs.
Topic
Page
2
3
4
5
7
8
9
10
11
13
14
19
20
22
Table of Contents
loading

Summary of Contents for Allen-Bradley POINT I/O 1734-IV2

  • Page 1: Table Of Contents

    Installation Instructions Original Instructions POINT I/O Source Input Modules Catalog Numbers 1734-IV2,1734-IV4, 1734-IV8, 1734-IV8K, Series C Catalog numbers with the suffix ‘K’ are conformal coated and their specifications are the same as non-conformal coated catalogs. Topic Page Important User Information Environment and Enclosure North American Hazardous Location Approval European Hazardous Location Approval...
  • Page 2: Important User Information

    POINT I/O Source Input Modules Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-state Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid- state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure

    POINT I/O Source Input Modules Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
  • Page 4: North American Hazardous Location Approval

    POINT I/O Source Input Modules North American Hazardous Location Approval The Following Information Applies When Informations sur l’utilisation de cet équipement en Operating This Equipment In Hazardous Locations. environnements dangereux. Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne Products marked "CL I, DIV 2, GP A, B, C, D"...
  • Page 5: European Hazardous Location Approval

    POINT I/O Source Input Modules European Hazardous Location Approval The following applies to products marked • Are intended for use in potentially explosive atmospheres as defined by European Union Directive 2014/34/EU and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
  • Page 6 POINT I/O Source Input Modules WARNING: • This equipment is not resistant to sunlight or other sources of UV radiation. • This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments.
  • Page 7: Special Conditions For Safe Use

    POINT I/O Source Input Modules Special Conditions for Safe Use ATTENTION: • This product is grounded through the DIN rail to chassis ground. Use zinc- plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
  • Page 8: Before You Begin

    POINT I/O Source Input Modules Before You Begin You can use these Series C POINT I/O™ Input modules with DeviceNet and PROFIBUS adapters. If you are using RSLogix 5000® software, version 11 or higher, you can also use the modules with ControlNet and Ethernet adapters. Use this diagram to identify the external features of the module.
  • Page 9: Install The Mounting Base

    POINT I/O Source Input Modules Description Description Module locking mechanism 1734-TB or 1734-TBS mounting base Slide-in writable label Interlocking side pieces Insertable I/O module Mechanical keying (orange) Removable terminal block (RTB) handle DIN rail locking screw (orange) Removable terminal block with screw (1734- Module wiring diagram RTB) or spring clamp (1734-RTBS) Install the Mounting Base...
  • Page 10: Install The Module

    POINT I/O Source Input Modules Install the Module The module can be installed before or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure that the mounting base locking screw is positioned horizontal referenced to the base.
  • Page 11: Install The Removable Terminal Block

    POINT I/O Source Input Modules Install the Removable Terminal Block A Removable Terminal Block (RTB) is supplied with your wiring base assembly. To remove, pull up on the RTB handle. This allows the mounting base to be removed and replaced as necessary without removing any of the wirings. To reinsert the Removable Terminal Block, proceed as follows.
  • Page 12 POINT I/O Source Input Modules WARNING: For 1734-RTBS and 1734-RTB3S, to latch and unlatch the wire, insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter blade) into the opening at approximately 73° (blade surface is parallel with top surface of the opening) and push up gently.
  • Page 13: Remove A Mounting Base

    POINT I/O Source Input Modules Remove a Mounting Base To remove a mounting base, you must remove any installed module and the module that is installed in the base to the right. Remove the removable terminal block, if wired. 1. Unlatch the RTB handle on the I/O module. 2.
  • Page 14: Wire The Module

    POINT I/O Source Input Modules Wire the Module To wire the module, see the diagrams and tables. 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K Module Module Module Status Status Status Network Network Network Status Status Status NODE: NODE: NODE: 24VDC 24VDC 24VDC Source Source Source Input...
  • Page 15 POINT I/O Source Input Modules POINT I/O Source Input Module Wiring – 1734-IV2 In 0 In 1 Prox Prox 2-wire 3-wire C = Common V = 12/24V DC supply Channel Input Terminal Common Terminal Power Connect power on 3-wire proximity switches. 12/24V DC is provided by the internal field power bus.
  • Page 16 POINT I/O Source Input Modules POINT I/O Source Input Module Wiring – 1734-IV8, 1734-IV8K 3-wire 3-wire Prox In 0 In 1 Prox 2-wire 2-wire Prox Prox In 2 In 3 3-wire 3-wire In 4 In 5 Prox Prox 2-wire 2-wire Prox In 6 In 7...
  • Page 17 POINT I/O Source Input Modules Wiring Example of 1734-IV8, 1734-IV8K Using 2-Wire Proximity Switches Module Module Status Status Network Network Status DeviceNet Status System Power DeviceNet Power 1734 1734 OB8E Prox Prox Prox Prox Prox Prox Prox Prox 24V DC return (C) 24V DC (V) Terminal block with bus connector strip Rockwell Automation Publication 1734-IN052F-EN-E - January 2019...
  • Page 18 POINT I/O Source Input Modules Wiring Example of 1734-IV8, 1734-IV8K Using 3-Wire Proximity Switches Module Module DeviceNet Status Status Network Network Status Status System Power DeviceNet Power 1734 1734 OB8E Prox Prox Prox Prox Prox Prox Prox Prox 24V DC return (C) 24V DC (V) Terminal block with bus Terminal block with bus...
  • Page 19: Communicate With The Module

    POINT I/O Source Input Modules Communicate with the Module POINT I/O modules send (produce) and receive (consume) I/O data (messages). You map this data into the memory of the processor. The 1734-IV2, 1734-IB4, and 1734-IV78 modules produce 1 byte of input data (scanner Rx).
  • Page 20: Interpret Status Indicators

    POINT I/O Source Input Modules Interpret Status Indicators See the following diagram and table for information on how to interpret the status indicators. 1734-IV8, 1734-IV2 1734-IV4 1734-IV8K Module status Module Module status Module Module Status Status Status Network Network status Network Network status Network...
  • Page 21 POINT I/O Source Input Modules Indicator Status for Modules Status Description No power applied to device. Green Device operating normally. Device needs commissioning due to missing, incomplete, or incorrect Flashing green configuration. Module status Flashing red Recoverable fault. Unrecoverable fault – may require device replacement. Flashing red/green Device is in self-test mode.
  • Page 22: Specifications

    POINT I/O Source Input Modules Specifications POINT I/O Source Input Modules – 1734-IV2, 1734-IV4, 1734-IV8, 1734-IV8K Attribute 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K 2 (1 group of 2), 4 (1 group of 4), Number of inputs 8 (1 group of 8), sourcing sourcing sourcing Voltage, on-state, min...
  • Page 23 POINT I/O Source Input Modules General Specifications Attribute 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K Terminal base screw torque 0.8 N•m (7 lb-in.) 1 green/red – Module Status indicator, logic side 1 green/red – network status indicator, logic side Indicators 2 yellow – input 4 yellow –...
  • Page 24 POINT I/O Source Input Modules Environmental Specifications Attribute Value IEC 60068-2-1 (Test Ad, operating cold), IEC 60068-2-2 (Test Bd, operating dry heat), Temperature, operating IEC 60068-2-14 (Test Nb, operating thermal shock): -20… +55 °C (-4…+131 °F) IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold), IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat), Temperature, storage IEC 60068-2-14 (Test Na, unpackaged nonoperating thermal shock):...
  • Page 25 POINT I/O Source Input Modules Certifications Certification (When Value Product Is Marked) UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada.
  • Page 26 POINT I/O Source Input Modules Notes: Rockwell Automation Publication 1734-IN052F-EN-E - January 2019...
  • Page 27 POINT I/O Source Input Modules Rockwell Automation Support Use the following resources to access support information. Knowledgebase Articles, How-to Videos, Technical Support www.rockwellautomation.com/ FAQs, Chat, User Forums, and Product knowledgebase Center Notification Updates. Local Technical www.rockwellautomation.com/global/ Support Phone Locate the phone number for your country. support/get-support-now.page Numbers Find the Direct Dial Code for your product.
  • Page 28 Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, POINT I/O, Rockwell Automation, Rockwell Software, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.