Allen-Bradley 1336 PLUS II Instructions Manual

Firmware download module
Hide thumbs Also See for 1336 PLUS II:

Quick Links

What is Flash Memory?
Firmware Download
Requirements
Required Communications
Cable
en-Bradley Replacements
1336
Firmware Download
PLUS
II
Module
Catalog Number 1336F-FDM
This document provides information on upgrading the 1336
firmware, including a description of the Flash memory used in the
drive and the procedures required for downloading the latest firmware
revision. For detailed drive information, refer to 1336
Manual, publication 1336 PLUS-5.3.
The drive firmware (including parameter layout and operating
algorithms) resides in a form of programmable read-only memory
called "Flash Memory." Flash memory allows the user to easily
upgrade the drive firmware locally using a standard computer and the
supplied Firmware Download Module. The latest firmware files are
available on the Internet or from your local Allen-Bradley Sales
Office.
The necessary file can be downloaded to the module with a computer
having the following:
• Disk drive (hard and/or floppy).
• Standard communications program capable of XMODEM
protocol.
• Standard serial "COM" port and connecting cable (see below).
In addition, the following is recommended:
®
• IBM
compatible computer with Microsoft
System.
• Internet access and browser software.
A standard serial communications cable wired as shown, is required.
This cable interconnects the computer and Flash Download Module.
Flash Download Module
9 Pin Female
D-Shell Connector
1
6
2
7
3
8
4
9
5
Instructions
PLUS
User
PLUS
II
®
®
Windows
Operating
PC COM Port
9 Pin Male
D-Shell Connector
5
9
4
8
TX
3
COM
7
2
RX
6
1
II
loading

Summary of Contents for Allen-Bradley 1336 PLUS II

  • Page 1 “Flash Memory.” Flash memory allows the user to easily upgrade the drive firmware locally using a standard computer and the supplied Firmware Download Module. The latest firmware files are available on the Internet or from your local Allen-Bradley Sales Office. Firmware Download The necessary file can be downloaded to the module with a computer...
  • Page 2: Main Control Board Power Requirements

    1336 PLUS II Firmware Download Module Main Control Board Power In order to upgrade firmware, the Main Control Board must have Requirements power applied. This can be accomplished through one of the following methods: • Application of AC line voltage per instructions in Chapter 2 of the 1336 User Manual.
  • Page 3 1336 PLUS II Firmware Download Module Figure 1 Component Locations Spare Jumpers Control Interface Option Location Status LEDs Spare Jumpers Status LEDs Flash Download Module External Power Connector Frames A1 - A4 Frames B - G Communications Connector 5. Install the Flash Download Module in the Main Control Board cradle –...
  • Page 4 1336 PLUS II Firmware Download Module C. Verify the files using the information below. .bin Major Revision Minor Revision Serial Flash Version Level Level Version File Type Major rev levels Minor revs may The file for a 1336 bin=binary may include new...
  • Page 5: Establishing Communications With The Drive

    1336 PLUS II Firmware Download Module Establishing Communications Setting Up the Communications Program with the Drive 10. Start the XMODEM communications program. The following examples demonstrate the use of HyperTerminal (supplied with Windows 95 operating system). Other programs will be similar.
  • Page 6 1336 PLUS II Firmware Download Module B. Phone Number window – locate the Connect using: menu and choose “Direct to Com1,” then select “OK.” If a different COM port is being used, substitute the appropriate one for your computer setup.
  • Page 7 1336 PLUS II Firmware Download Module Transferring the File to the Drive 12. Press the Enter key on your computer once to signal the drive – an introduction screen will be displayed. 13. Press “F” to enter the Flash Mode. You are now prompted to confirm your choice “Are you sure?”...
  • Page 8 1336 PLUS II Firmware Download Module 14. The default baud rate of 9600 should be acceptable under most conditions. However, to facilitate faster file transfers, the baud rate can be changed for communications up to the maximum drive rate of 115.2 kb (or the maximum computer rate). To use the default rate, proceed to step 15.
  • Page 9 1336 PLUS II Firmware Download Module 16. Select “(2) Send File to drive.” A message will appear regarding correct jumper installation. A string of C’s will then appear, indicating that the drive is waiting for the file to be downloaded.
  • Page 10 1336 PLUS II Firmware Download Module If the “packet” value is not incrementing and the time remaining block is continually incrementing, the file transfer is not taking place. If this occurs, cancel the operation and repeat the entire procedure, verifying jumper placement, cabling and communications setup.
  • Page 11 1336 PLUS II Firmware Download Module 18. If errors occurred in the transfer, the screen may display one of the following: • Error in Constant Block • Error in Program Block • Error in DSP Block • Error in Text and Language Block...
  • Page 12: Troubleshooting

    1336 PLUS II Firmware Download Module Troubleshooting Table A General Troubleshooting Condition Cause Action “Transfer cancelled by remote system” Jumper J20 not installed. End the communications session, remove power from the drive and return to Step 4 on page 2.