Honeywell C7007A Installation Instructions Manual

Flame rod holder & flame rod

Quick Links

C7007A, C7008A, C7009A Flame
Rod Holder & Flame Rod
Assemblies
The small size of these devices enable their application to
flame detection in installations where space is limited. The
holder and flame rod assemblies facilitate flame proving on
gas burners or gas-ignited oil burners which are controlled by
electronic flame safeguard systems.
• The C7007A, C7008A, and C7009A may be used with
flame safeguard controls utilizing the rectification principle
of flame detection.
• The C7007A is a small, sturdy holder for a 3/16 inch [4.8
mm] diameter flame rod (flame rod ordered separately).
• The holder is externally threaded (1/2-14 NPT) for pipe
mounting.
• A collet chuck and setscrew position a flame rod securely.
If additional support of the flame rod is required, the
C7007A extension assembly is internally threaded (1/8-27
NPT) to accept a 1/8 inch iron support pipe.
• The C7008A is a miniature flame rod assembly with a
threaded (external 1/4-18 NPT) base, snap-on cover, and
flame rod.
• The C7008A can be used without the cover and a
coverless model is available.
• The C7008A is available with several lengths of flame rod.
One end of the flame rod is threaded for insertion into the
C7008A and the other end may be cut to an exact size.
• The C7009A is a smaller diameter flame rod assembly with
an externally threaded (1/8-27 NPT) base and readily
accessible Rajah electrical connection.
• The C7009A has a 12 inch (305mm) flame rod which one
end is threaded and the other capable of being cut to an
exact size.
INSTALLATION INSTRUCTIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not match the listed specifications
exactly. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
SPECIFICATIONS
Tradeline Models:
C7008A Flame Rod Assembly, straight pattern, with cover
(can be used with or without cover).
FLAME RODS
C7008A1174, 12 inch [305 mm] Kanthal A1 C7008A1182, 24
inch [610 mm] Kanthal A1 see also, Accessories.
DIMENSIONS:
See Fig. 2.
ELECTRICAL CONNECTION:
Rajah male with companion connector.
MOUNTING:
Equipped with external 1/4-18 NPT threads.
STANDARD MODELS
C7007A Flame Rod Holder.
C7008A Flame Rod Assembly:
Miniature flame rod assembly.
C7009A Flame Rod Assembly: small diameter flame rod
assembly.
MOUNTING MEANS:
C7007A-external 1/2-14 NPT for pipe mounting.
C7008A-external 1/4-18 NPT for pipe mounting.
C7009A-external 1/8-27 NPT for pipe mounting.
FLAME ROD:
C7007A-Not furnished, refer to ACCESSORIES.
C7008A-Kanthal in 6, 12, 18, 24 inch [152, 305, 457, 610 mm]
lengths.
C7009A-Kanthal in 12 inch [305 mm] lengths.
SIL
3
Capable
60-2024-06
loading

Summary of Contents for Honeywell C7007A

  • Page 1 ELECTRICAL CONNECTION: • The C7007A is a small, sturdy holder for a 3/16 inch [4.8 Rajah male with companion connector. mm] diameter flame rod (flame rod ordered separately). • The holder is externally threaded (1/2-14 NPT) for pipe MOUNTING: mounting.
  • Page 2 C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES ELECTRICAL CONNECTION: C7007A-Terminal screw. [56] C7008A and C7009A-Rajah male, with companion connector. [49] [28] SIL 3 Capable: The C7008 or C7009 when used with a R7847B Ampli-check amplifier in Relay Module EC7810A, 20A, 30A, 40L, 50A;...
  • Page 3: Installation

    C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES INSTALLATION CAUTION Wrong position will provide inadequate pilot WARNING flame. Read these instructions carefully. Failure to follow WRONG POSITION OF ROD them could damage the product or cause a hazardous condition.
  • Page 4: Flame Grounding

    C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES When the flame rod has been properly positioned, weld or cement the pipe and/or flange permanently. Mount and screw C7009A the unit into the adapter pipe and tighten. FLAME ROD...
  • Page 5: Flame Rod Replacement

    C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES Protect the leadwire from excessive radiant or reflected heat. The Honeywell BCS 7700 and 7800 SERIES controls provide If any portion of the wire will be exposed to temperatures in for a voltage flame signal measurement.
  • Page 6 C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES POSITIVE (+) METER LEAD ONE MEGOHM/VOLT NEGATIVE (-) METER METER LEAD M7382 Fig. 12. Measuring 7800 SERIES controls flame signal voltage. 60-2024—06...
  • Page 7 C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES 60-2024—06...
  • Page 8 C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2011 Honeywell International Inc. 60-2024—06 M.S. Rev. 06-11 customer.honeywell.com Printed in U.S.A.

This manual is also suitable for: