Protection Control

4.2 Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
In heating operation [R-410A]
Pe<0.17MPa
Low pressure limited
56
Low pressure not limited
INV upper limit frequency :
3-step down from current
compressor frequency
Pe<0.17MPa
After 10 sec.
Current step limited
Pe>0.20MPa
After 15 sec.
INV upper limit frequency :
1-step up from current
compressor frequency
Pe< 0.07MPa
Low pressure
standby
Pe: LP pressure sensor detection
value
• Pe>2.3MPa
or
Reach INV freq = MAX INV freq for each HP
When occurring 3 times within 30 min., the
malfunction code "E4" is output.
ESIE09-08B
Hot gas SVP = OFF
Pe<0.12MPa
Pe>0.17MPa
Hot gas SVP = ON
Function