This publication contains new and updated information as indicated in the following table.
Topic
Added voltage code B to the Jumper Locations and Settings table
PowerFlex® 750-Series drives contain protective MOVs (metal-oxide varistors) and Common Mode Capacitors referenced to ground. To guard
against unstable operation and/or damage, the drive must be properly configured as shown in the tables on
R/L1
S/L2
T/L3
ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the
noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or
Installation Instructions Original Instructions PowerFlex 750-Series Power Jumpers Catalog Numbers 20F, 20G, 21G Topic Page Summary of Changes Precautions Power Jumper Configuration Jumper Installation, Removal, and Storage Jumper Locations and Settings Summary of Changes This publication contains new and updated information as indicated in the following table.
PowerFlex 750-Series Power Jumpers Precautions Before proceeding, verify that all power to the drive has been removed. Qualified Personnel ATTENTION: Allow only qualified personnel familiar with adjustable frequency AC drives and associated machinery to plan or implement the installation, start- up, and subsequent maintenance of the system.
Page 3
PowerFlex 750-Series Power Jumpers Recommended Power Jumper Configurations – Frames 1…7 (1) (2) Jumper PE-A Jumper PE-B Power Source Type Benefits of Correct Configuration on Power Source Type (DC Bus Common Mode Caps) (MOV / Input Filter Caps) Non-solid Ground •...
PowerFlex 750-Series Power Jumpers Jumper Installation, Removal, and Storage Jumper screws (Frames 2…5), wires (Frames 1, 6 & 7), or plugs (Frames 8…10) are used to complete an electrical connection when installed/connected. When power jumper screws are not used, they are stored on the left interior chassis wall as shown.
PowerFlex 750-Series Power Jumpers Jumper Locations and Settings The following pages show jumper locations and settings. Jumper Locations and Settings Factory Default Jumper Settings Frame Power Source Type Catalog Code ‘A’ Catalog Code ‘J’ PE-A jumper wire PE-A jumper wire and Solid Ground connected to ground.
Page 6
PowerFlex 750-Series Power Jumpers Jumper Locations and Settings (Continued) Factory Default Jumper Settings Frame Power Source Type Catalog Code ‘A’ Catalog Code ‘J’ PE-A Installed PE-A Installed Solid Ground PE-B Not Installed PE-B Installed Install jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and ‘PE-B’...
Page 7
PowerFlex 750-Series Power Jumpers Jumper Locations and Settings (Continued) Factory Default Jumper Settings Frame Power Source Type Catalog Code ‘A’ Catalog Code ‘J’ 8…10 PE-A1 & PE-A2 PE-A1, PE-A2, and PE-B Solid Ground Non-Solid Ground connected to ground. connected to ground. Connect the MOV jumper wire (PE-A1), Input Filter Cap Insulate/disconnect the MOV jumper wire (PE-A1), Input Filter Cap PE-B jumper plug...
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, PowerFlex, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400...