Honeywell XIO-8AI Installation Instructions Manual

Honeywell XIO-8AI Installation Instructions Manual

Compact i/o module universal analog input module

Quick Links

Compact I/O Module
XIO-8AI UNIVERSAL ANALOG INPUT MODULE
GENERAL
The Honeywell XI0-8AI Universal LON
is a LON module with 8 configurable temperature or voltage
inputs to record temperatures and voltages of passive and
active sensors for example, electrical ventilation and mixing
valves, valve positions etc. The recorded counted
measurands are produced in different formats. Temperature,
resistance, percentage and voltage can be read out
depending on the setting for each input, and bound to other
®
LonMark
devices. The setting of sensor characteristics and
measuring ranges are done by LNS
voltage for active sensors can be provided by the module.
SPECIFICATIONS
Electrical Ratings:
Supply Operating Voltage: 20 to 28 V AC/DC.
Current Consumption: 57 mA (AC) / 30 mA (DC).
Duty cycle: 100%.
Recovery time: 550 ms.
Terminal Blocks:
Supply and Bus: 16 AWG (1.5 mm
(Terminal block and strapping plug included in packing).
Analog Inputs: 14 AWG (2.5 mm
®
Analog Input Module
®
-Plugin. The supply
2
).
2
).
INSTALLATION INSTRUCTIONS
LON Interface:
Transceiver: FTT10A free topology.
Neuron: 3150, 64k Flash.
Data format: standard network variables (SNVT).
Transmission rate: 78 kBit/s.
Maximum Length:
line topology 8858 ft. (2700 m) / 64 nodes.
free topology 1640 ft. (500 m) / 64 nodes.
Cabling: twisted pair.
Temperature Ratings:
Operating: 23° F to 131° F (-5° C to +55° C).
Storage: -4° F to +158° F (-20° C to +70° C).
Dimensions (W x H x D):
2.0 x 2.7 x 2.6 in. (30 x 68 x 65 mm).
Weight: 4.4 ounces (126 g).
Mounting Position: Any.
Mounting: DIN rail per EN 50022.
Input:
Temperature Range: selectable.
NOTE: Temperature input for all sensors is in the range of
40 Ω up to 4 MΩ.
Resolution: 0.2 K.
Error: approximately ± 0.4° F (±0.2° C).
Voltage input: 0 to 10 V DC.
Resolution: 10 mV (0.0 to 100%).
Error: approximately ±100 mV.
Construction Material:
Housing and Terminal Blocks: Polyamide 6.6 V0.
Faceplate: Polycarbonate.
Protective Circuitry:
Operating Voltage: polarity reversal protection.
Protection:
IP40 housing DIN 40050.
IP20 terminal blocks DIN 40050.
Approvals:
UL 916, Standard for Energy Management Equipment.
European Community Mark (CE) Listed.
95-7716—1
Table of Contents
loading

Summary of Contents for Honeywell XIO-8AI

  • Page 1 Compact I/O Module XIO-8AI UNIVERSAL ANALOG INPUT MODULE INSTALLATION INSTRUCTIONS LON Interface: Transceiver: FTT10A free topology. Neuron: 3150, 64k Flash. Data format: standard network variables (SNVT). Transmission rate: 78 kBit/s. Maximum Length: line topology 8858 ft. (2700 m) / 64 nodes.
  • Page 2: Safety Instructions

    M25040 M25064 a. Remove about 0.75 in. (2 cm) of the plastic cable Mount the XIO-8AI Universal LON Analog Input Module on sheath. standard DIN rail per DIN EN 50022 (1.35 x 0.3 in. [35 x b. Strip 0.2 in. (5 mm) insulation from each wire. Put a 7.5 mm]), in junction boxes and/or on distribution panels.
  • Page 3 COMPACT I/O MODULE TERMINATION 4. Prepare cable for module connections. Fig. 1 shows the termination points of the XIO-8AI. 0.3 in. (7 mm) +24V E-bus 1 FTT-10A +24V 24 V AC/DC +24V E-bus 2 Inputs: voltage 0-10 V E-bus 1...
  • Page 4: Jumper Positions

    XIO-8AI WIRING 8 5 2 6 7 2 7 0 7 6 Wiring of the XIO-8AI must be accomplished in accordance with federal, state, and local requirements. Figures 4 through 6 show sample diagrams of wiring of the XIO-8AI. JUMPER IN BOTTOM POSITION (FACTORY DEFAULT), 15 VDC OUTPUT.
  • Page 5: Software Description

    Sensor nvoVoltage_1 - 8 SNVT_volt_f +10 to +20V M25070 nvoResistance_1 - 8 SNVT_res_f Fig. 6. Wiring example XIO-8AI with sensor. nvoHigh_1 - 8 SNVT_switch SOFTWARE DESCRIPTION nvoLow_1 - 8 SNVT_switch The Node Object monitors and controls the functions of the different objects in the device.
  • Page 6 COMPACT I/O MODULE nvoHigh_1...8 SNVT_switch nvoLow_1...8 SNVT_switch When exceeding the temperature set in UCPTHighT the When under-running the temperature set in UCPTLowT the output variable changes from 0,0 0 to 100,0 1. When under- output variable changes from 0,0 0 to 100,0 1. When running the temperature set in UCPTHighT plus the hysteresis exceeding the temperature set in UCPTLowT plus the set in UCPTHyst the output variable changes from 100,01 to...
  • Page 7 COMPACT I/O MODULE 95-7716—1...
  • Page 8 COMPACT I/O MODULE By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...