YASKAWA V1000 Quick Start Manual
Hide thumbs Also See for V1000:

Quick Links

V1000 AC Drive
Quick Start Procedure
Step
V1000 Model Identification and
1
OVERVIEW
The following
To make sure you received the correct model it is
procedure is a
essential to verify the V1000 nameplate with your order;
and make sure that the drive has the correct rating so it
supplement to other
can be used with your motor. Please check the nameplate
information as shown in the example below.
documentation
supplied with this
equipment and will
guide the user in
properly wiring the
V1000 and motor. It
will also allow the
installer to check
motor direction,
x
Check that the available power meets the input power
requirements.
correct if necessary
x
Ensure that the output power from the VFD is
and perform a motor
compatible with the motor requirements.
Auto-Tune.
x
In the case of systems with multiple VFDs, follow the
above procedure for each VFD and motor.
DANGER! Improper
wiring can and will
Mounting the V1000
cause bodily harm as
The mounting of the V1000 is extremely important regarding
well as damage
environment and accessibility. Depending on your system,
there are various models available and the mounting
to the equipment.
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document, the user is referred to the V1000 Quick
When installing the
Start Guide (Manual No. TOEPC71060614) received with the
V1000, Section 1 Physical Installation. Match the model
system be sure to
that you received and follow the procedure described in the
follow good wiring
manual to ensure a safe and functional installation. In cases
where the system has more than one V1000, refer to the
practices and all
proper clearances required for adequate ventilation. Please
applicable codes.
pay particular attention to:
Ensure that the
x
The clearances to be maintained around the enclosure
for adequate ventilation.
mounting of the
x
various components
The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
are secure and that
exposure, corrosive areas etc. to avoid damage to the
equipment and to maintain safety.
the environment,
such as extreme
Removing Protective Covers
dampness, poor
Improper removal of the V1000 protective covers, as well as
ventilation etc. will
the conduit bracket (NEMA 1) can cause extensive damage
not cause system
to the V1000. To avoid damage to these items, please pay
particular attention to the V1000 Quick Start Guide,
degradation.
Section 3, Protective Covers.
Please read this
document and other
documentation
provided with the
V1000 thoroughly
before attempting any
installation.
Open Chassis
YAI Document Number: TM.V1000.01 03/25/2013 © Yaskawa America, Inc. - (800) YASKAWA (927-5292)
Step
Connect Motor and
2
Mounting
Fig.1 & 2 below show the electrical connections for the
input power and motor terminals for various V1000 Drive
Models. Select the proper diagram for the single or three
phase model you are installing
POWER OFF, make the appropriate connections.
Make sure to follow good wiring practices and all applicable
codes. Ensure that the equipment is grounded properly as
shown.
!
DANGER:
LETHAL VOLTAGES ARE PRESENT. Before
applying power to the V1000, ensure that all protective
1012(13)
covers are fastened and all wiring connections are secure.
After the power has been turned OFF, wait at least five
minutes until the charge indicator extinguishes completely
before touching any wiring, circuit boards or components.
WARNING! DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
B1
B2
R/L1 S/L2
SINGLE PHASE
INPUT V1000
(R/L1)
(S/L2)
Connect to
motor rotation, swap any
chassis
ground
Input
Protection
(Fuse or C.B.)
L1 L2
1Ø Input Power
Fig. 1:
Input Power and Output Motor Electrical
Connections for Single Phase Input V1000
R/L1 S/L2 T/L3
THREE PHASE
INPUT V1000
(R/L1)
(S/L2)
(T/L3)
Connect to
chassis
motor rotation, swap any
ground
Input
Protection
(Fuse or C.B.)
L1 L2 L3
3Ø Input Power
NEMA 1
Fig. 2:
Input Power and Output Motor Electrical
Connections for Three Phase Input V1000
Step
Check Motor Direction
3
Line Power
In this step the motor is checked for proper direction and
operation. This test is to be performed solely from the
digital operator. Apply power to the V1000 after all the
(see Step 1) and WITH
electrical connections have been made and protective
covers have been re-attached. At this point, D D O NOT RUN
THE MOTOR, the Digital Operator should display as
shown below in Fig. 3 .
Fig. 3 Digital Operator
-
+
+1
+2
on the Digital Operator; the green LED
Next, press
should turn on.
U/T1 V/T2 W/T3
First Digit Flashing
(U/T1)
(V/T2)
(W/T3)
Next, press
on the Digital Operator once, then press
To change direction of
two of the three motor
leads (See Step 2)
.
First Digit Flashing
Connect
frame to
ground
3Ø Induction
motor
Next, press
should now be operating at low speed running in the correct forward
(clockwise) direction.
U/T1 V/T2 W/T3
Next, press
If motor rotation is not correct, then power down the V1000 Drive.
!
DANGER
(U/T1)
(V/T2)
After the power has been turned OFF, wait at least five minutes
until the charge indicator extinguishes completely before
(W/T3)
touching any wiring, circuit boards or components.
To change direction of
two of the three motor
leads (See Step 2)
Digital Operator
turned off.
Connect
frame to
ground
3Ø Induction
motor
Use precaution, and refer to Fig.1 or 2, swap any two of the three
output leads to the motor (U/T1, V/T2 and W/T3). After the wiring
change, repeat Step 3 and recheck motor direction.
Fax (847) 887-7310 [email protected]
Step
4
In this step the V1000 is setup for use with the
motor. Make sure all protective covers have been
re-attached then apply power to the V1000.
DO NOT RUN THE MOTOR.
Press
three times until the Digital Operator
REV LED
shows the Auto-Tuning menu (A.Tun) then press
OFF
.
Press
two times until the Digital Operator shows
parameter T1-02 then press
Enter Motor Power in kW (Kilowatt)
Press
to select the digit you would like to change and use the
and
to adjust the value, then press the
Press
to go to select the next parameter and follow the
same procedure described above to adjust its value.
Motor Rated Voltage (e.g. 230 V, 460 V)
Motor Rated current (e.g. 11.0 A, 22.0 A)
Motor Base Frequency (e.g. 60.0 Hz)
Motor Poles (e.g. 4 Poles)
Motor Rated Speed (e.g. 1750 rpm)
on the Digital Operator. The motor
After setting parameter T1-07 press
the Auto-Tuning start command.
!
on the Digital Operator.
Warning! Sudden movement hazard. The V1000 and motor may start
unexpectedly during Auto-Tuning.
Warning! Electric Shock Hazard. High voltage will be supplied to the motor when
stationary Auto-Tuning is performed. Do not touch the motor during auto-tuning.
Notice: Auto-Tuning will not function properly when a brake is engaged on the
load. Ensure the motor shaft can freely rotate. Never perform an Auto-Tune with
motor connected to a load.
Next, press
Auto-Tuning procedure.
The display will show
completed. Please reference the V1000 Quick Start Guide or repeat the Auto-Tuning procedure
again if the display shows an error message.
www.yaskawa.com
Page 1 of 2
Page 1 of 2
Auto-tuning
.
Digit Flashing
Motor HP to kW = HP x 0.746
Example: 10HP = 10 x 0.746 = 7.46 kW
to save the value.
For standard AC motors use
the default setting for motor
base frequency (60Hz), motor
poles (4) and motor rated
speed.
to select
on the Digital Operator; The V1000 will now start the
when the Auto-Tuning procedure has been successfully
loading