Mitsubishi Electric FX3G-2AD-BD Installation Manual page 2

Melsec-f
3.2 Wiring of Analog Input
→ For the terminal configuration, refer to Section 1.2
Using current
Terminal
2AD-BD
input
ch
block
110kΩ
V +
250Ω
*1
I
+
Grounding
88.7kΩ
Using voltage
input
ch
110kΩ
V +
250Ω
I
+
Grounding
88.7kΩ
VI-
V +, I +, ch
:
represents the channel number.
*1 Make sure to short-circuit the 'V +' and 'I +' terminals when current is
input. ( : input channel number)
3.2.1
Cautions
1) Make sure to short-circuit the 'V +' and 'VI-' terminals when ch is not used.
2) Use 2-core shielded twisted pair cable for the analog input lines, and
separate the analog input lines from other power lines or inductive lines.
3) The grounding resistance should be 100 Ω or less.
3.3 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of
the following figure.
For details, refer to the following manual.
→ FX
3S
Series User's Manual - Hardware Edition
→ FX
Series User's Manual - Hardware Edition
3G
Other
Other
PLC
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Common grounding
Best condition
Good condition
Not allowed
2
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
).
• The grounding point should be close to the PLC, and all grounding wire should
be as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the
product. After transportation, verify operation of the product and check for
damage of the mounting part, etc.
4.1 Applicable PLC
Model name
Applicability
FX
3S
Series PLC
Ver. 1.00 or later (from first production)
FX
Series PLC
Ver. 1.10 or later
3G
The version number can be checked by monitoring D8001/D8101 as the last three
digits indicate it.
• The number of connectable expansion boards varies depending on the main unit as
follows:
FX
, FX
-14M
, FX
-24M
Main units: 1 unit
3S
3G
3G
FX
-40M
, FX
-60M
Main units: 2 units
3G
3G
Other
Never stack up two or more expansion boards.
equipment
For details on the system configuration, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S
3G
3GC
3U
3UC
4.2 General Specifications
The general specifications are equivalent to the PLC main unit.
For general specifications, refer to the following manuals.
→ FX
Series User's Manual - Hardware Edition
3S
→ FX
Series User's Manual - Hardware Edition
3G
4.3 Performance Specifications
Specifications
Item
Voltage input
Analog input
0 to 10 V DC
range
(Input resistance: 198.7 kΩ)
Maximum
absolute
-0.5 V, +15 V
input
Digital output
12 bits, binary
Resolution
2.5 mV (10 V/4000)
• ±0.5 % (±50 mV) for full scale
of 10 V (when ambient
temperature is 25 °C±5 °C)
Total
accuracy
• ±1.0 % (±100 mV) for full
scale of 10 V (when ambient
temperature is 0 °C to 55 °C)
A/D
180 μs
conversion
(The data will be updated at every scan time of the PLC.)
time
4080
4000
Input
characteristics
0
10V
10.2V
Analog input
Insulation
No insulation between each channel or the PLC.
method
Occupied
0 point (This number is not related to the maximum number of input/
points
output points of the PLC.)
4.4 List of Special Devices
Device number
FX
3G
FX
3S
Board A Board B
M8260 M8260 M8270
Special
auxiliary
relay
M8261 M8261 M8271
D8260
D8260
D8261
D8261
D8264
D8264
D8265
D8265
Special
data
register
D8268
D8268
D8269
D8269
*1 Only available for FX
PLCs.
3S
The under scale detection function is valid only for current input mode.
As for the details of the special devices, refer to following manual.
→ FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
5. 「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
 本产品中所含有的有害6 物质的名称, 含有量, 含有部品如下表所示。
Current input
产品中有害物质的名称及含量
4 to 20 mA DC
(Input resistance: 250 Ω)
部件名称
-2 mA, +30 mA
(Pb)
11 bits, binary
外壳
可编程
8 μA (16 mA/2000)
控制器
印刷基板
×
• ±0.5 % (±80 μA) for full scale
of 16 mA (when ambient
本表格依据SJ/T 11364的规定编制。
temperature is 25 °C±5 °C)
• ±1.0 % (±160 μA) for full
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定
scale of 16 mA (when
的限量要求以下。
ambient temperature is 0 °C
to 55 °C)
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
2040
2000
0 4mA
20mA 20.32mA
Analog input
R: Read W: Write
Description
R/W
Switches the input mode of channel 1
R/W
OFF: Voltage input
ON: Current input
Switches the input mode of channel 2
R/W
OFF: Voltage input
ON: Current input
D8270 Channel-1 input data
R
D8271 Channel-2 input data
R
Averaging time for channel-1
D8274
R/W
(Setting range: 1 to 4095)
Averaging time for channel-2
D8275
R/W
(Setting range: 1 to 4095)
Error status
b0: Channel-1 over-scale detection
b1: Channel-2 over-scale detection
b2: Unused
b3: Unused
b4: EEPROM error
D8278
R/W
b5: Averaging time setting error
b6: 2AD-BD hardware error
b7: 2AD-BD communication data error
*1
b8: Channal-1 under-scale detection
*1
b9: Channal-2 under-scale detection
b10 to b15: Unused
D8279 Model code = 3
R
Series User's Manual - Analog Control Edition
3UC
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
For safe use
loading