Control Functions
6.8 Transformer Tap Changers
Parameter: Number of tap positions
Default setting Number of tap positions = 15
With the Number of tap positions parameter, you set the number of transformer taps. The range of
values extends from 2 to 127. The output of the tap position is limited from -63 to +63. If the number of taps
is > 63, set the Tap-display offset parameter so that the output of the tap position is within the range of
-63 to +63.
Parameter: Tap-coding type
Default setting Tap-coding type = binary
In the Tap-coding type list box, select the interpretation type of the indication pending at the binary input.
You can select from the following options:
binary
1-of-n
BCD
table
BCD signed
gray
A selection of tap-coding types is described in greater detail using examples in the following text.
Routing of the Binary Inputs (Tap-Coding Type binary)
The following table shows the routing of 3 binary inputs (BI 1 to BI 3) with 4 transformer tap positions desig-
nated 3 to 6. BI4 is the moving contact. The encoding is in binary.
Table 6-25
Tap changer
Meaning
Tap = 1
With 3 binary inputs, a maximum of 2
inputs indicate 0, this is interpreted as a connection error and is reported by Position --- or -64 with quality
invalid. The representation of transformer taps should start with the metered value 3. You must configure the
information properties as follows for the example:
Tap-coding type:
Number of tap positions:
Number of bits f. tap code:
Tap-display offset:
Moving contact (highest binary input):
The 3 binary inputs must be numbered sequentially, for example, BI 1, BI 2, BI 3, and BI 4 for the moving
contact.
Routing of the Binary Inputs (Tap-Coding Type BCD)
The following table shows the routing of 6 binary inputs (BI 1 to BI 6) with 39 transformer tap positions desig-
nated 1 to 39. The encoding is in BCD. BI 7 is the moving contact.
444
Routing of the Binary Inputs (Tap-Coding Type binary)
Example
BI1
BI2
X
X
Bit 1
Bit 2
1
0
3
-1 = 7 tap positions can be mapped in binary code. If all routed binary
BI3
BI4
X
X
Bit 3
Moving
contact
0
binary
7
4
2
Yes
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017