socomec NET-VISION Operating And Installation Manual
socomec NET-VISION Operating And Installation Manual

socomec NET-VISION Operating And Installation Manual

Version 7
Hide thumbs Also See for NET-VISION:
Table of Contents
NET-VISION
Version 7
GB
www.socomec.com
Table of Contents
loading

Summary of Contents for socomec NET-VISION

  • Page 1 NET-VISION Version 7 www.socomec.com...
  • Page 2: Table Of Contents

    3.2. SOCOMEC UPS COMPATIBILITY ........
  • Page 3 21.5. CLEAR & SAVE LOG DATA ..........58 NET-VISION 7 - SOCOMEC...
  • Page 4 Anyone entering into possession of the software without prior authorization from SOCOMEC must immediately uninstall it, if it has been installed and return it to SOCOMEC. If such persons fail to take this action SOCOMEC will exercise its rights to the full extent permitted by civil and criminal law.
  • Page 5: Electronic Emission Notice

    • Before maintenance, repair or shipment, the unit must be switched off completely and un- plugged and all connections removed. • Before plugging in the Net Vision power adaptor, please make sure the power source rating matches the Net Vision power adaptor rating. NET-VISION 7 - SOCOMEC...
  • Page 6: General Description

    The remote shutdown is provided by a client shutdown to be installed on all standalone servers (JNC) or on a virtual machine (VIRTUAL-JNC) that require this automatic function. JNC and VIRTUAL-JNC are shutdown agent software available for free on SOCOMEC’s web site or on the NET VISION CD.
  • Page 7: Net Vision 7 Features

    • HTTP / HTTPs with certificate • DHCP / BOOTP • SNMP v1 / v2c / v3 (MD5-SHA / DES-AES) • SMTP over TLS • SSH • UPnP • NTP / ICMP • WOL • RADIUS • TFTP • SYSLOG NET-VISION 7 - SOCOMEC...
  • Page 8: Requirements

    • DELPHYS MP / MP elite + / EM / MX: 9600bds, no parity, slave 1: COM-Slot 5 only • DELPHYS BC / GP / GP2.0 / Xtend: 9600bds, no parity, slave 1: COM-Slot 2 only NET-VISION 7 - SOCOMEC...
  • Page 9: Net Vision 7 Boot Sequence

    At 9600 bauds, the polling time for 1 unit is around 3 seconds. This polling time is to be multiplied by the number of units present in the system in order to have a global time of data refreshing. NET-VISION 7 - SOCOMEC...
  • Page 10: Ups Data Base

    • Module – without bypass • Modular Unit up to 8 modules • Parallel system, distributed bypass or centralized bypass, up to 6 Units (JBUSP) and 10 Units (VU-MAP) • Modular system up to 3 Units – 24 modules. NET-VISION 7 - SOCOMEC...
  • Page 11: Net Vision Explorer Presentation

    8.1. IP SETTINGS (only for NV 7) Click on to open the IP settings window: Connection must be unlocked to change IP settings 8.2. BROWSE Click on to start the web browser and open the NET VISION home page. NET-VISION 7 - SOCOMEC...
  • Page 12: Fw Upgrade

    8.5. BATCH OPERATION Click on to open the batch operation window Batch operation selection: FW update Config file upload 8.6. SUPGRADE.ExE TOOL The Supgrade.exe tool used for NET VISION 6 does not recognize the NET VISION 7 Card. NET-VISION 7 - SOCOMEC...
  • Page 13: Ip Address Configuration

    9.6. IP SETTINGS USING A TERMINAL AND USB for NET VISION 7 The USB Gadget Serial driver must be installed. Please refer to the APPENDIX. Once the device is recognized, open an SSH terminal connection to modify IP settings. NET-VISION 7 - SOCOMEC...
  • Page 14: Net Vision 6 Functions

    The RESET button does not affect the Net Vision settings, it only restarts Net Vision. Make sure that the IP given by the DHCP server remains the same as before the Net Vision RESET. NET-VISION 7 - SOCOMEC...
  • Page 15: Net Vision 7 User Interface

    12. NET VISION 7 USER INTERFACE 12.1. NET VISION HOME PAGE NET VISION reference UPS Reference Shortcut access Login NET VISION MENU UPS tree-view UPS SYNOPTIC Parameters table NET-VISION 7 - SOCOMEC...
  • Page 16: Net Vision Menu

    “Special day schedule” If “special day” is selected in shutdown event If “Power share” function is present and remote “Power share” controls are enabled by UPS “EMD device” If the EMD device is connected to NET VISION NET-VISION 7 - SOCOMEC...
  • Page 17 Pages are present if services or protocols “Modbus TCP Config” have been enabled in “Syslog Setup” Protocol pages settings NET VISION Control page. “DDNS Setup” “Firewall Setup” To add hyperlink for network devices access “External Links Setup” NET-VISION 7 - SOCOMEC...
  • Page 18 (%) if EMD connected 12.2.5. External Link An extra menu is present if devices have been activated. These links give direct access to other devices. It automatically opens a new page in the web browser with the selected link. NET-VISION 7 - SOCOMEC...
  • Page 19: Ups Architecture Tree-View

    UNIT VIEW FOR SINGLE, MODULAR OR UNITS AS PART OF A PARALLEL SYSTEM This view gives details of rectifier and bypass inputs supply, battery status and unit output pa- rameters. NET-VISION 7 - SOCOMEC...
  • Page 20: User Login

    “Read Only” ac- cess mode. NET VISION does not allow more than one admin session. If an admin session is still open, a new session that is opened forces the logout of the previous admin session. NET-VISION 7 - SOCOMEC...
  • Page 21: Ups Monitoring

    The output load rate value is reported to synoptic. The load value is not displayed if the mainte- nance bypass is closed. During battery charging and battery charged status, the battery capacity value in % is displayed. The capacity value is replaced by the remaining backup time when the battery is discharging. NET-VISION 7 - SOCOMEC...
  • Page 22 If one or more alarm is present, clicking on opens the alarm table. The icon flashes when a new alarm is incoming. In this situation, it opens the alarm page, resets all alarms and stops the audible alarm on UPS. NET-VISION 7 - SOCOMEC...
  • Page 23 “Remaining backup time (mn)” “Battery voltage (V)” “Temperature (°C)” UPS ambiance temperature “date / time” “EMD Parameters” “EMD temperature (°C)” “EMD humidity (%)” Only if “EMD” device is connected to NET VISION “EMD Alarm 1” “EMD Alarm 2” NET-VISION 7 - SOCOMEC...
  • Page 24 “Load OFF” Per phase “Output load rate (%)” Present if computed by UPS “Output Power (kVA)” Present if computed by UPS “Output Power (kW)” Per phase “Output Current (A)” Per phase “Output Voltage (V)” “Output Frequency (Hz)” NET-VISION 7 - SOCOMEC...
  • Page 25 13.1.10. INVERTER PARAMETERS TABLE “Inverter Parameters” Per phase. Set to 0 if inverter is off “Inverter Voltage (V)” Present if computed by UPS “Inverter Compound Voltage (V)” Set to 0 if inverter is off “Inverter Frequency (Hz) NET-VISION 7 - SOCOMEC...
  • Page 26: System Synoptic

    See “ Unit/UPS Parameters Table” 13.2.4. UPS OUTPUT PARAMETERS TABLE The table is updated with data read from the UPS at System level, which is a combination from all Unit data. See UPS “ Output Parameters Table” NET-VISION 7 - SOCOMEC...
  • Page 27: Alarm Table

    Alarm Table Number of Active Alarms Last Alarm General Alarm Index Alarm Time UPS Alarm Description Level Axxx Information dd/mm/yyyy hh:mm:ss Warning Critical For a parallel UPS system, the table shows only active alarms at system level. NET-VISION 7 - SOCOMEC...
  • Page 28: Ups Dashboard

    Output currents are represented in bar-graph. The vertical line defines the nominal amps limit. During battery discharging, remaining backup time is displayed Go back to synoptic; For a parallel UPS system, the measurements shown are values read from system level. NET-VISION 7 - SOCOMEC...
  • Page 29: Real Time Graph

    NET VISION Client Table Connected Client Number Index IP Address Client Name Connected Time 192.168.1.2 IT Server (JNC) 2017/04/08 11:17:18 NET-VISION 7 - SOCOMEC...
  • Page 30: Ups Management

    UPS. “Disabled standby mode” “Alarm Acknowledgement” Always present For parallel UPS systems, the controls are sent to the system and dispatched to all the units present. NET VISION does not allow sending controls unit by unit. NET-VISION 7 - SOCOMEC...
  • Page 31: Battery Test

     Only if remote … controls are … Sunday enabled by For parallel systems with distributed battery, the battery test schedule can be programmed unit by unit. Each battery test will be started at different time. NET-VISION 7 - SOCOMEC...
  • Page 32: Eco Mode Schedule

    … Sunday 17.6. SPECIAL DAY SHUTDOWN SCHEDULE This function is activated if the “Special Schedule” event is enabled in the “event shutdown man- agement” page. Special Schedule Index SHUTDOWN period RESTART period 01/01/2017 00:00 01/01/2017 00:00 NET-VISION 7 - SOCOMEC...
  • Page 33: Power Share

    Emergency lighting: switches the output plug to ON when the UPS is on battery. PLUGS CONTROL Select to close or unselect to open the plugs then apply. Plugs are immediately opened or closed according the control sent. NET-VISION 7 - SOCOMEC...
  • Page 34: Shutdown Management

    WARNING! Make sure that the UPS shut-off time period is longer than the total time period for the shutdown procedure for the Server / Hosts supplied by the UPS. See shutdown process paragraph for more details. NET-VISION 7 - SOCOMEC...
  • Page 35 The Shutdown agent can start running scripts or batch files before the OS shutdown. UPS shutdown delay must be greater than the server’s shutdown time, evaluated as the shutdown delay set on the agent + OS shutdown itself. NET-VISION 7 - SOCOMEC...
  • Page 36 UPS status. The agent is then ready for the shutdown procedure again. During the test, the button is disabled and switches to ‘enabled’ when the ‘shutdown cancel’ command is sent to servers. WARNING! If the Warning period = 0, the server shutdown command is sent immediately. NET-VISION 7 - SOCOMEC...
  • Page 37: Emd Device Management

    Sensor Name Set Point (Low) Set Point (High) Calibration  Temperature (°C) 18.0 30.0  Humidity (%) 10.0 80.0  Normal Open Alarm-1 Normal Closed  Normal Open Alarm-2 Normal Closed  Disabled EMD Status Auto NET-VISION 7 - SOCOMEC...
  • Page 38: Net Vision Management

    Set manually Date (dd/mm/yyyy): 01/01/2017 Time (hh:mm:ss): 00:00:00 In case of using NTP synchronisation GMT and daylight management are to set according NTP server configuration. GMT time zone and daylight are often managed by NTP server itself. NET-VISION 7 - SOCOMEC...
  • Page 39: Net Vision Configuration

    “IPv6 Configuration” Automatic Select the IPv6 mode “IPv6 Local Address” fe80::2e0:d8ff:feff:c1a0/64 To be set according to IPv6 settings “IPv6 Global Address” To be set according to IPv6 settings “IPv6 Router” To be set according to IPv6 settings NET-VISION 7 - SOCOMEC...
  • Page 40: Net Vision Control

    NET VISION must be installed on each Unit. This function enable or disable TRAP3 and TRAP4 notifica- “SNMP TRAP / E-mail Filter” Disabled tion when “ ” level is set as filter to send TRAP or severity e-mail. NET-VISION 7 - SOCOMEC...
  • Page 41: Multi-User Table

    Remote View Pro SW sees NET VISION as a communication node server. NET VISION must be added on Remote View Pro accordingly. Remote View Pro Configuration  Disabled Server Control Enabled Server IP Server Port GUID NV MAC address Password To set NET-VISION 7 - SOCOMEC...
  • Page 42: Remote View Pro Server Configuration

    This function is available from Remote View Pro v2.x version. Previous release has to be up- dated with last package available on SOCOMEC’s WEB page. A new licence is not needed if already installed. The configurations are reported in the new release during installation setup.
  • Page 43: Snmp V3 Usm Table Configuration

    Trap Version Event Filter Severity address String    Information None By Severity Warning RFC1628 Critical NET VISION TRAP By Event For SNMP v3 Trap Version, the USM table must be set according to the NMS configuration. NET-VISION 7 - SOCOMEC...
  • Page 44 EMD Sensor detected low temperature. TRAP 28 EMD Sensor detected low humidity. TRAP 32 EMD input1 is active. TRAP 36 EMD Sensor detected high temperature. TRAP 30 EMD Sensor detected high humidity. TRAP 34 EMD input2 is active. TRAP 38 NET-VISION 7 - SOCOMEC...
  • Page 45: Email Notification

    Index Mail account Description Mail Type Event Filter Event Level  None  Information Events By Severity Warning Daily status Critical Events/status  None By Event Note: the e-mail address length is limited to 64 characters. NET-VISION 7 - SOCOMEC...
  • Page 46: Authentication Configuration

    Packet Timeout Packet Retry Note: This service allows all users set in the RADIUS server to login to NET VISION with Read/Write permission. MULTI-USER TABLE To be used for changing the RADIUS user’s rights for NET VISION. NET-VISION 7 - SOCOMEC...
  • Page 47: Wol Targets

    This page enables or disables the MODBUS TCP protocol; the MODBUS Port can be changed. Modbus Configuration  Enabled Modbus TCP Configuration Disabled Modbus Port Refer to Annex for UPS data access through MODBUS TCP protocol. NET-VISION 7 - SOCOMEC...
  • Page 48: Syslog Setup

    The user name and password must be created with the selected DDNS provider. DDNS Setup DDNS State Disabled / Failed / Pass  Enabled DDNS Control Disabled  ezip pgpow DDNS ISP setup dyndns dyndns-stat easydns User Name Password DDNS Domain name NET-VISION 7 - SOCOMEC...
  • Page 49: Firewall Setup

    UPnP (Universal Plug and Play) protocol allows NET VISION to be managed as device network from a remote computer. The user interface can be opened clicking on the NET VISION device icon. The NET VISION is present in the device network list as bellow. NET VISION network device properties : NET-VISION 7 - SOCOMEC...
  • Page 50: External Link Setup

    The hyperlink includes the IP address set as Link Address External Links Setup Index Screen Text Link Address Status Disabled Enabled  Disabled Example: Click on the link to open a new page in the web browser. NET-VISION 7 - SOCOMEC...
  • Page 51: History Log

    UPS information: includes UPS temperature and battery capacity UPS History Graphic Show Specific Period  Records 30 minutes 60 minutes 3 hours 6 hours 12 hours 1 day Show dd/mm/yyyy dd/mm/yyyy Records Input information Output information UPS information NET-VISION 7 - SOCOMEC...
  • Page 52 If an EMD device is connected, the temperature and humidity measurements are added in the table. Maximum number of records: 2048 If the sample is set to 1 minute, the complete time window offers a view of 2048 minute (~1 day and 18 minutes) NET-VISION 7 - SOCOMEC...
  • Page 53: Ups Extended History Log

    Specific Period  Records 30 minutes 60 minutes 3 hours 6 hours 12 hours 1 day Show dd/mm/yyyy dd/mm/yyyy Records Input information Output information UPS information The graphs represent the minimum, average and maximum values of each measurement. NET-VISION 7 - SOCOMEC...
  • Page 54 If an EMD device is connected, the temperature and humidity measurements are added in the table. Maximum number of records: 2048 If the sample is set to 1 hour, the complete time window is a view of 2048 hours (~85 days and 8 hours) NET-VISION 7 - SOCOMEC...
  • Page 55: Ups Events Log

    Inverter General Al. Load off Bypass Critical Alarm UPS shut off sent Bypass Preventive Alarm Bypass General Al. Standby schedule sent Bypass Input Supply not OK Eco mode schedule sent Phase Rotation fault Maintenance Bypass Alarm FAN Failure NET-VISION 7 - SOCOMEC...
  • Page 56: Net Vision Events Log

    Send UPS output on command to UPS UPS communication lost UPS communication restored ??? Time changed by user ??? Time changed by server ??? Time changed by RTC Cannot connect to mail server Incorrect Mail receiver NET-VISION 7 - SOCOMEC...
  • Page 57 EMD Humidity not over high Set point EMD Humidity over high Set point EMD Humidity not under low Set point EMD Humidity under low Set point EMD Alarm-1 not active EMD Alarm-1 activated EMD Alarm-2 not active EMD Alarm-2 activated NET-VISION 7 - SOCOMEC...
  • Page 58: Clear & Save Log Data

    Clear Log Data NET VISION Events Log UPS Events Log UPS Extended Log UPS History Log stored files Click on to store the file on a local computer Clear logs Select which Log to clear and click on NET-VISION 7 - SOCOMEC...
  • Page 59 3.1.2 upsInputVoltage ###.# V 3.1.3 upsInputCurrent ###.# A (*) 3.1.4 upsInputVoltageMax ###.# V 3.1.5 upsInputVoltageMin ###.# V General rule: In case measurements not managed by UPS the related IOD value is set at -1 or 65535. NET-VISION 7 - SOCOMEC...
  • Page 60 (*) measurements are set to a value of -1 if the measurement is not managed upsBypass(5) Variables Values upsBypassFrequency Format ##.# Hz upsBypassNumLines 3 for 3 phase UPS upsBypassTable/upsBypassEntry/ .1.3.6.1.4.1.4555.1.1.7.1.5 upsBypassLineIndex upsBypassVoltage ###.# V upsBypassCurrent ###.# A (*) NET-VISION 7 - SOCOMEC...
  • Page 61 3.34 upsAlarmUPSPowerOffActive A059 3.35 upsAlarmWrongConfiguration A060 3.36 upsAlarmInternalFailure A061 3.37 upsAlarmOptionalBoards A062 3.38 upsAlarmExternalAlarm1 A064 3.39 upsAlarmExternalAlarm2 A065 3.40 upsAlarmExternalAlarm3 A066 3.41 upsAlarmExternalAlarm4 A067 3.42 upsAlarmModule1Alarm A096 3.43 upsAlarmModule2Alarm A097 3.44 upsAlarmModule3Alarm A098 3.45 upsAlarmModule4Alarm A099 NET-VISION 7 - SOCOMEC...
  • Page 62 4.1.5 upsControlWarningInterval upsControlWeeklyScheduleTable 5.1.1 upsControlWeeklyIndex .1.3.6.1.4.1.4555.1.1.7.1.7 5.1.2 upsControlWeeklyShutdownDay 5.1.3 upsControlWeeklyShutdownTime 5.1.4 upsControlWeeklyRestartDay 5.1.5 upsControlWeeklyRestartTime upsControlSpecialScheduleEntry 6.1.1 upsControlSpecialIndex 6.1.2 upsControlSpecialShutdownDay 6.1.3 upsControlSpecialShutdownTime 6.1.4 upsControlSpecialRestartDay 6.1.5 upsControlSpecialRestartTime upsControlEcoModeScheduleTable 7.1.1 upsControlEcoModeIndex 7.1.2 upsControlEcoModeStartDay 7.1.3 upsControlEcoModeStartTime 7.1.4 upsControlEcoModeEndDay 7.1.5 upsControlEcoModeEndTime NET-VISION 7 - SOCOMEC...
  • Page 63 .1.3.6.1.4.1.4555.1.1.7.1.9 upsAgentResetToDefault upsAgentRestart upsAgentClearAgentLog upsAgentClearEventLog upsAgentClearExtHistoryLog upsAgentClearHistoryLog upsAgentTrapsReceiversTable/upsAgentTrapsReceiversEntry 21.1.1 trapsIndex 21.1.2 trapsReceiverAddr 21.1.3 receiverCommunityString 21.1.4 receiverNmstype upsAgentAccessControlTable/upsAgentAccessControlEntry upsAgentMibVersion upsAgentTrapString emdStatus(10) Variables emdStatusTemperature emdStatusHumidity .1.3.6.1.4.1.4555.1.1.7.1.10 emdStatusIn1Active emdStatusIn2Active NET-VISION 7 - SOCOMEC...
  • Page 64 TRAP3: sent every time a new alarm is added to the list. The alarm index sent as parameters follows the well-known alarm index OID. TRAP4: sent every time when an alarm is removed from alarm list. The alarm index is the same as sent with TRAP3. NET-VISION 7 - SOCOMEC...
  • Page 65 !S02 & !S03 & !S04 !S049 & !S52 & !S57 upsAlarmFanFailure A054 upsAlarmFuseFailure Not available upsAlarmGeneralFault A015 upsAlarmDiagnosticTestFailed A022 Battery test failed upsAlarmCommunicationsLost NV alarm upsAlarmAwaitingPower Shutdown agent upsAlarmShutdownPending Shutdown agent upsAlarmShutdownImminent Shutdown agent upsAlarmTestInProgress A034 Battery test NET-VISION 7 - SOCOMEC...
  • Page 66 T001 – T015 SERIAL NUMBER 0x0010 READ ASCII R000 0x001A UPS REFERENCE READ ASCII R001 (*) 2 additional words for units status and alarms synthesis for parallel systems UPS Please refer to Appendix VU-MAP UPS CROSS-REF TABLE NET-VISION 7 - SOCOMEC...
  • Page 67 Maintenance Bypass proc. in progress S091 Programmable S091 S027 S028 UPS OFF procedure in progress S092 Programmable S092 S029 S093 Programmable S093 S030 Auto-test Procedure in progress S094 Programmable S094 S031 Alarm Acknowledgement requested S095 Programmable S095 NET-VISION 7 - SOCOMEC...
  • Page 68 PowerShare Plug 1 closed S124 [13] is available S061 PowerShare Plug 2 closed S125 [14] is available S062 PowerShare Plug 3 closed S126 [15] is available Data no longer up- S063 PowerShare Plug 4 closed S127 dated NET-VISION 7 - SOCOMEC...
  • Page 69 Programmable A090 A027 Battery Alarm A091 Programmable A091 A028 A092 Programmable A092 A029 UPS Backup Critical Alarm A093 Programmable A093 A030 UPS Backup preventive alarm A094 Programmable A094 A031 UPS Backup not OK A095 Programmable A095 NET-VISION 7 - SOCOMEC...
  • Page 70 [13] in Imminent STOP A061 Internal / Communication failure A125 [14] in Imminent STOP A062 Option Board Alarm A126 [15] in Imminent STOP A063 Spare part not A127 Alarms without a level indication are not managed by NET VISION. NET-VISION 7 - SOCOMEC...
  • Page 71 0x0063 M035 Rect. input supply freq. ##.# ##.# 0x0064 M036 Rect. input supply volt. U12 0x0065 M037 Rect. input supply volt. U23 0x0066 M038 Rect. input supply volt. U31 0x0067 M039 Bypass input supply voltage L1 NET-VISION 7 - SOCOMEC...
  • Page 72 Bypass Active Power L1 ## ### # ###.# 0x008A M074 Bypass Active Power L2 ## ### # ###.# 0x008B M075 Bypass Active Power L3 ## ### # ###.# 0x008C M076 0x008D M077 0x008E M078 0x008F M079 NET-VISION 7 - SOCOMEC...
  • Page 73 Operating on Gen Set If present If present If present   Maintenance mode active End of the first maintenance period …   For more information please refer to MODBUS User manual according to the UPS range. NET-VISION 7 - SOCOMEC...
  • Page 74 Unit 4 general alarm units units units Unit 5 general alarm Unit 6 general alarm External alarm 1 External alarm 2 NET-VISION 7 - SOCOMEC...
  • Page 75 Battery circuit open Fan failure Phase rotation fault Bypass critical alarm   Alarms without a level indication are not managed by NET VISION. For more information please refer to the MODBUS User manual according to the UPS range. NET-VISION 7 - SOCOMEC...
  • Page 76 M34 Rectifier input voltage phase 2 0x1083 M35 Rectifier input voltage phase 3 0x1084 M36 UPS output power kW*10 0x1085 M37 Output power phase 1 kVA*10 ###.# 0x1086 M38 Output power phase 2 kVA*10 0x1087 M39 Output power phase 3 kVA*10 NET-VISION 7 - SOCOMEC...
  • Page 77 0x108A M42 Input power L3 0x108B M43 Rec input Fr Hz*10 ##.# 0x108C 0x108D 0x108E 0x108F M47   Value -1 means that the measurement is not managed by the UPS. and not displayed by NET VISION. NET-VISION 7 - SOCOMEC...
  • Page 78 Using SSH tool to open a terminal session: login as: admin [email protected]’s password: Date 03/05/2017 Time 16:41:53 +================================================================+ Configuration Utility [Socomec Net Vision 7 V1.00] +================================================================+ 1. SNMP/WEB Card Settings 2. Reset Accounts/Passwords to Default 3. Reset Configuration to Default 4. Restart SNMP/WEB Card 0. Exit Please Enter Your Choice =>...
  • Page 79 Select the new IP address and go back to the main menu All Network services can be configured via this interface. At the end of all settings, select 0 to go back to the main menu to exit the session. NET-VISION 7 - SOCOMEC...
  • Page 80 • Download it from the SOCOMEC website Admin rights are necessary to install the NET VISION Explorer programme. Run the Net Vision Explorer V1.0.xx.1 file Follow the installation instructions. The programme is installed by default to \Program Files\SOCOMEC Running NET VISION Explorer NET-VISION 7 - SOCOMEC...
  • Page 81 2. PC will detect NET VISION as a USB device 3. Open device manager 4. Double click on Gadget Device, select “Update Driver” 5. Select “Browse my computer for driver software” and select the driver stored on the NET VISION CD. 6. Done NET-VISION 7 - SOCOMEC...
  • Page 82: Led Definition

    3.0 Watts Maximum SMT Switch SMT switch on the board for configuration Dimensions (L x W x H mm) 129.9(L) x 60.0(W) mm Operating Temperature -20 ~ 70° C Operating Humidity 10 ~ 80 % (Non-condensing) NET-VISION 7 - SOCOMEC...
  • Page 83 Gmail accounts need to enable TLS and authentication by NET VISION and make sure that the network is able to access to Internet. In your Gmail account is necessary to enable “Allow less secure apps ON” To set from google My Account > Sign-in & security session NET-VISION 7 - SOCOMEC...