B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 57)
ADDR
REGISTER NAME
7F31
Auxiliary Overvoltage 1 Signal Source
7F32
Auxiliary Overvoltage 1 Pickup
7F33
Auxiliary Overvoltage 1 Pickup Delay
7F34
Auxiliary Overvoltage 1 Reset Delay
7F35
Auxiliary Overvoltage 1 Block
B
7F36
Auxiliary Overvoltage 1 Target
7F37
Auxiliary Overvoltage 1 Events
7F38
Reserved (8 items)
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
(8-bit) Switch (Read/Write Setting) (6 modules)
8300
Switch 1 Function
8301
Switch 1 Argument A Bits (8 items)
8309
Switch 1 Argument B Bits (8 items)
8311
Switch 1 Control
8312
Reserved (6 items)
8318
...Repeated for Switch 2
8330
...Repeated for Switch 3
8348
...Repeated for Switch 4
8360
...Repeated for Switch 5
8378
...Repeated for Switch 6
EGD Fast Production Status (Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration Time
83E3
EGD Fast Producer Exchange 1 Size
EGD Slow Production Status (Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
83F1
EGD Slow Producer Exchange 1 Configuration Time
83F3
EGD Slow Producer Exchange 1 Size
B-38
RANGE
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 4294967295
0 to 65535
0 to 65535
0 to 4294967295
0 to 65535
F35 Multiple Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F001
---
1
F001
---
---
F003
---
1
F001
---
1
F001
---
---
F003
---
1
F001
DEFAULT
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0
0
-55
125
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
GE Multilin
Table of Contents
loading

Table of Contents