Programming Conventions; Ecp Mode Programming - Honeywell GSMV4G Installation And Setup Manual

Intellipath series 4g gsm communicator
Table of Contents

Programming Conventions

Programming is accomplished by answering a series of prompts (questions). Most prompts
require only a [Y]es or [N]o response, while others require a numerical response (ID
numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an
invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the
entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not
displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing
any values. Press the [ESC] key to go to the end of the list of questions.

ECP Mode Programming

The communicator supports ECP messaging to communicate with the control panel.
Likewise the control panel sends Contact ID format alarms to the communicator via the ECP
bus. Not all control panels support the communicator interface on ECP, so be sure to check
the Installation and Setup Guide of the control panel to see if it supports this feature.
ULC
Refer to Table 3-2 for ECP Mode programming and follow the prompts.
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device
NOTE: The default programming values for ECP mode are listed in the prompts below.
Table 3-2. Programming the communicator for ECP mode only.
PROMPTS
Strt Prog Mode?
1
(Y/N)_
Enter Password
2
Program Device?
3
(Y/N)_
Create Password?
4
(Y/N)_
Change
5
Password?
(Y/N)_
Only ECP Mode has been approved for ULC installations.
programming. If this has been done, the following prompt appears:
OPTIONS
[Y], [N]
Enters programming mode.
[0-9, A-F, N, S,
If a password has been previously assigned, this prompt appears.
T, X, Y]
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
[Y], [N]
To begin programming the communicator, press [Y] and go to
Prompt 9: "Device Mode."
To create a password if none has been assigned, press [N] and go to
Prompt 4: "Create Password."
To change an existing password, press [N] and go to Prompt 5:
"Change Password."
[Y], [N]
Passwords can be used to protect account and programming
information.
If no password has been assigned, this prompt appears after
pressing [N] at the "Program Device?" prompt.
If a password is desired, press [Y] and go to Prompt 6: "Enter
Password."
[Y], [N]
If a password has already been assigned, this prompt appears after
pressing [N] at the "Program Device?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering a new one,
answer [Y] to the "Change Password?" prompt, then press the
[Enter] key when prompted for the new password and its
confirmation.
Section 3: Programming the Communicator
DESCRIPTION
Access to Prog
Mode Denied