Siemens SIPART PS2 Operating Instructions Manual page 206

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents
Alarm, error, and system messages
10.1 Output of system messages in the display
Message
Line
Up
Bot-
tom
MANnn
X
oFL /
X
127.9
EXSTP
X
EX UP
X
EXDWN
X
EXPSt
InPSt
FST
X
SRT
X
MSRT
X
VPT
X
LEAKR
X
206
Operating mode
Automat-
Manual
P manu-
ic
mode
al mode
X
X
X
X
X
X
X
X
X
X
X
Meaning/cause
Manual mode
(nn = setpoint)
Display range exceeded.
Possible causes:
Friction clutch or
Transmission ratio selector
was moved or
Positioner was installed on a
different actuator without be-
ing re-initialized.
Actuator was stopped by the
binary input.
Actuator is moved to the upper
endstop by the binary input.
Actuator is moved to the lower
endstop by the binary input.
The partial stroke test was acti-
vated, e.g. by the binary input.
Cyclic partial stroke test.
Full stroke test running.
Step response test running.
Multi-step response test running.
Valve performance test running.
A leakage test started by com-
munication is running.
Operating Instructions, 02/2016, A5E00074631-AB
Measure
Switch to automatic
mode with mode but-
ton.
Offset friction clutch
so that, when the ac-
tuator moves, the ac-
tual value display
stays between 0.0
and 100.0, or
transmission ratio
selector, or
Perform factory set-
tings (Preset) and ini-
tialization.