Commissioning
7.5 Commissioning linear actuators
11.Press the
Note
Fault message "Set Middl"
The lever arm is not in the horizontal position if the "Set Middl" message is output on the
display. To correct the fault, set the reference point of the sine correction. Proceed as
follows:
1. Move the lever arm to the horizontal position using the
2. Press the
12.The initialization process is automatically resumed. Initialization steps "RUN1" to "RUN5"
are output in the bottom line of the display. The following is displayed when the
initialization has been completed successfully:
Note
Total stroke
If the "3.YWAY" parameter has been set, the display shows the total stroke in mm.
Aborting the manual initialization process
1. Press the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
software status is displayed. After releasing the
mode". The positioner is not initialized.
130
button. The current position of the actuator is applied.
button.
button. The display shows the "5.INITM" parameter. The positioner is in the
or
button.
button for at least 5 seconds. The
button, the positioner is in "P manual