GE c60 Instruction Manual page 178

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents
PRODUCT SETUP
RxGOOSE1 ID
Range: 0 to 129 VisibleString characters
Default:
If the value entered has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 00-00-00-00-00-00
Set this setting to the MAC address of the publisher. Only received GOOSE messages having a Media Access Control
(MAC) address equal to this value are accepted as valid RxGOOSE1 messages. An entered address of zero disables
RxGOOSE1.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher's TxGOOSE Dst MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher's TxGOOSE ETYPE APPID
setting.
5
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
Default:
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
/LLN0.
where is the function-related name if any of the logical device containing the publishing control block,
otherwise the product-related name of that logical device, and is the name of the publishing control
block.
The C60 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
/LLN0$GO$
If the publisher is a UR 7.3x series device, is the value of the publisher's Master functional ldName setting if
that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the publisher is a
UR 7.3x series device, is "GoCB" suffixed with the two digit TxGOOSE instance number, for example
"GoCB01".
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default:
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by /LLN0$ for the message to be accepted as a valid RxGOOSE1 message. is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting.
5-52
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Table of Contents
loading