When 2 Units Are Installed In 1 Room - Daikin CTXG09QVJUW Service Manual

Multi-split type air conditioners 2/3/4mxs-n series
Hide thumbs Also See for CTXG09QVJUW:
Table of Contents
Field Settings

5.2.3 When 2 Units are Installed in 1 Room

Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless
remote controller can be set for different address.
Both the indoor unit PCB and the wireless remote controller need alteration.
The method of address setting varies depending on the type of indoor unit and the series of wired
remote controller. Refer to the following pages for the appropriate indoor unit and wireless remote
controller.
CTXG, CTXS,
(1) Remove the front grille.
(2) Remove the electrical box.
FTXS Series
(3) Remove the shield plate of the electrical box.
(4) Cut the address setting jumper JA on the PCB.
CTXG Series
CTXS07LVJU, FTXS09/12LVJU
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
CDXS, FDXS
Series
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
216
JB
JA
JC
Cut the jumper JA on PCB.
ADDRESS : JA
JA
EXIST
1
CUT
2
ADDRESS : JA
EXIST : 1
CUT : 2
JA
(Bottom of electrical box)
(R21128)
FTXS15/18LVJU
JB
JA
JC
(R17375)
1
2
3
(R22010)
SiUS121630EA
(R9665)
Trial Operation and Field Settings