DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manuel dinstallation Manual de instalación MODELS FVXS09NVJU FVXS12NVJU FVXS15NVJU FVXS18NVJU...
Contents Safety Considerations ........1 4. Installing indoor unit ............ 8 4-1. Preparation ............8 Accessories ............. 3 4-2. Installation ............9 5. Flaring the pipe end ............. 12 Choosing an Installation Site ......3 6. Connecting the refrigerant pipe ........12 6-1.
Page 3
Corroding copper pipes or soldered parts may result in is shorted and operated forcibly, or parts other than those refrigerant leakage. specified by Daikin are used, fire or explosion may occur. (c) Near machinery emitting electromagnetic waves. Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction.
Indoor Unit Installation Diagram • The indoor unit may be mounted in any of the 3 styles shown here. Exposed Half concealed Concealed Mounting plate Molding Grid (field supply) Floor Installation Wall Installation • Recommended mounting plate retention spots and dimensions. 19-11/16 (500) 18-11/16 (475) 11 (280)
Indoor Unit Installation Refrigerant piping 1) Drill a hole (φ2-9/16 inch (65mm) in diameter) in the spot indicated by the symbol in the illustration as below. 2) The location of the hole is different depending on which side of the pipe is taken out. 3) For piping, refer to “6.
Page 7
[Back piping] 2-15/16 (75) 2-15/16 (75) Left back piping Right back piping unit: inch (mm) About the outdoor unit refrigerant pipe • In order to connect the pipe, the outdoor unit refrigerant pipe must have a length of at least 13-3/4 inch (350mm) measured from the wall.
Indoor Unit Installation Drilling a wall hole and installing wall embedded pipe WARNING For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole to prevent possible heat, electric shock, or fire. •...
Installing indoor unit 4-1. Preparation 1)Slide the stoppers. • Remove the front panel. 1) Slide until the 2 stoppers click inside. 2) Open the front panel forward and remove the string. 3) Remove the front panel. String Open the front panel 2)Remove the string.
Indoor Unit Installation 4-2. Installation Exposed installation 1) Secure the indoor unit [Floor Installation] • Secure the indoor unit using 6 screws. (2 screws for floor and 4 screws for rear wall) Casing 4 screws 2 screws Indoor unit fixing screws Indoor unit fixing screws 3/16”...
Page 11
Half concealed installation 1) The size of a wall opening space shown in the illustration on 26-3/8 – 27-3/16 the right. (670-690) Open size Opening space Floor unit: inch (mm) 2) The rear of the unit can be fixed with screws at the points shown in the illustration as below. Be sure to install the propping object in accordance with the depth of the inner wall.
Indoor Unit Installation Concealed installation • Install the unit according to the instructions below. Failure to do so may cause lead to both cooling and heating failure and the condensation inside the house. 1) Allow enough space between the main unit and ceiling not to obstruct the flow of cool/warm air. 2) Place a partition plate between outlet and inlet sections.
Flaring the pipe end 1) Cut the pipe end with a pipe cutter. 2) Remove burrs with the cut surface facing downward, so that the filings do not enter the pipe. 3) Put the flare nut on the pipe. 4) Flare the pipe. 5) Check that the flaring has been done correctly.
Indoor Unit Installation 6-1. Caution on piping handling 1) Protect the open end of the pipe against dust and moisture. Wall Be sure to 2) All pipe bends should be as gentle as possible. Use a pipe place a cap. bender for bending.
Wiring With a multi indoor unit , install as described in the installation manual supplied with the multi outdoor unit. • Live the sensor securing plate, remove the front electrical wiring box cover, and connect the branch wiring to the terminal block.
Indoor Unit Installation When connecting to an HA system 1) Remove the front panel and the front grille. (Refer to “4-1. Preparation” on page 8.) 2) Open up the sensor securing plate. (See Fig. 3) 3) Remove the front electrical wiring box cover (4 tabs). (See Fig. 3) 4) Remove connectors .
How to set the different addresses • When 2 indoor units are installed in 1 room, the 2 wireless remote controllers can be set for different addresses. Change the address setting of one of the 2 units. When cutting the jumper be careful not to damage any of the surrounding parts. 1) Remove the electrical wiring box.
Trial Operation and Testing Trial operation and testing • Trial operation should be carried out in either COOL or HEAT operation. 1-1. Measure the supply voltage and make sure that it is within the specified range. 1-2. In COOL operation, select the lowest programmable temperature; in HEAT operation, select the highest programmable temperature.