Installing A Remote Keypad Sounder (For Commercial Burglary Use Only); Figure 3-22: Remote Keyswitch Wiring; Figure 3-23: Remote Keypad Sounder Wiring - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents
LED Indications
Green
Red
On
Off
Off
Off
Off
On Steady
Off
Slow Flash
Off
Rapid Flash
The keyswitch reports as user 0, if Open/Close reporting is enabled in field
Keyswitch Tamper Operation
For UL Commercial Burglary installations, the tamper switch must be wired to zone 6, see Figure 3-23).
Program zone 6 for Day Trouble/Night Alarm (response type 5). When the keyswitch is removed from the wall, the
tamper switch opens, causing an alarm or trouble on the zone. This also causes the control to disable keyswitch
operation until the tamper is restored and the associated partition is disarmed.
Wiring for the Remote Keyswitch
To install the ADEMCO 4146 keyswitch, perform the following steps:
Step
Action
1
Connect the ADEMCO 4146 to the panel as shown in Figure 3-22.
2
If you are using the tamper, make sure it is connected to a zone.

Installing a Remote Keypad Sounder (For Commercial Burglary use only)

An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds produced by the keypad's built-in
sounder. The remote sounder will duplicate all sounds (such as alarms, trouble beeps, etc.) except for the short beeps
associated with keypad key depression. One application of this feature would be to produce chime beeps at a distant
location from the keypads.
If used, program field 3
The remote sounder must be connected to the Output 5 on the J2 connector as shown in Figure 3-23.
Indication
Disarmed & Ready
Disarmed & Not Ready
Armed Away
Armed Stay
Alarm Memory
TO OUT 1 (J2 PIN 7)
TO GND (J2 PIN 8)
TO OUT 5 (J2 PIN 6)
TO ZONE 8 + (TERM 27)
TO ZONE 7/ZONE 8 - (TERM 26)
TO ZONE 7 + (TERM 25)

Figure 3-22: Remote Keyswitch Wiring

20 must be set to "0" and field
1

Figure 3-23: Remote Keypad Sounder Wiring

(ARMED)
(READY)
RED
GREEN
820
820
OHMS
OHMS
2000
OHMS
LOCK
SWITCH (N.O.)
4146 KEYSWITCH
15 must be set to the desired partition number.
J2 CONNECTOR
2
3
4
5
6
7
8
9
4142TR CABLE
BLACK
AMSECO PAL-328N
PIEZO SOUNDER
(10MA)
+
RED
Section 3 - Installing the Control
40.
TAMPER
SWITCH
(N.C.)
2000
OHMS
EOLR
3-23