1.0
Description
The DS160/161 is a passive-infrared (PIR) detector designed for request to exit (REX) interior applications. It is UL Listed as an access
control device under the UL 294 Standard.
The technology designed into the DS160/161 is based on the principal that all objects emit infrared energy. The warmer an object is, the more
infrared energy emitted. Its PIR technology allows the DS160/161 to detect the change in infrared energy that occurs when a person passes
through its field of view.
The DS160/161 has features such as Sequential Logic Input (SLI) to eliminate unauthorized entry. SLI allows you to arm the detector using
any dry contact device, such as a second detector, card reader, or the access control system. This provides better control for this type of
application.
A built-in sounder can be automatically activated if the door is propped open. The sounder can be controlled from any dry contact device. The
DS160/161 detection pattern provides dense C-shaped coverage ideal for most REX applications. In addition, complete pattern control
allows it to be adjusted to a single zone or placed over a doorknob, for example. There are fifteen possible coverage patterns to accommo-
date most applications. This, combined with the ability to monitor the door and intelligently control the lock, adds considerable security to
these types of applications.
The DS160/161 uses Motion Analyzer II signal processing to help prevent false activation due to environmental conditions. The relay output
consists of two Form "C" contacts that can be adjusted to latch from approximately 0.5 to 64 seconds. The latch time features two modes of
operation, resettable (where the relay timer will not time out as long as someone is in the field of view) and non-resettable (where the relay
will remain latched for a fixed period of time). The relay can also be programmed to fail safe or fail secure in the event of power loss.
The DS160/161 may either be ceiling or wall mounted, and its pattern may be aimed and/or masked for more effective use based upon
installation needs. It is not designed as a primary means of exit for emergency egress applications.
The DS160/161 is available in a light grey (DS160) or a black (DS161) enclosure along with an optional trim plate (light gray TP160 or black
TP161) that can cover a single gang box. Panic hardware must be used with this or any other egress device.
2.0
Specifications
• Input Power:
12 VDC to 30 VDC or AC
• Current Draw: 39 mA at 12 VAC, 76 mA at 30 VAC Alarm 39 mA at
12 VDC, 60 mA at 30 VDC Alarm 8 mA nominal
standby current
• Relay:
Two Form "C" contact sets rated for 1 A each at
30 VDC or AC max for resistive loads.
• Sounder:
85 dB with adjustable volume
3.0
Installation
3.1
Remove the cover using a small flat blade screwdriver.
DS160/161
Request To Exit PIR sensors

Installation Instructions

Insert screwdriver
here
Bottom
of
unit
• Temperature:
-20°F to +120°F (-29°X to +49°C). For UL
Listed installations, the temperature range
is +32°F to +120°F (0°F to +49°C) .
• Humidity:
0% to 95% non-condensing. 0% to 85%
non-condensing
installations .
• Dimensions ( xWxD):
1.8 in. x 7 in. x 1.75 in.
(4.5 cm x 17.8 cm x 4.4 cm)
• Trim plate (HxW):
Optional. TP160 (light gray); TP161 (black)
3 in. x 8.25 in. (7.6 cm x 21 cm)
3.2
Rotate the detector clockwise to remove it from the
base.
3.3
Select a mounting location
Push to Exit
Alarm will Sound
Push to Exit
Alarm will Sound
Above the
On the Ceiling
Door
for
UL
Listed
Push to Exit
Push to Exit
Alarm will Sound
Alarm will Sound
Above
Double Doors
loading

Summary of Contents for Bosch DS161

  • Page 1: Installation Instructions

    It is not designed as a primary means of exit for emergency egress applications. The DS160/161 is available in a light grey (DS160) or a black (DS161) enclosure along with an optional trim plate (light gray TP160 or black TP161) that can cover a single gang box.
  • Page 2 Failure to spike protect the detector can shorten the Before wiring the unit, review Wiring Examples in Sections 4 and 5 for more information on the wiring life of the relay contacts. of the DS160/161. IMPORTANT IMPORTANT Page © 2004 Bosch Security Systems DS160/161 Installation Instructions...
  • Page 3: Switch Settings

    Use the following chart to set the Remote Input function. 8 Seconds OFF OFF 16 Seconds OFF ON Switch Function 32 Seconds 64 Seconds Keycard Input Direct Sounder Enable Sequential Logic Input Monitor Door Contacts DS160/161 Installation Instructions © 2004 Bosch Security Systems Page 3...
  • Page 4 Relay contacts shown with Switch 3 ON (Failsafe Mode), Switch 8 is OFF, Switch 9 is ON and Switch 10 is ON (Monitor Door Contacts Mode) Door Contacts (Normally Closed contacts) Page © 2004 Bosch Security Systems DS160/161 Installation Instructions...
  • Page 5: Complete Installation

    ® requires secured doors to have a “manual release device that shall result in direct interruption of power to the lock - independent of the access control system electronics”. IMPORTANT DS160/161 Installation Instructions © 2004 Bosch Security Systems Page 5...
  • Page 6: Coverage Patterns

    When the DS160/161 is mounted on the wall above the door, you can move the coverage pattern away from the wall by rotating the detector’s lens. Page © 2004 Bosch Security Systems DS160/161 Installation Instructions...
  • Page 7 If you want a setup as shown above, mount the DS160/161 just above the door, on the hinge IMPORTANT side, with the lens pointed down and slightly out. DS160/161 Installation Instructions © 2004 Bosch Security Systems Page 7...
  • Page 8 Bosch Security Systems © 2004 Bosch Security Systems 130 Perinton Parkway, Fairport, New York, USA 14450-9199 DS160/DS161 Installation Instructions Customer Service: (800) 289-0096; Technical Support: (888) 886-6189 P/N: 37365M 02/04 Page 8...

This manual is also suitable for:

Ds160