ABB RED615 Technical Manual page 664

615 series
Hide thumbs Also See for RED615:
Table of Contents
Section 8
Measurement functions
658
Table 576:
Non-group analog channel settings for disturbance recorder
Parameter
Values (Range) Unit
Operation
1=on
5=off
Channel
0=Disabled,
selection
1=Io
2=IL1
3=IL2
4=IL3
5=IoB
6=IL1B
7=IL2B
8=IL3B
9=Uo
10=U1
11=U2
12=U3
13=UoB
14=U1B
15=U2B
16=U3B
17=CIo
1)
18=SI1
1)
19=SI2
20=SU0
1)
21=SU1
1)
22=SU2
23=CIoB
1)
24=SI1B
1)
25=SI2B
26=SUoB
1)
27=SU1B
1)
28=SU2B
29=U12
30=U23
31=U31
32=UL1
33=UL2
34=UL3
35=U12B
36=U23B
37=U31B
38=UL1B
39=UL2B
40=UL3B
41=U1T
42=U2T
43=U3T
44=PD
Channel id
0 to 64
text
characters,
alphanumeric
Table continues on next page
Step
Default
1
1=on
0
0=Disabled
DR analog
channel X
1YHT530004D05 D
Description
Analog
channel is
enabled or
disabled
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product
variant
dependent.
Every product
variant
includes only
the values
that are
applicable to
that particular
variant
Identification
text for the
analog
channel used
in the
COMTRADE
format
615 series
Technical Manual

Hide quick links:

Table of Contents
loading