Safety Rated Inputs; Operational Specifications - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents
Magnetic Field Influence
Device
ASD
A/DSD
DSD
Accuracy
Hysteresis and Deadband
Repeatability
Conformity
Start-Up Drift
Long Term Drift
Position Travel Limits
Position Auto Tune
SVI II ESD performs automatic determination of
the optimal valve position control parameters. In
addition to P, I, D, the position algorithm uses
damping, symmetry for exhaust and fill time con-
stants, dead zone and magnitude characteriza-
tion parameters. Auto Tune is optimized for 5%
step changes with negligible overshoot. After Auto
Tune process is completed, you can further adjust
positioner tuning parameters to more conserva-
tive or to more responsive values.
Start Up Time (from no power)
Minimum current to maintain HART
156 |
=GE Oil & Gas
Table 13 Environmental Specifications
Negligible at 30 A/m (EN61000-4-8)
CE MARK certified to EN50081-2 and EN50082-2
Table 14 Safety Rated Inputs
Terminal
Signal
4 - 20 mA IN
< 5.6 mA
24 VDC IN
< 3 VDC
24 VDC IN
< 3 VDC
Table 15 Operational Specifications
+/- 0.5% (typical +/-0. 10% or less) Full Span
+/- 0.3% Full Span
+/- 0.3% Full Span
+/- 0.5% Full Span
Less than 0.02% in first hour
Less than 0.003% per month
Rotary: 18 - 140°
Reciprocating: 0.25" - 2.5" (6 mm - 64 mm)
Note: Above 2.5" (64 mm) consult factory for mounting instruc-
tions.
Proportional gain: 0 to 5, displayed as 0 to 5000
Integral time: 0 to 100 s - displayed as 0 to 1000 (1/10 s)
Derivative time: 0 to 200 ms
Dead Zone: 0 to +/-5% (0 to 10% deadband)
Padj: +/- 3000 (depends on P)
Beta (non-linear gain factor): -9 to +9
Stroking Time: 0 to 250 seconds
Position compensation coefficient: 1 to 20
Boost: 0 to 20
Less than 200 ms
®
3.0 mA
Action
De-energize to Trip
De-energize to Trip
De-energize to Trip
© 2016 General Electric Company. All rights reserved.