Important Product Information
GFK-1892TW
December 2016
CPUE05
PWR
OK
RUN
FAULT
FORCE
PORT 1
IC200CPUE05
PORT 2
PORT 1
RS232
PORT 2
RS485
Features
Supports up to 64 modules with up to 2048 I/O
points
Can be either auto-configured or configured
from a programmer using configuration software
128KB of configurable memory for the
application program, hardware configuration,
registers (%R), analog inputs (%AI), and analog
outputs (%AQ)
Programming in Ladder Diagram and
Instruction List
Non-volatile flash memory for program storage
Battery backup for program, data, and time of
day clock
Super capacitor provides power to memory for
1 hour
-
Over 1 hour, backup battery protects memory
contents up to 6 months.
-
Backup battery has shelf life of 5 years when
not in use.
Run/Stop switch
Floating point (real) data functions
Embedded RS-232, RS-485, and Ethernet
communications
70mm height when mounted on DIN rail with
power supply (sold separately)
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
*
owners.
© 2001-2016 General Electric Company. All Rights Reserved.
MAC XXXXXXXXXXXX
IP ADDRESS
ETHERNET
RESTART
ETHERNET
LAN
STAT
10 MBPS BASE T
PORT 1
CPU with Embedded Ethernet Interface
IC200CPUE05 shares the basic features of the other VersaMax
PLC CPUs. It provides powerful PLC functionality in a small,
versatile system. CPUE05 can serve as the system controller for up
to 64 modules with up to 2048 I/O points. Two serial ports provide
RS-232 and RS-485 interfaces for serial communications. CPUE05
also provides a built-in Ethernet Interface. The RS-232 serial port
can be configured for Local Station manager operation to provide
access to diagnostic information about the Ethernet interface.
CPUE05 has 128KB of configurable memory.
In addition, CPUE05 is compatible with the EZ Program Store
device, which can be used to write, read, update, and verify
programs, configuration, and reference table data without a
programmer or programming software.
Product Information
Revision
IC200CPUE05-LT
Power Supply
Requires PWRx02
Firmware
Version 3.10
Programmer
VersaPro software version 2.0 or later and
Compatibility
Machine Edition Logic Developer.
Expansion I/O
All types of I/O and communications modules can
Compatibility
be used in expansion racks. Some analog
modules require specific module revisions in
expansion racks, as listed below:
VersaMax*
IC200CPUE05
Module
Module Revision
ALG320
B or later
ALG321
B or later
ALG322
B or later
ALG430
C or later
ALG431
C or later
ALG432
B or later
*
Table of Contents
loading

Summary of Contents for GE VersaMax IC200CPUE05

  • Page 1 VersaMax* Important Product Information IC200CPUE05 CPU with Embedded Ethernet Interface GFK-1892TW December 2016 IC200CPUE05 shares the basic features of the other VersaMax CPUE05 MAC XXXXXXXXXXXX PLC CPUs. It provides powerful PLC functionality in a small, versatile system. CPUE05 can serve as the system controller for up FAULT FORCE to 64 modules with up to 2048 I/O points.
  • Page 2 CPU with Embedded Ethernet Interface GFK-1892TW IC200CPUE05 Specifications: IC200CPUE05 Size Width: 4.95” (126mm) - along DIN rail Length: 5.04” (128mm) Depth: 2.72” (69.1mm) Program storage System flash, battery-backed RAM Power Supply current consumption with no serial port 5Vdc uses 220mA 3.3Vdc uses: 570mA converter or EZ Program Store device Power Supply current consumption with serial port...
  • Page 3: Emc Installation Requirements

    CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW EMC Installation Requirements To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the IC695PNC001 module is used shall be mounted in a metal enclosure when three or more IC695PNC001 modules are used. All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity.
  • Page 4: Quick Start

    CPU with Embedded Ethernet Interface GFK-1892TW IC200CPUE05 Quick Start Installation and initial startup procedures for the CPUE05 include the following steps. Before installing and operating the CPUE05, refer to VersaMax PLC User's Manual, GFK-1503 for detailed information. Pre-Installation check Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately.
  • Page 5: Panel Mounting

    CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW Panel-Mounting If excessive vibration is a factor, the CPU should also be screwed down to the mounting panel. Note 1. Tolerances are ±0.13mm (0.005in) non-cumulative. Note 2. 1.1-1.4Nm (10-12 in/lbs) of torque should be applied to M3.5 (#6-32) steel screw threaded into material containing internal threads and having a minimum thickness of 2.4mm (0.093in).
  • Page 6 CPU with Embedded Ethernet Interface GFK-1892TW IC200CPUE05 Switching the PLC Operating Mode The CPU Run/Stop mode switch is located behind the module door. This switch can be used to place the CPU in Stop or Run mode. It can also be used to block accidental writing to CPU memory and forcing or overriding discrete data. Use of this feature is configurable.
  • Page 7 CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW Observing the Module LEDs The CPU contains two sets of LEDs, one in the upper left corner and one in the lower right corner. The LEDs in the upper left corner indicate the presence of power and show the operating mode and status of the CPU.
  • Page 8 CPU with Embedded Ethernet Interface GFK-1892TW IC200CPUE05 Port 1 is an RS-232 port with a 9-pin female D-sub connector. The pinout of Port 1 allows a simple, PORT 1 straight-through cable to connect with a standard AT-style RS-232 port. Cable shielding attaches to the shell.
  • Page 9 CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW Cable: Computer cable, overall braid over foil shield Belden 9610 5 conductor 30 Volt / 80C (176F) 24 AWG tinned copper, 7x32 stranding 9 Pin Male Type: Vendor: Plug: Pin: Connector: Crimp ITT/Cannon DEA9PK87F0 030-2487-017 205204-1...
  • Page 10 CPU with Embedded Ethernet Interface GFK-1892TW IC200CPUE05 Cable: Low Capacitance Computer cable, overall braid over foil shield Belden 8105 5 Twisted-pairs Shield Drain Wire 30 Volt / 80C (176F) 24 AWG tinned copper, 7x32 stranding Velocity of Propagation = 78% Nominal Impedance = 100...
  • Page 11: Using The Ethernet Port

    CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW Using the Ethernet Port The built-in Ethernet interface makes it possible to communicate on a 10BaseT network. The CPUE05 supports half- duplex and full-duplex operation; operation is automatically sensed without user configuration. Using 10/100 hubs allows communication on a network containing 100Mb devices.
  • Page 12: Release History

    Firmware release 3.10 through 3.18 is ONLY compatible with versions –Jx and later. (i.e. Firmware 3.10 through 3.18 is incompatible with hardware versions -AA through –HK). For future revision product users who want to install the new firmware, a firmware upgrade kit is available for download at http://ge-ip.com/support. CPUE05-LS CPU FW - Aug 2016 Ethernet Firmware 3.17 (33A1) addresses the issue where the EGD producers stops...
  • Page 13 CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW (26A1) Ethernet daughterboard firmware version: 3.00 (25A2). Firmware 3.10 (25A2) is not compatible with any hardware revision prior to IC200CPUE05-JL Network Time Protocol (NTP) is not supported in this release. CPUE05-HK 2.38 Apr. 2013 Hardware update to resolve component obsolescence issues.
  • Page 14: New Features And Enhancements

    For future situations, where users want to install the current firmware, upgrade kit 41G1937-MS10-000-A6 can be downloaded from http://support.ge-ip.com. The firmware resides in FLASH memory, and is upgraded by serial download from a Windows PC via CPU port 1. Port 2 cannot be used.
  • Page 15: Operational Notes

    CPU with Embedded Ethernet Interface IC200CPUE05 GFK-1892TW Restrictions and Open Issues Issue Description When configuration is downloaded to IC200CPUE05 having EGD, if user selects “Download When configuration is downloaded to and Start Active Target” button EGD Productions will not produce. IC200CPUE05 having EGD, if user To avoid this issue, the user should download the configuration using separate action selects download and run button of...
  • Page 16: Additional Information

    This enhancement in transmit sequence will add robustness to the system. Additional Information For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support website, http://support.ge-ip.com. VersaMax PLC User's Manual GFK-1503 VersaMax Modules, Power Supplies and Carriers User's Manual...

Table of Contents