Emerson Rosemount 3051 Quick Start Manual
Emerson Rosemount 3051 Quick Start Manual

Emerson Rosemount 3051 Quick Start Manual

Pressure transmitter; 3051cf series flowmeter
Hide thumbs Also See for Rosemount 3051:

Quick Links

Quick Start Guide
00825-0100-4797, Rev ED
October 2016
Rosemount
3051 Pressure Transmitter
and Rosemount 3051CF Series Flowmeter
®
with PROFIBUS
PA Protocol
loading

Summary of Contents for Emerson Rosemount 3051

  • Page 1 Quick Start Guide 00825-0100-4797, Rev ED October 2016 ™ Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter ® with PROFIBUS PA Protocol...
  • Page 2: Table Of Contents

    October 2016 Quick Start Guide NOTICE This installation guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 Reference Manual more instruction.
  • Page 3: Mount The

    Quick Start Guide October 2016 1.0 Mount the transmitter 1.1 Liquid applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. 1.2 Gas applications 1.
  • Page 4 October 2016 Quick Start Guide 1.4 Mounting options Panel mount Pipe mount Coplanar flange Traditional flange Rosemount 3051T 1. Panel bolts are customer supplied.
  • Page 5 Use only bolts supplied ™ with the transmitter or sold by Emerson Process Management as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 6 October 2016 Quick Start Guide Table 1. Torque Values for the Flange and Flange Adapter Bolts Bolt material Head markings Initial torque Final torque 300 in-lb 650 in-lb Carbon Steel (CS) Stainless Steel (SST) 150 in-lb 300 in-lb 1.6 O-rings with flange adapters Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury.
  • Page 7: Consider Housing Rotation

    Quick Start Guide October 2016 transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
  • Page 8: Connect Wiring And Power Up

    “ON” position after power is applied. This feature prevents the transmitter from being accidentally left in simulate mode. Figure 4. Transmitter Jumper Locations ROSEMOUNT 3051 PROFIBUS PA OUTPUT 4.0 Connect wiring and power up Use the following steps to wire the transmitter: 1.
  • Page 9 Quick Start Guide October 2016 Figure 5. Terminals A. Power terminals B. Ground terminal Note: “NC” is a No Connect terminal (do not use) Figure 6. Wiring A. 6234 ft (1900 m) max F. Trunk (depending upon cable characteristics) G. DP network B.
  • Page 10: Basic Configuration

    October 2016 Quick Start Guide 2. Connect the wiring pair and ground as indicated in Figure 7. The cable shield should: Be trimmed close and insulated from touching the transmitter housing.  Continuously connect to the termination point.  Be connected to a good earth ground at the power supply end. ...
  • Page 11 2. Configure engineering units (scaling). Note Rosemount 3051 Profibus Profile 3.02 devices are set to identification number adaptation mode when shipped from the factory. This mode allows the transmitter to communicate with any Profibus control host with either the generic Profile GSD (9700) or Rosemount 3051 specific GSD (4444) loaded on the host;...
  • Page 12 1. Characters blink when they can be changed. Figure 8. LOI Menu 5.5 Class 2 Master The Rosemount 3051 Profibus DD and DTM files are available at EmersonProcess.com/Rosemount or by contacting your local salesperson. Table 3 for steps to configure the transmitter for Pressure measurement.
  • Page 13: Trim The Transmitter

    Profile 3.02 specification and NE 107. See manual for condensed status bit assignment information. The appropriate GSD file must be loaded on the control host - Rosemount 3051 specific (rmt4444.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be found on EmersonProcess.com/Rosemount...
  • Page 14: Product Certifications

    Care must be taken into account during installation and use to prevent impact and friction. 2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1) will not pass the 500Vrms dielectric strength test and this must be taken into account during installation.
  • Page 15 Quick Start Guide October 2016 C6 Canada Explosionproof, Dust-Ignitionproof, Intrinsic Safety and Nonincendive Certificate: 1053834 Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987 Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5;...
  • Page 16 October 2016 Quick Start Guide I1 ATEX Intrinsic Safety and Dust Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-11:2012, EN60079-31:2009 II 1 G Ex ia IIC Ga T4(–60 °C ≤ T ≤ +60 °C) Markings: HART: II 1 G Ex ia IIC Ga T4(–60 °C ≤ T ≤...
  • Page 17 Quick Start Guide October 2016 N1 ATEX Type n and Dust Certificate: BAS00ATEX3105X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-15:2010, EN60079-31:2009 II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T ≤ +70 °C); Markings: 105 °C Da (–20 °C ≤ T ≤...
  • Page 18 October 2016 Quick Start Guide Special Conditions for Safe Use (X): 1. If the apparatus is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus.
  • Page 19 Quick Start Guide October 2016 2. In case of repair, contact the manufacturer for information on the dimensions of the flameproof joints. 3. The capacitance of the wrap around label, being 1.6nF, exceeds the limit in Table 9 of ABNT NBR IEC 60079-0. The user shall determine suitability for the specific application. I2 INMETRO Intrinsic Safety Certificate: UL-BR 13.0584X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009...
  • Page 20 October 2016 Quick Start Guide 7.7 China E3 China Flameproof Certificate: GYJ14.1041X; GYJ15.1368X [Flowmeters] Standards: GB12476-2000; GB3836.1-2010, GB3836.2-2010, GB3836.20-2010 Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ Ta ≤ +65 °C), T5(-50 °C ≤ Ta ≤ +80 °C) Special Conditions for Safe Use (X): 1.
  • Page 21 Quick Start Guide October 2016 Parameter HART Fieldbus/PROFIBUS FISCO Capacitance C 0.012 μF 0 μF < 5 nF Inductance L 0 mH 0 mH < 10 μH Note 1: FISCO parameters apply to both Group IIC and IIB. Note 2: [For Flowmeters] When Rosemount 644 Temperature Transmitter is used, the Rosemount 644 should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres.
  • Page 22 October 2016 Quick Start Guide IM EAC Intrinsically Safe Certificate: RU C-US.GB05.B.01197 ≤ ≤ ≤ ≤ Markings: HART: 0Ex ia IIC T4/T5 Ga X, T4(–60 °C +70 °C), T5(–60 °C +40 °C) ≤ ≤ Fieldbus/PROFIBUS: 0Ex ia IIC T4 Ga X (–60 °C +60 °C) Special Condition for Safe Use (X): 1.
  • Page 23 Quick Start Guide October 2016 7.12 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 09-HS446883A-5-PDA Intended Use: Marine & Offshore Applications – Measurement of either gauge or absolute pressure for liquid, gas, and vapor. SBV Bureau Veritas (BV) Type Approval Certificate: 23155 BV Rules: Bureau Veritas Rules for the Classification of Steel Ships Requirements: Bureau Veritas Rules for the Classification of Steel Ships...
  • Page 24 October 2016 Quick Start Guide Figure 9. Rosemount 3051 Declaration of Conformity...
  • Page 25 Quick Start Guide October 2016...
  • Page 26 October 2016 Quick Start Guide...
  • Page 27 Quick Start Guide October 2016...
  • Page 28 October 2016 Quick Start Guide Rosemount 3051 China RoHS List of Rosemount 3051 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 29 Quick Start Guide October 2016...
  • Page 30 +65 6777 0947 [email protected] Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use The Emerson logo is a trademark and service mark of Emerson Middle East and Africa Regional Office Electric Co. Emerson Process Management Rosemount and Rosemount logotype are trademarks of Emerson Emerson FZE P.O.

This manual is also suitable for:

Rosemount 3051cf