GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Quick Links

Title Page
GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0106-U4*
F35 Multiple Feeder Protection
UR Series Instruction Manual
Manual P/N: 1601-0106-U4 (GEK-113520C)
E83849
LISTED
IND.CONT. EQ.
System
F35 Revision: 5.7x
52TL
832761A2.CDR
GE Multilin's Quality Management
System is registered to
ISO9001:2008
QMI # 005094
UL # A3775
Table of Contents
loading

Summary of Contents for GE UR F35 Series

  • Page 1 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO9001:2008 Tel: +1 905 927 7070 Fax: +1 905 927 5098 QMI # 005094 UL # A3775 Internet: http://www.GEDigitalEnergy.com...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3 Addendum ADDENDUM This addendum contains information that relates to the F35 Multiple Feeder Protection System, version 5.7x. It outlines items that appear in the instruction manual GEK-113520C (revision U4) that are not included in the current F35 opera- tions. The following functions and items are not yet available with the current version of the F35 relay: •...
  • Page 5: Table Of Contents

    3.2 WIRING 3.2.1 TYPICAL WIRING.................... 3-10 3.2.2 DIELECTRIC STRENGTH ................3-11 3.2.3 CONTROL POWER ..................3-11 3.2.4 CT/VT MODULES .................... 3-12 3.2.5 PROCESS BUS MODULES ................3-14 3.2.6 CONTACT INPUTS AND OUTPUTS ............... 3-14 GE Multilin F35 Multiple Feeder Protection System...
  • Page 6 MODBUS USER MAP ..................5-35 5.2.6 REAL TIME CLOCK ..................5-36 5.2.7 FAULT REPORTS ....................5-37 5.2.8 OSCILLOGRAPHY ...................5-39 5.2.9 DATA LOGGER ....................5-41 5.2.10 DEMAND ......................5-43 5.2.11 USER-PROGRAMMABLE LEDS ..............5-44 5.2.12 USER-PROGRAMMABLE SELF TESTS ............5-47 5.2.13 CONTROL PUSHBUTTONS ................5-48 F35 Multiple Feeder Protection System GE Multilin...
  • Page 7 IEC 61850 GOOSE INTEGERS..............5-170 5.9 TRANSDUCER INPUTS AND OUTPUTS 5.9.1 DCMA INPUTS ....................5-171 5.9.2 RTD INPUTS....................5-172 5.9.3 DCMA OUTPUTS ..................5-174 5.10 TESTING 5.10.1 TEST MODE ....................5-177 5.10.2 FORCE CONTACT INPUTS ................5-178 GE Multilin F35 Multiple Feeder Protection System...
  • Page 8 RELAY MAINTENANCE ..................7-3 7.2 TARGETS 7.2.1 TARGETS MENU ....................7-4 7.2.2 TARGET MESSAGES ..................7-4 7.2.3 RELAY SELF-TESTS ..................7-4 8. SECURITY 8.1 PASSWORD SECURITY 8.1.1 OVERVIEW ......................8-1 8.1.2 PASSWORD SECURITY MENU ................8-2 8.1.3 LOCAL PASSWORDS..................8-2 viii F35 Multiple Feeder Protection System GE Multilin...
  • Page 9 INTRODUCTION....................C-1 C.1.2 COMMUNICATION PROFILES .................C-1 C.2 SERVER DATA ORGANIZATION C.2.1 OVERVIEW......................C-2 C.2.2 GGIO1: DIGITAL STATUS VALUES ..............C-2 C.2.3 GGIO2: DIGITAL CONTROL VALUES ..............C-2 C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE GE Multilin F35 Multiple Feeder Protection System...
  • Page 10 ANALOG INPUTS.................... E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY..................F-1 F.1.2 CHANGES TO THE MANUAL ................F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-7 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY................F-9 F35 Multiple Feeder Protection System GE Multilin...
  • Page 11 TABLE OF CONTENTS INDEX GE Multilin F35 Multiple Feeder Protection System...
  • Page 12 TABLE OF CONTENTS F35 Multiple Feeder Protection System GE Multilin...
  • Page 13: Getting Started

    • Mounting screws For product information, instruction manual updates, and the latest software updates, please visit the GE Digital Energy website. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately. NOTE...
  • Page 14: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. F35 Multiple Feeder Protection System...
  • Page 15: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin F35 Multiple Feeder Protection System...
  • Page 16: Software Architecture

    5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section in chapter 5. F35 Multiple Feeder Protection System GE Multilin...
  • Page 17: Enervista Ur Setup Software

    After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD. Insert the GE EnerVista CD into your CD-ROM drive.
  • Page 18: Configuring The F35 For Software Access

    The user can connect remotely to the F35 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The F35 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature. F35 Multiple Feeder Protection System GE Multilin...
  • Page 19 A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is will be required. Refer to the F485 instruction manual for additional details. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 20 Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin).
  • Page 21: Using The Quick Connect Feature

    Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 22 Now, assign the laptop computer an IP address compatible with the relay’s IP address. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window. Right-click the Local Area Connection icon and select Properties. 1-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 23 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Note that the values for will vary depending on local network configuration. time If the following sequence of messages appears when entering the command: C:\WINNT>ping 1.1.1.1 GE Multilin F35 Multiple Feeder Protection System 1-11...
  • Page 24 Default Gateway ..: C:\WINNT> It may be necessary to restart the laptop for the change in IP address to take effect (Windows 98 or NT). 1-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 25 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the F35 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 26 Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to identify and interrogate, in seconds, all UR-series devices in a particular location. 1-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 27: Connecting To The F35 Relay

    View the F35 event record. • View the last recorded oscillography record. • View the status of all F35 inputs and outputs. • View all of the F35 metering values. • View the F35 protection summary. GE Multilin F35 Multiple Feeder Protection System 1-15...
  • Page 28: Ur Hardware

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the F35 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the F35 rear communications port.
  • Page 29: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message    SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin F35 Multiple Feeder Protection System 1-17...
  • Page 30: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 31: Commissioning

    View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements. If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service. GE Multilin...
  • Page 32 1.5 USING THE RELAY 1 GETTING STARTED 1-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 33: Product Description

    50N (up to 12) Neutral instantaneous overcurrent Auxiliary overvoltage 50P (up to 12) Phase instantaneous overcurrent 79 (up to 6) Autoreclose 51G (up to 6) Ground time overcurrent 81 (up to 6) Underfrequency GE Multilin F35 Multiple Feeder Protection System...
  • Page 34: Ordering

    Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules). Order codes are subject to change without notice. Refer to the GE Multilin ordering page at http://www.gedigitalenergy.com/multilin/order.htm for the latest details concerning F35 ordering options.
  • Page 35 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin F35 Multiple Feeder Protection System...
  • Page 36 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels F35 Multiple Feeder Protection System GE Multilin...
  • Page 37 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin F35 Multiple Feeder Protection System...
  • Page 38: Replacement Modules

    Not all replacement modules may be applicable to the F35 relay. Only the modules specified in the order codes are available as replacement modules. NOTE Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http:// http://www.gedigitalenergy.com/multilin/order.htm for the latest details concerning F35 ordering options.
  • Page 39 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs GE Multilin F35 Multiple Feeder Protection System...
  • Page 40 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs F35 Multiple Feeder Protection System GE Multilin...
  • Page 41: Specifications

    Level accuracy: ±0.5% of reading from 10 to 208 V Level accuracy: Curve shapes: GE IAV Inverse, Definite Time for 0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01...
  • Page 42: User-Programmable Elements

    –90.000 to 90.000 pu in steps of 0.001 Hysteresis: 0.1 to 50.0% in steps of 0.1 Delta dt: 20 ms to 60 days Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001 2-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 43: Monitoring

    Storage capacity: (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days ↓ 60-minute rate: 01 channel for NN days 16 channels for NN days GE Multilin F35 Multiple Feeder Protection System 2-11...
  • Page 44: Metering

    Auto-burnish impulse current: 50 to 70 mA Conversion range: 1 to 275 V Duration of auto-burnish impulse: 25 to 50 ms Voltage withstand: continuous at 260 V to neutral 1 min./hr at 420 V to neutral 2-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 45: Power Supply

    Operate time: < 4 ms 48 V 0.5 A Contact material: silver alloy 125 V 0.3 A Control: separate operate and reset inputs 250 V 0.2 A Control mode: operate-dominant or reset-dominant GE Multilin F35 Multiple Feeder Protection System 2-13...
  • Page 46 (0 to 250 V Manufacturer: Conquer; Part number: 1.6 A 10 A 10 A L/R = 20 ms L/R = 40 ms L/R = 40 ms SCD-A 005 0.8 A L/R = 40 ms 2-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 47: Communications

    Shielded twisted pair: 150 m (492 ft.) MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS 10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) GE Multilin F35 Multiple Feeder Protection System 2-15...
  • Page 48: Inter-Relay Communications

    Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 49: Type Tests

    Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin F35 Multiple Feeder Protection System 2-17...
  • Page 50: Approvals

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to NOTE avoid deterioration of electrolytic capacitors. 2-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 51: Hardware

    11.016” [279,81 mm] 9.687” [246,05 mm] 17.56” [446,02 mm] 7.460” [189,48 mm] 6.995” 6.960” [177,67 mm] [176,78 mm] 19.040” [483,62 mm] 842807A1.CDR Figure 3–1: F35 HORIZONTAL DIMENSIONS (ENHANCED PANEL) GE Multilin F35 Multiple Feeder Protection System...
  • Page 52 The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment. F35 Multiple Feeder Protection System GE Multilin...
  • Page 53 RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.015” 7.482” 1.329” 13.560” 15.000” 14.025” 4.000” 9.780” 843809A1.CDR Figure 3–4: F35 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin F35 Multiple Feeder Protection System...
  • Page 54 Figure 3–5: F35 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting F35 devices with the enhanced front panel, refer to the following documents available online from the GE Multilin website. • GEK-113180: UR-series UR-V side-mounting front panel assembly instructions •...
  • Page 55 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: F35 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin F35 Multiple Feeder Protection System...
  • Page 56: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the F35. F35 Multiple Feeder Protection System GE Multilin...
  • Page 57 All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con- nectors must be individually disconnected from the module before it can be removed from the chassis. NOTE GE Multilin F35 Multiple Feeder Protection System...
  • Page 58: Rear Terminal Layout

    Inst. Manual: Contact Outputs: Standard Pilot Duty / 250V AC 7.5A MAZB98000029 Serial Number: 360V A Resistive / 125V DC Break Firmware: GE Multilin 4A @ L/R = 40mS / 300W 1999/01/05 Mfg. Date: Technical Support: Made in Tel: (905) 294-6222 ®...
  • Page 59 3 HARDWARE 3.1 DESCRIPTION Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin F35 Multiple Feeder Protection System...
  • Page 60: Wiring

    CONTACT INPUT P6c COMMON P5b CONTACT INPUT P7a CONTACT INPUT P7c CONTACT INPUT P8a CONTACT INPUT P8c COMMON P7b SURGE GE Consumer & Industrial Multilin MULTIPLE FEEDER MANAGEMENT RELAY CONTACT INPUT H5a CONTACT INPUT H5c COMPUTER CONTACT INPUT H6a CONTACT INPUT H6c...
  • Page 61: Dielectric Strength

    Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay of the module will also indicate a faulted power supply. GE Multilin F35 Multiple Feeder Protection System...
  • Page 62: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair cabling on the zero-sequence CT is recommended. 3-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 63 NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING GE Multilin F35 Multiple Feeder Protection System 3-13...
  • Page 64: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The F35 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 65 Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of NOTE the output contact (in situations when the element initiating the contact output is bouncing, at values in the region of the pickup value). GE Multilin F35 Multiple Feeder Protection System 3-15...
  • Page 66 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 67 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin F35 Multiple Feeder Protection System 3-17...
  • Page 68 3.2 WIRING 3 HARDWARE Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 69 CONTACT IN COMMON SURGE 842763A2.CDR Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output connections. GE Multilin F35 Multiple Feeder Protection System 3-19...
  • Page 70 There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 71 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin F35 Multiple Feeder Protection System 3-21...
  • Page 72: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–22: TRANSDUCER INPUT/OUTPUT MODULE WIRING 3-22 F35 Multiple Feeder Protection System GE Multilin...
  • Page 73: Rs232 Faceplate Port

    RS485 Redundant 10Base-F RS485 100Base-FX RS485 Redundant 100Base-FX RS485 100Base-FX RS485 Redundant 100Base-FX RS485 10/100Base-T RS485 100Base-FX RS485 Redundant 100Base-FX RS485 Ethernet switch module with two 10/100Base-T and four 100Base-FX ports RS485 GE Multilin F35 Multiple Feeder Protection System 3-23...
  • Page 74 3.2 WIRING 3 HARDWARE Figure 3–24: CPU MODULE COMMUNICATIONS WIRING 3-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 75 To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. Figure 3–25: RS485 SERIAL CONNECTION GE Multilin F35 Multiple Feeder Protection System 3-25...
  • Page 76 In order to engage or disengage the ST type connec- tor, only a quarter turn of the coupling is required. 3-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 77: Irig-B

    UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–27: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping. NOTE GE Multilin F35 Multiple Feeder Protection System 3-27...
  • Page 78: Direct Input/Output Communications

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. 3-28 F35 Multiple Feeder Protection System GE Multilin...
  • Page 79 1300 nm, multi-mode, LED, 2 channels 1300 nm, single-mode, ELED, 2 channels 1300 nm, single-mode, LASER, 2 channels Channel 1: RS422, channel: 820 nm, multi-mode, LED Channel 1: RS422, channel 2: 1300 nm, multi-mode, LED GE Multilin F35 Multiple Feeder Protection System 3-29...
  • Page 80: Fiber: Led And Eled Transmitters

    1 Channel 2 Channels Figure 3–32: LASER FIBER MODULES When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. 3-30 F35 Multiple Feeder Protection System GE Multilin...
  • Page 81: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. GE Multilin F35 Multiple Feeder Protection System 3-31...
  • Page 82 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-32 F35 Multiple Feeder Protection System GE Multilin...
  • Page 83 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–37: G.703 DUAL LOOPBACK MODE GE Multilin F35 Multiple Feeder Protection System 3-33...
  • Page 84: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. 3-34 F35 Multiple Feeder Protection System GE Multilin...
  • Page 85 Figure 3–41: CLOCK AND DATA TRANSITIONS d) RECEIVE TIMING The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data. NRZI-MARK is an edge-type, invertible, self-clocking code. GE Multilin F35 Multiple Feeder Protection System 3-35...
  • Page 86: Rs422 And Fiber Interface

    When using a laser interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–43: G.703 AND FIBER INTERFACE CONNECTION 3-36 F35 Multiple Feeder Protection System GE Multilin...
  • Page 87: Ieee C37.94 Interface

    IEEE C37.94 standard, as shown below. In 2008, GE Digital Energy released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 88 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-38 F35 Multiple Feeder Protection System GE Multilin...
  • Page 89 3 HARDWARE 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS Figure 3–44: IEEE C37.94 TIMING SELECTION SWITCH SETTING GE Multilin F35 Multiple Feeder Protection System 3-39...
  • Page 90: C37.94Sm Interface

    It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below. In 2008, GE Digital Energy released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 91 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. GE Multilin F35 Multiple Feeder Protection System...
  • Page 92 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE Figure 3–45: C37.94SM TIMING SELECTION SWITCH SETTING 3-42 F35 Multiple Feeder Protection System GE Multilin...
  • Page 93: Managed Ethernet Switch Modules

    Two 10/100Base-T ports Four 100Base-FX multimode ports with ST connectors RS232 console port Independent power supply. Options: 2S: high-voltage 2T: low-voltage FRONT VIEW REAR VIEW 842867A2.CDR Figure 3–46: MANAGED ETHERNET SWITCHES HARDWARE GE Multilin F35 Multiple Feeder Protection System 3-43...
  • Page 94: Managed Switch Led Indicators

    Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net- work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified. Do not connect to network while configuring the switch module. 3-44 F35 Multiple Feeder Protection System GE Multilin...
  • Page 95 Select the desired device from site tree in the online window. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File > Retreive Settings File item from the device settings tree. GE Multilin F35 Multiple Feeder Protection System 3-45...
  • Page 96 Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open. The settings file will be transferred to the Ethernet switch and the settings uploaded to the device. 3-46 F35 Multiple Feeder Protection System GE Multilin...
  • Page 97: Uploading F35 Switch Module Firmware

    NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
  • Page 98 Select the firmware file to be loaded on to the Switch, and select the Open option. The following window will pop up, indicating that the firmware file transfer is in progress. If the firmware load was successful, the following window will appear: Note 3-48 F35 Multiple Feeder Protection System GE Multilin...
  • Page 99: Ethernet Switch Self-Test Errors

    To clear the main CPU upon power-up the fault, cycle power to the F35. and create the error if there is a conflict between the input/ output state and the order code. GE Multilin F35 Multiple Feeder Protection System 3-49...
  • Page 100 3.4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3-50 F35 Multiple Feeder Protection System GE Multilin...
  • Page 101: Human Interfaces

    Factory default values are supplied and can be restored after any changes. The following communications settings are not transferred to the F35 with settings files. Modbus Slave Address Modbus IP Port Number RS485 COM1 Baud Rate RS485 COM1 Parity COM1 Minimum Response Time GE Multilin F35 Multiple Feeder Protection System...
  • Page 102 EEPROM DATA ERROR message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This message does not signal any problems when appearing after firmware upgrades. F35 Multiple Feeder Protection System GE Multilin...
  • Page 103: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin F35 Multiple Feeder Protection System...
  • Page 104: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. F35 Multiple Feeder Protection System GE Multilin...
  • Page 105 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin F35 Multiple Feeder Protection System...
  • Page 106 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F35 Multiple Feeder Protection System GE Multilin...
  • Page 107 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin F35 Multiple Feeder Protection System...
  • Page 108: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. F35 Multiple Feeder Protection System GE Multilin...
  • Page 109 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin F35 Multiple Feeder Protection System...
  • Page 110: Settings File Traceability

    SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. 4-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 111 Figure 4–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 4–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA GE Multilin F35 Multiple Feeder Protection System 4-11...
  • Page 112 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. 4-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 113: Faceplate Interface

    LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin F35 Multiple Feeder Protection System 4-13...
  • Page 114: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 115 IN SERVICE VOLTAGE TROUBLE CURRENT RESET TEST MODE FREQUENCY TRIP OTHER USER 1 ALARM PHASE A PICKUP PHASE B USER 2 PHASE C NEUTRAL/GROUND USER 3 842781A1.CDR Figure 4–19: LED PANEL 1 GE Multilin F35 Multiple Feeder Protection System 4-15...
  • Page 116 LEDs on these panels. USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS 842782A1.CDR Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE) DEFAULT LABELS FOR LED PANEL 2: The default labels are intended to represent: 4-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 117: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational. • The F35 settings have been saved to a settings file. • The F35 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http:// www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed.
  • Page 118 Remove the F35 label insert tool from the package and bend the tabs as described in the following procedures. These tabs will be used for removal of the default and custom LED labels. It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part number facing the user.
  • Page 119 Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED label. GE Multilin F35 Multiple Feeder Protection System 4-19...
  • Page 120 Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the bent tab is pointing away from the relay. 4-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 121 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin F35 Multiple Feeder Protection System 4-21...
  • Page 122 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
  • Page 123: Display

    Microsoft Word 97 or later software for editing the template. • 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069), and a custom module cover (GE Multilin Part Number: 1502-0015).
  • Page 124: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 125 Display Properties. TIME: 1.0 s  To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% GE Multilin F35 Multiple Feeder Protection System 4-25...
  • Page 126: Changing Settings

    Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. 4-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 127: Settings

    When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The F35 supports password entry from a local or remote connection. GE Multilin F35 Multiple Feeder Protection System 4-27...
  • Page 128 FlexLogic™ operand will be set to “On” and the F35 will not allow LOCAL ACCESS DENIED Settings or Command access via the faceplate interface for the next ten minutes. The TOO MANY ATTEMPTS – BLOCKED 4-28 F35 Multiple Feeder Protection System GE Multilin...
  • Page 129 F35 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout. REMOTE ACCESS DENIED GE Multilin F35 Multiple Feeder Protection System 4-29...
  • Page 130 4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-30 F35 Multiple Feeder Protection System GE Multilin...
  • Page 131: Overview

    See page 5-57.   TELEPROTECTION See page 5-65.   INSTALLATION See page 5-65.   SETTINGS  AC INPUTS See page 5-68.  SYSTEM SETUP   POWER SYSTEM See page 5-69.  GE Multilin F35 Multiple Feeder Protection System...
  • Page 132  SELECTOR SWITCH See page 5-128.   UNDERFREQUENCY See page 5-134.   AUTORECLOSE See page 5-135.   DIGITAL ELEMENTS See page 5-141.   DIGITAL COUNTERS See page 5-144.  F35 Multiple Feeder Protection System GE Multilin...
  • Page 133  DCMA INPUTS See page 5-171.  TRANSDUCER I/O   RTD INPUTS See page 5-172.   DCMA OUTPUTS See page 5-174.   SETTINGS TEST MODE See page 5-177.  TESTING FUNCTION: Disabled GE Multilin F35 Multiple Feeder Protection System...
  • Page 134: Introduction To Elements

    • NAME setting: This setting is used to uniquely identify the element. • SOURCE setting: This setting is used to select the parameter or set of parameters to be monitored. F35 Multiple Feeder Protection System GE Multilin...
  • Page 135: Introduction To Ac Sources

    The same considerations apply to transformer Winding 2. The protection elements require access to the net current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2. GE Multilin F35 Multiple Feeder Protection System...
  • Page 136 CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > F35 Multiple Feeder Protection System GE Multilin...
  • Page 137 CTs on each of two breakers is required to measure the winding current flow. GE Multilin F35 Multiple Feeder Protection System...
  • Page 138: Product Setup

    ACCESS LOC SETG OFF: Asserted when local setting access is disabled. • ACCESS LOC SETG ON: Asserted when local setting access is enabled. • ACCESS LOC CMND OFF: Asserted when local command access is disabled. F35 Multiple Feeder Protection System GE Multilin...
  • Page 139 The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the Settings > Product Setup > Password Security menu item to open the remote password settings window. Figure 5–2: REMOTE PASSWORD SETTINGS WINDOW GE Multilin F35 Multiple Feeder Protection System...
  • Page 140 FlexLogic™ operand is UNAUTHORIZED ACCESS asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be used to protect against both unauthorized and accidental access attempts. 5-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 141 ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time- out is restarted. The status of this timer is updated every 5 seconds. GE Multilin F35 Multiple Feeder Protection System 5-11...
  • Page 142: Display Properties

    DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. 5-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 143 Any calculated power value below this cut-off will not be displayed. As well, the three-phase energy data will not accumu- late if the total power from all three phases does not exceed the power cut-off. GE Multilin F35 Multiple Feeder Protection System...
  • Page 144: Clear Relay Records

    Set the properties for User-Programmable Pushbutton 1 by making the following changes in the  SETTINGS PRODUCT   menu: SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.20 s” PUSHBTN 1 DROP-OUT TIME: 5-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 145: Communications

    19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that GE Multilin F35 Multiple Feeder Protection System...
  • Page 146 1. Refer to Appendix B for more information on the Modbus protocol. Changes to the setting will not take effect until the F35 is restarted. MODBUS TCP PORT NUMBER NOTE 5-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 147 DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min GE Multilin F35 Multiple Feeder Protection System 5-17...
  • Page 148 NOTE settings can force the F35 to respond to a maximum of five specific DNP masters. The DNP NETWORK CLIENT ADDRESS settings in this sub-menu are shown below. 5-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 149 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The F35 can be configured to sup- GE Multilin F35 Multiple Feeder Protection System...
  • Page 150 Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config- ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the full range of assignable parameters. 5-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 151   PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION  GSSE / GOOSE  TRANSMISSION  CONFIGURATION   RECEPTION MESSAGE  The main transmission menu is shown below: GE Multilin F35 Multiple Feeder Protection System 5-21...
  • Page 152 Range: 0 to 7 in steps of 1 GOOSE VLAN PRIORITY: MESSAGE Range: 0 to 4095 in steps of 1 GOOSE VLAN ID: MESSAGE Range: 0 to 16383 in steps of 1 GOOSE ETYPE APPID: MESSAGE 5-22 F35 Multiple Feeder Protection System GE Multilin...
  • Page 153 GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent. For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no changes in the data items are detected. GE Multilin F35 Multiple Feeder Protection System 5-23...
  • Page 154 IEC 61850 IED configuration section later in this appendix). The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The general steps required for transmission configuration are: 5-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 155 Configure the GOOSE service settings by making the following changes in the  INPUTS/OUTPUTS REMOTE DEVICES  settings menu: REMOTE DEVICE 1 – to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”. REMOTE DEVICE 1 ID GE Multilin F35 Multiple Feeder Protection System 5-25...
  • Page 156 Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non- instantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1 and higher items. Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up). 5-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 157 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the F35 is restarted. GE Multilin F35 Multiple Feeder Protection System...
  • Page 158 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the F35 virtual inputs. 5-28 F35 Multiple Feeder Protection System GE Multilin...
  • Page 159 ANALOG IN 1 MAX numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded NOTE to the closest possible floating point number. GE Multilin F35 Multiple Feeder Protection System 5-29...
  • Page 160 Disconnect any IEC 61850 client connection to the F35 prior to making setting changes to the report configuration. Disconnecting the rear Ethernet connection from the F35 disconnects the IEC 61850 client connection. NOTE 5-30 F35 Multiple Feeder Protection System GE Multilin...
  • Page 161 Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net- work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN NOTE functionality. GE Multilin F35 Multiple Feeder Protection System 5-31...
  • Page 162 IEC POWER DEFAULT MESSAGE THRESHOLD: 30000 Range: 0 to 65535 in steps of 1 IEC ENERGY DEFAULT MESSAGE THRESHOLD: 30000 Range: 0 to 65535 in steps of 1 IEC OTHER DEFAULT MESSAGE THRESHOLD: 30000 5-32 F35 Multiple Feeder Protection System GE Multilin...
  • Page 163 This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The Ethernet Global Data (EGD) protocol feature is not available if CPU Type E is ordered. GE Multilin F35 Multiple Feeder Protection System 5-33...
  • Page 164 50 ms. If the setting is 1000 ms, the exchange data will be updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a setting range of 500 to 1000 ms. 5-34 F35 Multiple Feeder Protection System GE Multilin...
  • Page 165: Modbus User Map

    “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis- ADDRESS played for all registers. Different values can be entered as required in any of the register positions. ADDRESS GE Multilin F35 Multiple Feeder Protection System 5-35...
  • Page 166: Real Time Clock

    F35 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used. Only timestamps in the event recorder and communications protocols are affected by the daylight savings time set- tings. The reported real-time clock value does not change. NOTE 5-36 F35 Multiple Feeder Protection System GE Multilin...
  • Page 167: Fault Reports

    Elements operated at the time of triggering. • Events: 9 before trigger and 7 after trigger (only available via the relay webpage). • Fault duration times for each breaker (created by the breaker arcing current feature). GE Multilin F35 Multiple Feeder Protection System 5-37...
  • Page 168 It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). 5-38 F35 Multiple Feeder Protection System GE Multilin...
  • Page 169: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. GE Multilin F35 Multiple Feeder Protection System...
  • Page 170 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. 5-40 F35 Multiple Feeder Protection System GE Multilin...
  • Page 171: Data Logger

    The relay automatically partitions the available memory between the channels in use. Exam- ple storage capacities for a system frequency of 60 Hz are shown in the following table. GE Multilin F35 Multiple Feeder Protection System...
  • Page 172 – entering this number via the relay keypad will cause the corresponding parameter to be displayed. • DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to “Off” without over-writing old data. 5-42 F35 Multiple Feeder Protection System GE Multilin...
  • Page 173: Demand

    Start Demand Interval logic input pulses. Each new value of demand becomes available at the end of each pulse. Assign a FlexLogic™ operand to the setting to program the input for the new DEMAND TRIGGER demand interval pulses. GE Multilin F35 Multiple Feeder Protection System 5-43...
  • Page 174: User-Programmable Leds

    LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress. 5-44 F35 Multiple Feeder Protection System GE Multilin...
  • Page 175 Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This is to be performed via user-programmable pushbutton 1. GE Multilin F35 Multiple Feeder Protection System...
  • Page 176 “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com- munications channel, or from any programmed operand, even if the LED operand state de-asserts. 5-46 F35 Multiple Feeder Protection System GE Multilin...
  • Page 177: User-Programmable Self Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the is “Enabled” in this ETHERNET SWITCH FAIL FUNCTION menu. NOTE GE Multilin F35 Multiple Feeder Protection System 5-47...
  • Page 178: Control Pushbuttons

    An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key must be released before the next one can be pressed. 5-48 F35 Multiple Feeder Protection System GE Multilin...
  • Page 179: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled GE Multilin F35 Multiple Feeder Protection System 5-49...
  • Page 180 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. 5-50 F35 Multiple Feeder Protection System GE Multilin...
  • Page 181 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. GE Multilin F35 Multiple Feeder Protection System...
  • Page 182 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-52 F35 Multiple Feeder Protection System GE Multilin...
  • Page 183 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin F35 Multiple Feeder Protection System 5-53...
  • Page 184: Flex State Parameters

    16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers. 5-54 F35 Multiple Feeder Protection System GE Multilin...
  • Page 185: User-Definable Displays

    INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin F35 Multiple Feeder Protection System 5-55...
  • Page 186 4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-56 F35 Multiple Feeder Protection System GE Multilin...
  • Page 187 On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output GE Multilin F35 Multiple Feeder Protection System...
  • Page 188 Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. 5-58 F35 Multiple Feeder Protection System GE Multilin...
  • Page 189 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. GE Multilin F35 Multiple Feeder Protection System...
  • Page 190 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–13: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. 5-60 F35 Multiple Feeder Protection System GE Multilin...
  • Page 191 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin F35 Multiple Feeder Protection System 5-61...
  • Page 192 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. 5-62 F35 Multiple Feeder Protection System GE Multilin...
  • Page 193 FlexLogic™ operand is set. When the total message counter reaches the user-defined maximum specified by the set- CRC ALARM CH1 MESSAGE COUNT ting, both the counters reset and the monitoring process is restarted. GE Multilin F35 Multiple Feeder Protection System 5-63...
  • Page 194: Direct Inputs/Outputs

    The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration. The total number of unreturned input and output messages is available as the   ACTUAL VALUES STATUS DIRECT  actual value. INPUTS UNRETURNED MSG COUNT CH1 5-64 F35 Multiple Feeder Protection System GE Multilin...
  • Page 195: Teleprotection

    TERMINAL 1 ID NUMBER 5.2.19 INSTALLATION   PATH: SETTINGS PRODUCT SETUP INSTALLATION Range: Not Programmed, Programmed  INSTALLATION RELAY SETTINGS:  Not Programmed Range: up to 20 alphanumeric characters RELAY NAME: MESSAGE Relay-1 GE Multilin F35 Multiple Feeder Protection System 5-65...
  • Page 196 This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. 5-66 F35 Multiple Feeder Protection System GE Multilin...
  • Page 197: Remote Resources Configuration

    Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are dis- tinct binary channels that provide high-speed protection quality signaling between relays through a Brick. For additional information on how to configure a relay with a process bus module, please refer to GE publication number GEK-113500: HardFiber System Instruction Manual.
  • Page 198: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-68 F35 Multiple Feeder Protection System GE Multilin...
  • Page 199: Power System

    Range: ABC, ACB PHASE ROTATION: MESSAGE Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6 FREQUENCY AND PHASE MESSAGE REFERENCE: SRC 1 Range: Disabled, Enabled FREQUENCY TRACKING: MESSAGE Enabled GE Multilin F35 Multiple Feeder Protection System 5-69...
  • Page 200: Signal Sources

    For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5”, scaled to whichever CT has the higher ratio. Selecting “None” hides the associated actual values. 5-70 F35 Multiple Feeder Protection System GE Multilin...
  • Page 201 An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration: INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 GE Multilin F35 Multiple Feeder Protection System 5-71...
  • Page 202 CT/VT inputs that are used to provide the data. DSP Bank Source 1 Source 2 Amps Amps Source 3 51BF-1 51BF-2 Volts Amps Amps Volts Source 4 UR Relay Figure 5–20: EXAMPLE USE OF SOURCES 5-72 F35 Multiple Feeder Protection System GE Multilin...
  • Page 203: Breakers

    Range: 0.000 to 1 000 000.000 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled GE Multilin F35 Multiple Feeder Protection System 5-73...
  • Page 204 MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after an operator has initiated a manual close command to operate a circuit breaker. • BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service. 5-74 F35 Multiple Feeder Protection System GE Multilin...
  • Page 205 5.4 SYSTEM SETUP Figure 5–21: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin F35 Multiple Feeder Protection System 5-75...
  • Page 206 BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING BREAKER 1 OUT OF SV = Off 842025A1.CDR Figure 5–22: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) 5-76 F35 Multiple Feeder Protection System GE Multilin...
  • Page 207: Disconnect Switches

    1. • SWITCH 1 MODE: This setting selects “3-pole” mode, where all disconnect switch poles are operated simultaneously, or “1-pole” mode where all disconnect switch poles are operated either independently or simultaneously. GE Multilin F35 Multiple Feeder Protection System 5-77...
  • Page 208 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in the local control mode. NOTE 5-78 F35 Multiple Feeder Protection System GE Multilin...
  • Page 209 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–23: DISCONNECT SWITCH SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-79...
  • Page 210: Flexcurves

    1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-80 F35 Multiple Feeder Protection System GE Multilin...
  • Page 211 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin F35 Multiple Feeder Protection System 5-81...
  • Page 212 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the F35 are displayed in the following graphs. 5-82 F35 Multiple Feeder Protection System GE Multilin...
  • Page 213 842723A1.CDR Figure 5–27: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–28: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin F35 Multiple Feeder Protection System 5-83...
  • Page 214 Figure 5–29: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–30: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-84 F35 Multiple Feeder Protection System GE Multilin...
  • Page 215 Figure 5–31: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–32: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin F35 Multiple Feeder Protection System 5-85...
  • Page 216 Figure 5–33: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–34: RECLOSER CURVES GE119, GE135, AND GE202 5-86 F35 Multiple Feeder Protection System GE Multilin...
  • Page 217: Flexlogic

    Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. GE Multilin F35 Multiple Feeder Protection System 5-87...
  • Page 218 The virtual input is presently in the ON state. Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1"). 5-88 F35 Multiple Feeder Protection System GE Multilin...
  • Page 219 Same set of operands as shown for AUX UV1 ELEMENT: BKR ARC 1 OP Breaker arcing current 1 has operated Breaker arcing BKR ARC 2 OP Breaker arcing current 2 has operated GE Multilin F35 Multiple Feeder Protection System 5-89...
  • Page 220 Non-volatile latch 1 is ON (Logic = 1) Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0) LATCH 2 to LATCH 16 Same set of operands as shown for LATCH 1 5-90 F35 Multiple Feeder Protection System GE Multilin...
  • Page 221 Setting group 3 is active SETTING GROUP ACT 4 Setting group 4 is active SETTING GROUP ACT 5 Setting group 5 is active SETTING GROUP ACT 6 Setting group 6 is active GE Multilin F35 Multiple Feeder Protection System 5-91...
  • Page 222 (will not appear unless ordered) ↓ ↓ INPUTS/OUTPUTS: Cont Op 1 (will not appear unless ordered) Contact outputs, Cont Op 2 (will not appear unless ordered) current ↓ ↓ (from detector on form-A output only) 5-92 F35 Multiple Feeder Protection System GE Multilin...
  • Page 223 Communications source of the reset command. RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS  RESETTING menu) source of the reset command. RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command. GE Multilin F35 Multiple Feeder Protection System 5-93...
  • Page 224 2 to 16 any input is ‘1’ 2 to 16 all inputs are ‘1’ 2 to 16 all inputs are ‘0’ NAND 2 to 16 any input is ‘0’ only one input is ‘1’ 5-94 F35 Multiple Feeder Protection System GE Multilin...
  • Page 225: Flexlogic™ Rules

    If it is necessary to re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down and then back up. GE Multilin F35 Multiple Feeder Protection System 5-95...
  • Page 226: Flexlogic™ Example

    Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–37: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 5-96 F35 Multiple Feeder Protection System GE Multilin...
  • Page 227 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." GE Multilin F35 Multiple Feeder Protection System 5-97...
  • Page 228 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". 5-98 F35 Multiple Feeder Protection System GE Multilin...
  • Page 229 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) GE Multilin F35 Multiple Feeder Protection System 5-99...
  • Page 230: Flexlogic™ Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". 5-100 F35 Multiple Feeder Protection System GE Multilin...
  • Page 231: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin F35 Multiple Feeder Protection System 5-101...
  • Page 232 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-102 F35 Multiple Feeder Protection System GE Multilin...
  • Page 233 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–45: FLEXELEMENT™ INPUT MODE SETTING GE Multilin F35 Multiple Feeder Protection System 5-103...
  • Page 234 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-104 F35 Multiple Feeder Protection System GE Multilin...
  • Page 235: Non-Volatile Latches

    LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–46: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin F35 Multiple Feeder Protection System 5-105...
  • Page 236: Grouped Elements

    5.6.3 PHASE CURRENT a) INVERSE TIME OVERCURRENT CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 237 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 GE Multilin F35 Multiple Feeder Protection System 5-107...
  • Page 238 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-108 F35 Multiple Feeder Protection System GE Multilin...
  • Page 239 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–17: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 240 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The F35 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. 5-110 F35 Multiple Feeder Protection System GE Multilin...
  • Page 241 ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. GE Multilin F35 Multiple Feeder Protection System 5-111...
  • Page 242 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–48: PHASE TIME OVERCURRENT 1 SCHEME LOGIC 5-112 F35 Multiple Feeder Protection System GE Multilin...
  • Page 243 The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing curves are shown below for form-A contacts in a 60 Hz system. GE Multilin F35 Multiple Feeder Protection System 5-113...
  • Page 244 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–49: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES Figure 5–50: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC 5-114 F35 Multiple Feeder Protection System GE Multilin...
  • Page 245: Neutral Current

    RESET: NEUTRAL TOC1 PKP NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–51: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-115...
  • Page 246 RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–52: NEUTRAL IOC1 SCHEME LOGIC 5-116 F35 Multiple Feeder Protection System GE Multilin...
  • Page 247: Ground Current

    ETT NG RESET: GROUND TOC1 PKP GROUND TOC1 IG ≥ PICKUP GROUND TOC1 DPO SOURCE: GROUND TOC1 OP ETT NG GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–53: GROUND TOC1 SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-117...
  • Page 248 ETT NG DELAY: GROUND IOC1 GROUND IOC1 RESET ETT NG PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP ETT NG GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–54: GROUND IOC1 SCHEME LOGIC 5-118 F35 Multiple Feeder Protection System GE Multilin...
  • Page 249: Voltage Elements

    The time delay is adjustable from 0 to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char- acteristic. GE Multilin F35 Multiple Feeder Protection System 5-119...
  • Page 250 V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–55: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE 5-120 F35 Multiple Feeder Protection System GE Multilin...
  • Page 251 FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–56: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-121...
  • Page 252 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–57: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC 5-122 F35 Multiple Feeder Protection System GE Multilin...
  • Page 253 AUX UV1 PKP AUX UV1 DPO SETTING SETTING AUX UV1 OP AUX UV1 MINIMUM AUX UV1 SIGNAL VOLTAGE: SOURCE: < AUX VOLT Vx Vx Minimum 827849A2.CDR Figure 5–58: AUXILIARY UNDERVOLTAGE SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-123...
  • Page 254 Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–59: AUXILIARY OVERVOLTAGE SCHEME LOGIC 5-124 F35 Multiple Feeder Protection System GE Multilin...
  • Page 255: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. GE Multilin F35 Multiple Feeder Protection System...
  • Page 256 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–61: TRIP BUS LOGIC 5-126 F35 Multiple Feeder Protection System GE Multilin...
  • Page 257: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 GE Multilin F35 Multiple Feeder Protection System 5-127...
  • Page 258: Selector Switch

    SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled 5-128 F35 Multiple Feeder Protection System GE Multilin...
  • Page 259 SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest GE Multilin F35 Multiple Feeder Protection System 5-129...
  • Page 260 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. 5-130 F35 Multiple Feeder Protection System GE Multilin...
  • Page 261 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–63: TIME-OUT MODE GE Multilin F35 Multiple Feeder Protection System 5-131...
  • Page 262 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 5-132 F35 Multiple Feeder Protection System GE Multilin...
  • Page 263 SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–65: SELECTOR SWITCH LOGIC GE Multilin F35 Multiple Feeder Protection System 5-133...
  • Page 264: Underfrequency

    ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–66: UNDERFREQUENCY SCHEME LOGIC 5-134 F35 Multiple Feeder Protection System GE Multilin...
  • Page 265: Autoreclose

    4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE GE Multilin F35 Multiple Feeder Protection System 5-135...
  • Page 266 Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). 5-136 F35 Multiple Feeder Protection System GE Multilin...
  • Page 267 ‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE GE Multilin F35 Multiple Feeder Protection System 5-137...
  • Page 268 5.7 CONTROL ELEMENTS 5 SETTINGS To sheet 2 Figure 5–67: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) 5-138 F35 Multiple Feeder Protection System GE Multilin...
  • Page 269 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–68: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) GE Multilin F35 Multiple Feeder Protection System 5-139...
  • Page 270 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–69: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT 5-140 F35 Multiple Feeder Protection System GE Multilin...
  • Page 271: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin F35 Multiple Feeder Protection System 5-141...
  • Page 272 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–71: TRIP CIRCUIT EXAMPLE 1 5-142 F35 Multiple Feeder Protection System GE Multilin...
  • Page 273 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). GE Multilin F35 Multiple Feeder Protection System 5-143...
  • Page 274: Digital Counters

    Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter. 5-144 F35 Multiple Feeder Protection System GE Multilin...
  • Page 275 If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation. GE Multilin F35 Multiple Feeder Protection System...
  • Page 276: 8-Bit Switches

    8BIT SW 1 ARG B0: MESSAGE Range: FlexLogic™ operand 8BIT SW 1 ARG B1: MESSAGE ↓ Range: FlexLogic™ operand 8BIT SW 1 ARG B7: MESSAGE Range: FlexLogic™ operand 8BIT SW 1 CONTROL: MESSAGE 5-146 F35 Multiple Feeder Protection System GE Multilin...
  • Page 277 FLEXLOG C OPE AND Off = 0 8BIT SW 1 ARG B7: 8BIT SWITCH 1 BIT 7 Off = 0 ETT NG 8BIT SW 1 CONTROL: Off = 0 842017A1.CDR Figure 5–74: 8-BIT SWITCH LOGIC GE Multilin F35 Multiple Feeder Protection System 5-147...
  • Page 278: Monitoring Elements

    MESSAGE See page 5–151.   INCIPIENT FAULT 4 MESSAGE See page 5–151.   INCIPIENT FAULT 5 MESSAGE See page 5–151.   INCIPIENT FAULT 6 MESSAGE See page 5–151.  5-148 F35 Multiple Feeder Protection System GE Multilin...
  • Page 279 • BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. GE Multilin F35 Multiple Feeder Protection System 5-149...
  • Page 280 BKR 1 ARCING AMP C Φ 827071A3.CDR BKR 1 OPERATING TIME A Φ BKR 1 OPERATING TIME B Φ BKR 1 OPERATING TIME C Φ BKR 1 OPERATING TIME Figure 5–76: BREAKER ARCING CURRENT SCHEME LOGIC 5-150 F35 Multiple Feeder Protection System GE Multilin...
  • Page 281 B current (red). The superimposed current shows two fault current blips as the data slides through the two-cycle memory window. During the actual fault, the neutral current and the superimposed phase B currents closely correspond, confirming the incipient fault hypothesis and identifying the affected phase. GE Multilin F35 Multiple Feeder Protection System 5-151...
  • Page 282 INCIPNT FLT 1 DETECT WINDOW: This setting specifies a time window for “Counts per window” mode of operation. • INCIPIENT FAULT 1 RESET DELAY: This setting specifies a reset time for the output after the trip is initiated. 5-152 F35 Multiple Feeder Protection System GE Multilin...
  • Page 283 INCIPIENT FAULT 1 PH A FAULTS INCIPIENT FAULT 1 PH B FAULTS COMMAND INCIPIENT FAULT 1 PH C FAULTS CLEAR INCIPIENT FAULT COUNTERS RESET = Yes 832028A1.CDR Figure 5–78: INCIPIENT CABLE FAULT DETECTOR SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-153...
  • Page 284: Inputs/Outputs

    The update is performed at the beginning of the protection pass so all protection and control functions, as well as FlexLogic™ equations, are fed with the updated states of the contact inputs. 5-154 F35 Multiple Feeder Protection System GE Multilin...
  • Page 285 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin F35 Multiple Feeder Protection System 5-155...
  • Page 286: Virtual Inputs

    “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–80: VIRTUAL INPUTS SCHEME LOGIC 5-156 F35 Multiple Feeder Protection System GE Multilin...
  • Page 287: Contact Outputs

    L-Cont Op 1 Range: FlexLogic™ operand OUTPUT H1a OPERATE: MESSAGE Range: FlexLogic™ operand OUTPUT H1a RESET: MESSAGE Range: Operate-dominant, Reset-dominant OUTPUT H1a TYPE: MESSAGE Operate-dominant Range: Disabled, Enabled OUTPUT H1a EVENTS: MESSAGE Disabled GE Multilin F35 Multiple Feeder Protection System 5-157...
  • Page 288 Application Example 3: A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement this functionality as described below: 5-158 F35 Multiple Feeder Protection System GE Multilin...
  • Page 289: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin F35 Multiple Feeder Protection System 5-159...
  • Page 290: Remote Devices

    PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE    setting. CONFIGURATION TRANSMISSION GSSE GSSE ID In F35 releases previous to 5.0x, these name strings were represented by the setting. RELAY NAME 5-160 F35 Multiple Feeder Protection System GE Multilin...
  • Page 291: Remote Inputs

    REMOTE IN 1 DEFAULT STATE the remote device sending the point is declared to be non-communicating. The following choices are available: GE Multilin F35 Multiple Feeder Protection System 5-161...
  • Page 292: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled 5-162 F35 Multiple Feeder Protection System GE Multilin...
  • Page 293: Resetting

    RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) GE Multilin F35 Multiple Feeder Protection System 5-163...
  • Page 294: Direct Inputs And Outputs

    APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. 5-164 F35 Multiple Feeder Protection System GE Multilin...
  • Page 295 DIRECT INPUT 7 DEFAULT STATE : "3" DIRECT INPUT 8 DEVICE ID : "3" DIRECT INPUT 8 BIT NUMBER : select "On" for security, select "Off" for dependability DIRECT INPUT 8 DEFAULT STATE GE Multilin F35 Multiple Feeder Protection System 5-165...
  • Page 296 DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: 5-166 F35 Multiple Feeder Protection System GE Multilin...
  • Page 297: Teleprotection Inputs And Outputs

    Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-2 MESSAGE DEFAULT: Off ↓ Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-16 MESSAGE DEFAULT: Off GE Multilin F35 Multiple Feeder Protection System 5-167...
  • Page 298 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. 5-168 F35 Multiple Feeder Protection System GE Multilin...
  • Page 299: Iec 61850 Goose Analogs

    GOOSE analog input value. GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to configure GOOSE Analog, so that it can be used in a FlexElement. GE Multilin F35 Multiple Feeder Protection System 5-169...
  • Page 300: Iec 61850 Goose Integers

    “Default Value”, then the value of the GOOSE uinteger input is defined by the setting. UINTEGER 1 DEFAULT The GOOSE integer input FlexInteger™ values are available for use in other F35 functions that use FlexInteger™ values. 5-170 F35 Multiple Feeder Protection System GE Multilin...
  • Page 301: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin F35 Multiple Feeder Protection System 5-171...
  • Page 302: Rtd Inputs

    1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-172 F35 Multiple Feeder Protection System GE Multilin...
  • Page 303 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin F35 Multiple Feeder Protection System 5-173...
  • Page 304: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–87: DCMA OUTPUT CHARACTERISTIC 5-174 F35 Multiple Feeder Protection System GE Multilin...
  • Page 305 The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: GE Multilin F35 Multiple Feeder Protection System 5-175...
  • Page 306 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-176 F35 Multiple Feeder Protection System GE Multilin...
  • Page 307: Testing

    The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table. GE Multilin F35 Multiple Feeder Protection System...
  • Page 308: Force Contact Inputs

    Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis- abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled. 5-178 F35 Multiple Feeder Protection System GE Multilin...
  • Page 309: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin F35 Multiple Feeder Protection System 5-179...
  • Page 310 5.10 TESTING 5 SETTINGS 5-180 F35 Multiple Feeder Protection System GE Multilin...
  • Page 311: Actual Values

     GOOSE UINTEGERS  EGD PROTOCOL See page 6-8.  STATUS  TELEPROT CH TESTS See page 6-9.   INCIPIENT FAULT See page 6-9.   ETHERNET SWITCH See page 6-10.  GE Multilin F35 Multiple Feeder Protection System...
  • Page 312  DATA LOGGER See page 6-23.   MAINTENANCE See page 6-24.   ACTUAL VALUES  MODEL INFORMATION See page 6-25.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-25.  F35 Multiple Feeder Protection System GE Multilin...
  • Page 313: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin F35 Multiple Feeder Protection System...
  • Page 314: Remote Double-Point Status Inputs

    The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. F35 Multiple Feeder Protection System GE Multilin...
  • Page 315: Virtual Outputs

    The present state of up to 16 programmed remote devices is shown here. The message indi- ALL REMOTE DEVICES ONLINE cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin F35 Multiple Feeder Protection System...
  • Page 316: Digital Counters

      PATH: ACTUAL VALUES STATUS FLEX STATES Range: Off, On  FLEX STATES PARAM 1: Off  Range: Off, On PARAM 2: Off MESSAGE ↓ Range: Off, On PARAM 256: Off MESSAGE F35 Multiple Feeder Protection System GE Multilin...
  • Page 317: Ethernet

    The UNRETURNED MSG COUNT CRC FAIL values can be cleared using the command. COUNT CLEAR DIRECT I/O COUNTERS values represent the state of each direct input. DIRECT INPUT 1 DIRECT INPUT (32) GE Multilin F35 Multiple Feeder Protection System...
  • Page 318: Direct Devices Status

    SIGNATURE: FAST EXCHANGE 1 MESSAGE DATA LENGTH: These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the fast EGD exchange is displayed. F35 Multiple Feeder Protection System GE Multilin...
  • Page 319: Teleprotection Channel Tests

    The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values can be reset to zero with the   command. COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT COUNTERS GE Multilin F35 Multiple Feeder Protection System...
  • Page 320: Ethernet Switch

    • SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module. 6-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 321: Metering Conventions

    WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin F35 Multiple Feeder Protection System 6-11...
  • Page 322 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 323 SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS GE Multilin F35 Multiple Feeder Protection System 6-13...
  • Page 324: Sources

    SRC 1 RMS Ic: MESSAGE 0.000 SRC 1 RMS In: MESSAGE 0.000 SRC 1 PHASOR Ia: MESSAGE 0.000 0.0° SRC 1 PHASOR Ib: MESSAGE 0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° 6-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 325 SRC 1 PHASOR Vcg: MESSAGE 0.000 0.0° SRC 1 RMS Vab: MESSAGE 0.00 SRC 1 RMS Vbc: MESSAGE 0.00 SRC 1 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° GE Multilin F35 Multiple Feeder Protection System 6-15...
  • Page 326 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 SRC 1 APPARENT PWR MESSAGE 3φ: 0.000 SRC 1 APPARENT PWR MESSAGE φa: 0.000 6-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 327 DMD IA MAX: MESSAGE 0.000 SRC 1 DMD IA DATE: MESSAGE 2001/07/31 16:30:07 SRC 1 DMD IB: MESSAGE 0.000 SRC 1 DMD IB MAX: MESSAGE 0.000 SRC 1 DMD IB DATE: MESSAGE 2001/07/31 16:30:07 GE Multilin F35 Multiple Feeder Protection System 6-17...
  • Page 328 The signal used for frequency estimation is low-pass filtered. The SYSTEM SETUP POWER SYSTEM final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and transients. 6-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 329: Tracking Frequency

    The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the setting in the   menu. Refer to the FREQUENCY AND PHASE REFERENCE SETTINGS SYSTEM SETUP POWER SYSTEM Power System section of chapter 5 for additional details. GE Multilin F35 Multiple Feeder Protection System 6-19...
  • Page 330: Flexelements

    2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered. The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received via IEC 61850 GOOSE messages sent from other devices. 6-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 331: Transducer Inputs/Outputs

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin F35 Multiple Feeder Protection System 6-21...
  • Page 332: Records

    If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the menu for clearing event records.  COMMANDS CLEAR RECORDS 6-22 F35 Multiple Feeder Protection System GE Multilin...
  • Page 333: Oscillography

    It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the  menu for clearing data logger records. COMMANDS CLEAR RECORDS GE Multilin F35 Multiple Feeder Protection System 6-23...
  • Page 334: Breaker Maintenance

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 335: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  F35-E00-HCH-F8F-H6G Range: standard GE multilin order code format...
  • Page 336 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 337: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin F35 Multiple Feeder Protection System...
  • Page 338 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. F35 Multiple Feeder Protection System GE Multilin...
  • Page 339: Relay Maintenance

    For example, it may be desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self- checking variables are reset to their initial state and diagnostics will restart from scratch. GE Multilin F35 Multiple Feeder Protection System...
  • Page 340: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE F35 Multiple Feeder Protection System GE Multilin...
  • Page 341 How often the test is performed: On power up and whenever the   PRODUCT SETUP INSTALLATION RELAY SETTINGS setting is altered • What to do: Program all settings and then set   to “Programmed”. PRODUCT SETUP INSTALLATION RELAY SETTINGS GE Multilin F35 Multiple Feeder Protection System...
  • Page 342 – Proper cable functionality (that is, check for physical damage or perform a continuity test). – The IRIG-B receiver is functioning. – Check the input signal level (it may be less than specification). F35 Multiple Feeder Protection System GE Multilin...
  • Page 343 What to do: Check direct input and output configuration and wiring. REMOTE DEVICE FAIL: COMM Path Incomplete • Latched target message: No. • Description of problem: One or more GOOSE devices are not responding. GE Multilin F35 Multiple Feeder Protection System...
  • Page 344 Description of problem: Abnormal restart from modules being removed or inserted while the F35 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven. • What to do: Contact the factory. F35 Multiple Feeder Protection System GE Multilin...
  • Page 345: Security

    The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated every five seconds. A command or setting write operation is required to update the state of all the remote and local security operands shown above. NOTE GE Multilin F35 Multiple Feeder Protection System...
  • Page 346: Password Security Menu

    If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE F35 Multiple Feeder Protection System GE Multilin...
  • Page 347: Remote Passwords

     SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min GE Multilin F35 Multiple Feeder Protection System...
  • Page 348: Dual Permission Security Access

    If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the local setting password to gain setting access. F35 Multiple Feeder Protection System GE Multilin...
  • Page 349 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin F35 Multiple Feeder Protection System...
  • Page 350: Settings Security

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. F35 Multiple Feeder Protection System GE Multilin...
  • Page 351 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin F35 Multiple Feeder Protection System...
  • Page 352 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F35 Multiple Feeder Protection System GE Multilin...
  • Page 353 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin F35 Multiple Feeder Protection System...
  • Page 354: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. 8-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 355 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin F35 Multiple Feeder Protection System 8-11...
  • Page 356: Settings File Traceability

    SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 8–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. 8-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 357 Figure 8–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA GE Multilin F35 Multiple Feeder Protection System 8-13...
  • Page 358 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. 8-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 359: Enervista Security Management System

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin F35 Multiple Feeder Protection System...
  • Page 360: Modifying User Privileges

    The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 361 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin F35 Multiple Feeder Protection System 8-17...
  • Page 362 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 363: Theory Of Operation

    Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 9.7) GE Multilin F35 Multiple Feeder Protection System...
  • Page 364 -- - V (EQ 9.14) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 F35 Multiple Feeder Protection System GE Multilin...
  • Page 365 FAULT TYPE FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 9–2: FAULT LOCATOR SCHEME GE Multilin F35 Multiple Feeder Protection System...
  • Page 366 9.1 FAULT LOCATOR 9 THEORY OF OPERATION F35 Multiple Feeder Protection System GE Multilin...
  • Page 367: Commissioning

    The injected frequency should smoothly ramp through the set threshold, with the ramp starting frequency sufficiently out- side the threshold so the relay becomes conditioned to the trend before operation. For typical interconnected power sys- tems, the recommended testing ramp rate is 0.20 Hz/s. GE Multilin F35 Multiple Feeder Protection System 10-1...
  • Page 368 20 ms. The tracking frequency should not be used in timing measurements, as its algorithm involves phase locking, which purposely sets its frequency high or low to allow the F35 sample clock to catch-up or wait as necessary to reach synchro- nism with the power system. 10-2 F35 Multiple Feeder Protection System GE Multilin...
  • Page 369: Parameter Lists

    SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude 6241 SRC 2 I_2 Angle Amps Source 2 negative-sequence current angle 6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude GE Multilin F35 Multiple Feeder Protection System...
  • Page 370 SRC 4 I_2 Angle Amps Source 4 negative-sequence current angle 6370 SRC 4 Igd Mag Degrees Source 4 differential ground current magnitude 6372 SRC 4 Igd Angle Amps Source 4 differential ground current angle F35 Multiple Feeder Protection System GE Multilin...
  • Page 371 SRC 6 Igd Mag Degrees Source 6 differential ground current magnitude 6500 SRC 6 Igd Angle Amps Source 6 differential ground current angle 6656 SRC 1 Vag RMS Volts Source 1 phase AG voltage RMS GE Multilin F35 Multiple Feeder Protection System...
  • Page 372 6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS 6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude 6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle F35 Multiple Feeder Protection System GE Multilin...
  • Page 373 SRC 4 Vca RMS Volts Source 4 phase CA voltage RMS 6869 SRC 4 Vab Mag Volts Source 4 phase AB voltage magnitude 6871 SRC 4 Vab Angle Degrees Source 4 phase AB voltage angle GE Multilin F35 Multiple Feeder Protection System...
  • Page 374 SRC 6 Vag Angle Degrees Source 6 phase AG voltage angle 6985 SRC 6 Vbg Mag Volts Source 6 phase BG voltage magnitude 6987 SRC 6 Vbg Angle Degrees Source 6 phase BG voltage angle F35 Multiple Feeder Protection System GE Multilin...
  • Page 375 Source 2 phase C reactive power 7216 SRC 2 S Source 2 three-phase apparent power 7218 SRC 2 Sa Source 2 phase A apparent power 7220 SRC 2 Sb Source 2 phase B apparent power GE Multilin F35 Multiple Feeder Protection System...
  • Page 376 Source 5 phase B reactive power 7310 SRC 5 Qc Vars Source 5 phase C reactive power 7312 SRC 5 S Source 5 three-phase apparent power 7314 SRC 5 Sa Source 5 phase A apparent power F35 Multiple Feeder Protection System GE Multilin...
  • Page 377 7720 SRC 3 Demand var Vars Source 3 reactive power demand 7722 SRC 3 Demand Va Source 3 apparent power demand 7728 SRC 4 Demand Ia Amps Source 4 phase A current demand GE Multilin F35 Multiple Feeder Protection System...
  • Page 378 Fault 2 pre-fault phase A current angle 9065 Prefault Ib Mag [1] Amps Fault 2 pre-fault phase B current magnitude 9067 Prefault Ib Ang [1] Degrees Fault 2 pre-fault phase B current angle A-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 379 Postfault Vc Mag [2] Volts Fault 3 post-fault phase C voltage magnitude 9135 Postfault Vc Ang [2] Degrees Fault 3 post-fault phase C voltage angle 9136 Fault Type [2] Fault 3 type GE Multilin F35 Multiple Feeder Protection System A-11...
  • Page 380 Fault 5 post-fault phase C current angle 9203 Postfault Va Mag [4] Volts Fault 5 post-fault phase A voltage magnitude 9205 Postfault Va Ang [4] Degrees Fault 5 post-fault phase A voltage angle A-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 381 RTD input 14 actual value 13566 RTD Inputs 15 Value RTD input 15 actual value 13567 RTD Inputs 16 Value RTD input 16 actual value 13568 RTD Inputs 17 Value RTD input 17 actual value GE Multilin F35 Multiple Feeder Protection System A-13...
  • Page 382 39445 FlexElement 11 Value FlexElement™ 11 actual value 39447 FlexElement 12 Value FlexElement™ 12 actual value 39449 FlexElement 13 Value FlexElement™ 13 actual value 39451 FlexElement 14 Value FlexElement™ 14 actual value A-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 383: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin F35 Multiple Feeder Protection System A-15...
  • Page 384 A.1 PARAMETER LISTS APPENDIX A A-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 385: Introduction

    Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin F35 Multiple Feeder Protection System...
  • Page 386: Algorithm

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC F35 Multiple Feeder Protection System GE Multilin...
  • Page 387: Modbus Function Codes

    1 to 127 though only a small subset is generally needed. The relay supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail. FUNCTION CODE MODBUS DEFINITION GE MULTILIN DEFINITION Read holding registers Read actual values or settings Read holding registers...
  • Page 388: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high F35 Multiple Feeder Protection System GE Multilin...
  • Page 389: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin F35 Multiple Feeder Protection System...
  • Page 390: File Transfers

    Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT F35 Multiple Feeder Protection System GE Multilin...
  • Page 391: Modbus Password Operation

    Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP. GE Multilin F35 Multiple Feeder Protection System...
  • Page 392: Memory Mapping

    0419 Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) 041B Virtual Input 28 State 0 to 1 F108 0 (Off) F35 Multiple Feeder Protection System GE Multilin...
  • Page 393 ...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 FlexStates (Read Only) 0900 FlexState Bits (16 items) 0 to 65535 F001 Element States (Read Only) 1000 Element Operate States (64 items) 0 to 65535 F502 GE Multilin F35 Multiple Feeder Protection System...
  • Page 394 Source 1 Phase A Current Magnitude 0 to 999999.999 0.001 F060 180A Source 1 Phase A Current Angle -359.9 to 0 degrees F002 180B Source 1 Phase B Current Magnitude 0 to 999999.999 0.001 F060 B-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 395 1A2B Source 1 Negative Sequence Voltage Angle -359.9 to 0 degrees F002 1A2C Reserved (20 items) F001 1A40 ...Repeated for Source 2 1A80 ...Repeated for Source 3 1AC0 ...Repeated for Source 4 GE Multilin F35 Multiple Feeder Protection System B-11...
  • Page 396 Frequency for Source 1 F003 1D82 Frequency for Source 2 F003 1D84 Frequency for Source 3 F003 1D86 Frequency for Source 4 F003 1D88 Frequency for Source 5 F003 1D8A Frequency for Source 6 F003 B-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 397 Breaker 1 Operating Time Phase B 0 to 65535 F001 21E8 Breaker 1 Operating Time Phase C 0 to 65535 F001 21E9 Breaker 1 Operating Time 0 to 65535 F001 21EA ...Repeated for Breaker Arcing Current 2 GE Multilin F35 Multiple Feeder Protection System B-13...
  • Page 398 263B ... Repeated for double-point status input 4 2644 ... Repeated for double-point status input 5 IEC 61850 GGIO5 configuration (read/write setting registers) 26B0 IEC 61850 GGIO5 uinteger input 1 operand F612 B-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 399 Number of Fault Reports 0 to 65535 F001 Fault Report Actuals (Read Only Non-Volatile) (15 modules) 3030 Fault Report 1 Time 0 to 4294967295 F050 3032 Fault Report 2 Time 0 to 4294967295 F050 GE Multilin F35 Multiple Feeder Protection System B-15...
  • Page 400 RTD Input Values (Read Only) (48 modules) 34F0 RTD Input 1 Value -32768 to 32767 °C F002 34F1 RTD Input 2 Value -32768 to 32767 °C F002 34F2 RTD Input 3 Value -32768 to 32767 °C F002 B-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 401 Passwords (Read/Write Command) 4000 Command Password Setting 0 to 4294967295 F003 Passwords (Read/Write Setting) 4002 Setting Password Setting 0 to 4294967295 F003 Passwords (Read/Write) 4008 Command Password Entry 0 to 4294967295 F003 GE Multilin F35 Multiple Feeder Protection System B-17...
  • Page 402 F102 0 (Disabled) 40AA DNP Unsolicited Responses Timeout 0 to 60 F001 40AB DNP unsolicited responses maximum retries 1 to 255 F001 40AC DNP unsolicited responses destination address 0 to 65519 F001 B-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 403 Ethernet switch (Read Only Actual Values) 4151 Ethernet switch MAC address F072 4154 Ethernet switch Port 1 Status 0 to 2 F134 0 (Fail) 4155 Ethernet switch Port 2 Status 0 to 2 F134 0 (Fail) GE Multilin F35 Multiple Feeder Protection System B-19...
  • Page 404 1 (Self-Reset) 4282 ...Repeated for User-Programmable LED 2 4284 ...Repeated for User-Programmable LED 3 4286 ...Repeated for User-Programmable LED 4 4288 ...Repeated for User-Programmable LED 5 428A ...Repeated for User-Programmable LED 6 B-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 405 User Programmable Battery Fail Function 0 to 1 F102 1 (Enabled) 4447 User Programmable SNTP Fail Function 0 to 1 F102 1 (Enabled) 4448 User Programmable IRIG-B Fail Function 0 to 1 F102 1 (Enabled) GE Multilin F35 Multiple Feeder Protection System B-21...
  • Page 406 ...Repeated for incipient cable fault detector 4 46DE ...Repeated for incipient cable fault detector 5 46E9 ...Repeated for incipient cable fault detector 6 Breaker control (read/write settings) 4700 Breaker 1 function 0 to 1 F102 0 (Disabled) B-22 F35 Multiple Feeder Protection System GE Multilin...
  • Page 407 ...Repeated for User-Definable Display 8 4D00 ...Repeated for User-Definable Display 9 4D20 ...Repeated for User-Definable Display 10 4D40 ...Repeated for User-Definable Display 11 4D60 ...Repeated for User-Definable Display 12 4D80 ...Repeated for User-Definable Display 13 GE Multilin F35 Multiple Feeder Protection System B-23...
  • Page 408 ...Repeated for RTD Input 14 550A ...Repeated for RTD Input 15 551D ...Repeated for RTD Input 16 5530 ...Repeated for RTD Input 17 5543 ...Repeated for RTD Input 18 5556 ...Repeated for RTD Input 19 B-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 409 ...Repeated for FlexLogic™ Timer 16 5880 ...Repeated for FlexLogic™ Timer 17 5888 ...Repeated for FlexLogic™ Timer 18 5890 ...Repeated for FlexLogic™ Timer 19 5898 ...Repeated for FlexLogic™ Timer 20 58A0 ...Repeated for FlexLogic™ Timer 21 GE Multilin F35 Multiple Feeder Protection System B-25...
  • Page 410 ...Repeated for Phase Instantaneous Overcurrent 11 5AB0 ...Repeated for Phase Instantaneous Overcurrent 12 Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules) 5B00 Neutral Time Overcurrent 1 Function 0 to 1 F102 0 (Disabled) B-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 411 ...Repeated for Ground Time Overcurrent 2 5D20 ...Repeated for Ground Time Overcurrent 3 5D30 ...Repeated for Ground Time Overcurrent 4 5D40 ...Repeated for Ground Time Overcurrent 5 5D50 ...Repeated for Ground Time Overcurrent 6 GE Multilin F35 Multiple Feeder Protection System B-27...
  • Page 412 0 to 65535 F300 6246 Autoreclose 1 Reset Lockout if Breaker Closed 0 to 1 F108 0 (Off) 6247 Autoreclose 1 Reset Lockout On Manual Close 0 to 1 F108 0 (Off) B-28 F35 Multiple Feeder Protection System GE Multilin...
  • Page 413 ...Repeated for Breaker 2 Arcing Current 72D4 ...Repeated for Breaker 3 Arcing Current 72DE ...Repeated for Breaker 4 Arcing Current 72E8 ...Repeated for Breaker 5 Arcing Current 72F2 ...Repeated for Breaker 6 Arcing Current GE Multilin F35 Multiple Feeder Protection System B-29...
  • Page 414 0 to 1 F102 0 (Disabled) 7553 Reserved (2 items) 7555 ...Repeated for disconnect switch 2 756A ...Repeated for disconnect switch 3 757F ...Repeated for disconnect switch 4 7594 ...Repeated for disconnect switch 5 B-30 F35 Multiple Feeder Protection System GE Multilin...
  • Page 415 ...Repeated for User Programmable Pushbutton 15 7DE5 ...Repeated for User Programmable Pushbutton 16 Underfrequency (Read/Write Setting) (6 modules) 7E10 Underfrequency Function 0 to 1 F102 0 (Disabled) 7E11 Underfrequency 1 Block 0 to 65535 F300 GE Multilin F35 Multiple Feeder Protection System B-31...
  • Page 416 0 to 1 F102 0 (Disabled) 7F69 Reserved (7 items) 0 to 65535 F001 7F70 ...Repeated for Auxiliary Undervoltage 2 7F80 ...Repeated for Auxiliary Undervoltage 3 Frequency (Read Only) 8000 Tracking Frequency F001 B-32 F35 Multiple Feeder Protection System GE Multilin...
  • Page 417 ...Repeated for Digital Element 4 8A50 ...Repeated for Digital Element 5 8A64 ...Repeated for Digital Element 6 8A78 ...Repeated for Digital Element 7 8A8C ...Repeated for Digital Element 8 8AA0 ...Repeated for Digital Element 9 GE Multilin F35 Multiple Feeder Protection System B-33...
  • Page 418 0 to 65535 F300 8E0B Trip Bus 1 Input 8 0 to 65535 F300 8E0C Trip Bus 1 Input 9 0 to 65535 F300 8E0D Trip Bus 1 Input 10 0 to 65535 F300 B-34 F35 Multiple Feeder Protection System GE Multilin...
  • Page 419 Fault Report 1 Z1 Magnitude 0.01 to 250 ohms 0.01 F001 9203 Fault Report 1 Z1 Angle 25 to 90 degrees F001 9204 Fault Report 1 Z0 Magnitude 0.01 to 650 ohms 0.01 F001 GE Multilin F35 Multiple Feeder Protection System B-35...
  • Page 420 ...Repeated for Direct Input/Output 9 946C ...Repeated for Direct Input/Output 10 9478 ...Repeated for Direct Input/Output 11 9484 ...Repeated for Direct Input/Output 12 9490 ...Repeated for Direct Input/Output 13 949C ...Repeated for Direct Input/Output 14 B-36 F35 Multiple Feeder Protection System GE Multilin...
  • Page 421 -2147483.647 to 2147483.647 0.001 F004 9A1B FlexElement™ 14 Actual -2147483.647 to 2147483.647 0.001 F004 9A1D FlexElement™ 15 Actual 0.001 F004 -2147483.647 to 2147483.647 9A1F FlexElement™ 16 Actual 0.001 F004 -2147483.647 to 2147483.647 GE Multilin F35 Multiple Feeder Protection System B-37...
  • Page 422 A700 Non-Volatile Latch 1 Function 0 to 1 F102 0 (Disabled) A701 Non-Volatile Latch 1 Type 0 to 1 F519 0 (Reset Dominant) A702 Non-Volatile Latch 1 Set 0 to 65535 F300 B-38 F35 Multiple Feeder Protection System GE Multilin...
  • Page 423 ...Repeated for IEC 61850 GOOSE analog input 6 AA2A ...Repeated for IEC 61850 GOOSE analog input 7 AA31 ...Repeated for IEC 61850 GOOSE analog input 8 AA38 ...Repeated for IEC 61850 GOOSE analog input 9 GE Multilin F35 Multiple Feeder Protection System B-39...
  • Page 424 Repeated for IEC 61850 XSWI8 AEDF Repeated for IEC 61850 XSWI9 AEE1 Repeated for IEC 61850 XSWI10 AEE3 Repeated for IEC 61850 XSWI11 AEE5 Repeated for IEC 61850 XSWI12 AEE7 Repeated for IEC 61850 XSWI13 B-40 F35 Multiple Feeder Protection System GE Multilin...
  • Page 425 F206 (None) AB33 IEC 61850 Logical Node PIOCx Name Prefix (72 items) 0 to 65534 F206 (None) AC0B IEC 61850 Logical Node PTOCx Name Prefix (24 items) 0 to 65534 F206 (None) GE Multilin F35 Multiple Feeder Protection System B-41...
  • Page 426 0.001 to 100 0.001 F003 10000 B0E4 IEC 61850 MMXU VAr.phsA Deadband 1 0.001 to 100 0.001 F003 10000 B0E6 IEC 61850 MMXU VAr.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B-42 F35 Multiple Feeder Protection System GE Multilin...
  • Page 427 ...Repeated for Module 2 B676 ...Repeated for Module 3 B6E1 ...Repeated for Module 4 B74C ...Repeated for Module 5 B7B7 ...Repeated for Module 6 B822 ...Repeated for Module 7 B88D ...Repeated for Module 8 GE Multilin F35 Multiple Feeder Protection System B-43...
  • Page 428 ...Repeated for Contact Input 37 BC28 ...Repeated for Contact Input 38 BC30 ...Repeated for Contact Input 39 BC38 ...Repeated for Contact Input 40 BC40 ...Repeated for Contact Input 41 BC48 ...Repeated for Contact Input 42 B-44 F35 Multiple Feeder Protection System GE Multilin...
  • Page 429 ...Repeated for Contact Input 91 BDD8 ...Repeated for Contact Input 92 BDE0 ...Repeated for Contact Input 93 BDE8 ...Repeated for Contact Input 94 BDF0 ...Repeated for Contact Input 95 BDF8 ...Repeated for Contact Input 96 GE Multilin F35 Multiple Feeder Protection System B-45...
  • Page 430 ...Repeated for Virtual Input 42 C028 ...Repeated for Virtual Input 43 C034 ...Repeated for Virtual Input 44 C040 ...Repeated for Virtual Input 45 C04C ...Repeated for Virtual Input 46 C058 ...Repeated for Virtual Input 47 B-46 F35 Multiple Feeder Protection System GE Multilin...
  • Page 431 ...Repeated for Virtual Output 29 C218 ...Repeated for Virtual Output 30 C220 ...Repeated for Virtual Output 31 C228 ...Repeated for Virtual Output 32 C230 ...Repeated for Virtual Output 33 C238 ...Repeated for Virtual Output 34 GE Multilin F35 Multiple Feeder Protection System B-47...
  • Page 432 ...Repeated for Virtual Output 83 C3C8 ...Repeated for Virtual Output 84 C3D0 ...Repeated for Virtual Output 85 C3D8 ...Repeated for Virtual Output 86 C3E0 ...Repeated for Virtual Output 87 C3E8 ...Repeated for Virtual Output 88 B-48 F35 Multiple Feeder Protection System GE Multilin...
  • Page 433 ...Repeated for Contact Output 28 C590 ...Repeated for Contact Output 29 C59C ...Repeated for Contact Output 30 C5A8 ...Repeated for Contact Output 31 C5B4 ...Repeated for Contact Output 32 C5C0 ...Repeated for Contact Output 33 GE Multilin F35 Multiple Feeder Protection System B-49...
  • Page 434 0 to 65535 F300 C779 Clear Breaker 5 Arcing Current operand 0 to 65535 F300 C77A Clear Breaker 6 Arcing Current operand 0 to 65535 F300 C77B Clear Demand operand 0 to 65535 F300 B-50 F35 Multiple Feeder Protection System GE Multilin...
  • Page 435 ...Repeated for Direct Input 32 Platform Direct Outputs (Read/Write Setting) (96 modules) CA10 Direct Output 1 Operand 0 to 65535 F300 CA11 Direct Output 1 Events 0 to 1 F102 0 (Disabled) GE Multilin F35 Multiple Feeder Protection System B-51...
  • Page 436 Direct I/O Channel 2 Unreturned Messages Alarm Events 0 to 1 F102 0 (Disabled) CAEC Reserved (4 items) F001 Remote Devices (Read/Write Setting) (16 modules) CB00 Remote Device 1 GSSE/GOOSE Application ID F209 “Remote Device 1“ B-52 F35 Multiple Feeder Protection System GE Multilin...
  • Page 437 ...Repeated for Remote Input 26 D0A4 ...Repeated for Remote Input 27 D0AE ...Repeated for Remote Input 28 D0B8 ...Repeated for Remote Input 29 D0C2 ...Repeated for Remote Input 30 D0CC ...Repeated for Remote Input 31 GE Multilin F35 Multiple Feeder Protection System B-53...
  • Page 438 ...Repeated for Remote Output 10 D2C8 ...Repeated for Remote Output 11 D2CC ...Repeated for Remote Output 12 D2D0 ...Repeated for Remote Output 13 D2D4 ...Repeated for Remote Output 14 D2D8 ...Repeated for Remote Output 15 B-54 F35 Multiple Feeder Protection System GE Multilin...
  • Page 439 IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value 0 to 2 F001 D341 IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value 0 to 2 F001 D342 IEC 61850 GGIO2.CF.SPCSO35.ctlModel Value 0 to 2 F001 D343 IEC 61850 GGIO2.CF.SPCSO36.ctlModel Value 0 to 2 F001 GE Multilin F35 Multiple Feeder Protection System B-55...
  • Page 440 ...Repeated for Remote Device 20 D3D0 ...Repeated for Remote Device 21 D3D4 ...Repeated for Remote Device 22 D3D8 ...Repeated for Remote Device 23 D3DC ...Repeated for Remote Device 24 D3E0 ...Repeated for Remote Device 25 B-56 F35 Multiple Feeder Protection System GE Multilin...
  • Page 441: Data Formats

    FlexCurve base address where the corresponding time UR_UINT32 TIME in SR format (alternate format for F050) value is stored. First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm; Minutes: 0 to 59 in steps of 1 GE Multilin F35 Multiple Feeder Protection System B-57...
  • Page 442 ENUMERATION: UNDERVOLTAGE CURVE SHAPES 0 = Wye; 1 = Delta 0 = Definite Time, 1 = Inverse Time F101 ENUMERATION: MESSAGE DISPLAY INTENSITY 0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% B-58 F35 Multiple Feeder Protection System GE Multilin...
  • Page 443 0 = 1 A, 1 = 5 A F124 ENUMERATION: LIST OF ELEMENTS bitmask element Phase Instantaneous Overcurrent 1 Phase Instantaneous Overcurrent 2 Phase Instantaneous Overcurrent 3 Phase Instantaneous Overcurrent 4 Phase Instantaneous Overcurrent 5 GE Multilin F35 Multiple Feeder Protection System B-59...
  • Page 444 Ground Instantaneous Overcurrent 12 Selector 1 Ground Time Overcurrent 1 Selector 2 Ground Time Overcurrent 2 Control pushbutton 1 Ground Time Overcurrent 3 Control pushbutton 2 Ground Time Overcurrent 4 Control pushbutton 3 B-60 F35 Multiple Feeder Protection System GE Multilin...
  • Page 445 Trip Bus 3 Digital Counter 7 Trip Bus 4 Digital Counter 8 Trip Bus 5 Digital Element 1 Trip Bus 6 Digital Element 2 RTD Input 1 Digital Element 3 RTD Input 2 GE Multilin F35 Multiple Feeder Protection System B-61...
  • Page 446 Incipient cable fault detector 6 User-Programmable Pushbutton 2 User-Programmable Pushbutton 3 F125 User-Programmable Pushbutton 4 ENUMERATION: ACCESS LEVEL User-Programmable Pushbutton 5 0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service B-62 F35 Multiple Feeder Protection System GE Multilin...
  • Page 447 0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles Brick Trouble 3 = 3 x 64 cycles, 4 = 1 x 128 cycles Field RTD Trouble Field TDR Trouble Remote Device Offline GE Multilin F35 Multiple Feeder Protection System B-63...
  • Page 448 0 = Disabled, 1 = Open, 2 = Closed System Integrity Recovery 07 F145 F148 ENUMERATION: ALPHABET LETTER ENUMERATION: FAULT TYPE bitmask type bitmask type bitmask type bitmask type bitmask fault type bitmask fault type null ABCG B-64 F35 Multiple Feeder Protection System GE Multilin...
  • Page 449 0 = 52a, 1 = 52b, 2 = None F166 ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca GE Multilin F35 Multiple Feeder Protection System B-65...
  • Page 450 GooseIn 8 ENUMERATION: PHASE LETTERS 0 = A, 1 = B, 2 = C F185 ENUMERATION: PHASE A,B,C, GROUND SELECTOR 0 = A, 1 = B, 2 = C, 3 = G B-66 F35 Multiple Feeder Protection System GE Multilin...
  • Page 451 0 = Disabled, 1 = Enabled, 2 = Custom ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER METHOD 0 = None, 1 = GSSE, 2 = GOOSE F200 TEXT40: 40-CHARACTER ASCII TEXT 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB GE Multilin F35 Multiple Feeder Protection System B-67...
  • Page 452 MMXU1.MX.A.phsB.cVal.ang.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU1.MX.A.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU1.MX.A.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU1.MX.A.neut.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU1.MX.A.neut.cVal.ang.f MMXU3.MX.TotPF.mag.f MMXU1.MX.W.phsA.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f B-68 F35 Multiple Feeder Protection System GE Multilin...
  • Page 453 MMXU4.MX.PhV.phsC.cVal.mag.f MMXU5.MX.VA.phsA.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU5.MX.VA.phsB.cVal.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU5.MX.VA.phsC.cVal.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU5.MX.PF.phsA.cVal.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU5.MX.PF.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU6.MX.TotVAr.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU6.MX.TotVA.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU6.MX.TotPF.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU6.MX.Hz.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GE Multilin F35 Multiple Feeder Protection System B-69...
  • Page 454 ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS GGIO4.MX.AnIn15.mag.f FOR RECEPTION GGIO4.MX.AnIn16.mag.f value GOOSE dataset item GGIO4.MX.AnIn17.mag.f None GGIO4.MX.AnIn18.mag.f GGIO3.ST.Ind1.q GGIO4.MX.AnIn19.mag.f GGIO3.ST.Ind1.stVal GGIO4.MX.AnIn20.mag.f GGIO3.ST.Ind2.q GGIO4.MX.AnIn21.mag.f GGIO3.ST.Ind2.stVal GGIO4.MX.AnIn22.mag.f ↓ ↓ GGIO4.MX.AnIn23.mag.f GGIO1.ST.Ind64q GGIO4.MX.AnIn24.mag.f GGIO1.ST.Ind64.stVal GGIO4.MX.AnIn25.mag.f GGIO3.MX.AnIn1.mag.f GGIO4.MX.AnIn26.mag.f B-70 F35 Multiple Feeder Protection System GE Multilin...
  • Page 455 Wednesday GGIO3.ST.UIntIn3.stVal Thursday GGIO3.ST.UIntIn4.q Friday GGIO3.ST.UIntIn4.stVal Saturday GGIO3.ST.UIntIn5.q GGIO3.ST.UIntIn5.stVal F239 GGIO3.ST.UIntIn6.q ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS GGIO3.ST.UIntIn6.stVal TIME START DAY INSTANCE GGIO3.ST.UIntIn7.q GGIO3.ST.UIntIn7.stVal value instance GGIO3.ST.UIntIn8.q First GGIO3.ST.UIntIn8.stVal Second GGIO3.ST.UIntIn9.q Third GE Multilin F35 Multiple Feeder Protection System B-71...
  • Page 456 IDs. The operate bit for element ID [14] REMOTE INPUTS (1 to 32) X is bit [X mod 16] in register [X/16]. [28] INSERT (via keypad only) B-72 F35 Multiple Feeder Protection System GE Multilin...
  • Page 457 ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION 18TH 19TH bitmask default variation 20TH 21ST 10TH 22ND 11TH 23RD 12TH 24TH 13TH 25TH F515 ENUMERATION ELEMENT INPUT MODE 0 = Signed, 1 = Absolute GE Multilin F35 Multiple Feeder Protection System B-73...
  • Page 458 Analogs (basically all metering quantities used in protection). F612 UR_UINT16: FLEXINTEGER PARAMETER This 16-bit value corresponds to the Modbus address of the selected FlexInteger paramter. Only certain values may be used as FlexIntegers. B-74 F35 Multiple Feeder Protection System GE Multilin...
  • Page 459: Iec 61850

    System Specification Description (SSD) file. The entire substation con- figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ- ual ICD files and the SSD file. GE Multilin F35 Multiple Feeder Protection System...
  • Page 460: Server Data Organization

    GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 in order to obtain the analog values provided by GGIO4. F35 Multiple Feeder Protection System GE Multilin...
  • Page 461: Mmxu: Analog Measured Values

    The following list describes the protection elements for all UR-series relays. The F35 relay will contain a subset of protec- tion elements from this list. • PDIF: bus differential, transformer instantaneous differential, transformer percent differential GE Multilin F35 Multiple Feeder Protection System...
  • Page 462 IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. F35 Multiple Feeder Protection System GE Multilin...
  • Page 463: Server Features And Configuration

    F35. This attribute is programmed through the setting and its LOCATION default value is “Location”. This value should be changed to describe the actual physical location of the F35. GE Multilin F35 Multiple Feeder Protection System...
  • Page 464: Logical Node Name Prefixes

    The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a F35 relay with an MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc. F35 Multiple Feeder Protection System GE Multilin...
  • Page 465: Generic Substation Event Services: Gsse And Goose

    The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the F35. The F35 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices. GE Multilin F35 Multiple Feeder Protection System...
  • Page 466 Configure the GOOSE service settings by making the following changes in the  PRODUCT SETUP COMMUNICATION      IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU- settings menu: RABLE GOOSE 1 F35 Multiple Feeder Protection System GE Multilin...
  • Page 467: Ethernet Mac Address For Gsse/Goose

    (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can be different for each Ethernet frame depending on the intended destination of the frame. GE Multilin F35 Multiple Feeder Protection System...
  • Page 468: Gsse Id And Goose Id Settings

    DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block. These strings are automatically populated and interpreted by the F35; no settings are required. C-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 469: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the F35 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 470: Configuring Iec 61850 Settings

    It can also import a system SCL file (SCD) to set communication configuration parame- ters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software. C.5.2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED.
  • Page 471: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 472 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 F35 Multiple Feeder Protection System GE Multilin...
  • Page 473 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin F35 Multiple Feeder Protection System C-15...
  • Page 474 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 F35 Multiple Feeder Protection System GE Multilin...
  • Page 475: Creating An Icd File With Enervista Ur Setup

    C.5.5 ABOUT SCD FILES System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI version 4.6 or above and ASE Visual SCL Beta 0.12).
  • Page 476 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 F35 Multiple Feeder Protection System GE Multilin...
  • Page 477 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin F35 Multiple Feeder Protection System...
  • Page 478: Importing An Scd File With Enervista Ur Setup

    The following procedure describes how to update the F35 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item. Select the saved SCD file and click Open. C-20 F35 Multiple Feeder Protection System GE Multilin...
  • Page 479 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 480: Acsi Conformance

    REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 F35 Multiple Feeder Protection System GE Multilin...
  • Page 481: Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin F35 Multiple Feeder Protection System C-23...
  • Page 482 S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference C-24 F35 Multiple Feeder Protection System GE Multilin...
  • Page 483 NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin F35 Multiple Feeder Protection System C-25...
  • Page 484: Logical Nodes

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 F35 Multiple Feeder Protection System GE Multilin...
  • Page 485 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin F35 Multiple Feeder Protection System C-27...
  • Page 486 ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 F35 Multiple Feeder Protection System GE Multilin...
  • Page 487: Iec 60870-5-104 Protocol

    Balanced Transmision Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin F35 Multiple Feeder Protection System...
  • Page 488  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 F35 Multiple Feeder Protection System GE Multilin...
  • Page 489  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin F35 Multiple Feeder Protection System...
  • Page 490 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 F35 Multiple Feeder Protection System GE Multilin...
  • Page 491 M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin F35 Multiple Feeder Protection System...
  • Page 492 F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure F35 Multiple Feeder Protection System GE Multilin...
  • Page 493  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin F35 Multiple Feeder Protection System...
  • Page 494 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs F35 Multiple Feeder Protection System GE Multilin...
  • Page 495: Points List

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin F35 Multiple Feeder Protection System...
  • Page 496 D.1 IEC 60870-5-104 PROTOCOL APPENDIX D D-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 497: Device Profile Document

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin F35 Multiple Feeder Protection System...
  • Page 498 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. F35 Multiple Feeder Protection System GE Multilin...
  • Page 499  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin F35 Multiple Feeder Protection System...
  • Page 500: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. F35 Multiple Feeder Protection System GE Multilin...
  • Page 501 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. GE Multilin F35 Multiple Feeder Protection System...
  • Page 502 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. F35 Multiple Feeder Protection System GE Multilin...
  • Page 503 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. GE Multilin F35 Multiple Feeder Protection System...
  • Page 504: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 F35 Multiple Feeder Protection System GE Multilin...
  • Page 505: Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin F35 Multiple Feeder Protection System...
  • Page 506: Counters

    A counter freeze command has no meaning for counters 8 and 9. F35 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values. E-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 507: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin F35 Multiple Feeder Protection System E-11...
  • Page 508 E.2 DNP POINT LISTS APPENDIX E E-12 F35 Multiple Feeder Protection System GE Multilin...
  • Page 509: Change Notes

    12 March 2008 URX-260 1601-0106-T1 5.6x 27 June 2008 08-0390 1601-0109-U1 5.7x 29 May 2009 09-0938 1601-0109-U2 5.7x 30 September 2009 09-1165 1601-0109-U3 5.7x 15 October 2010 10-2044 1601-0109-U4 5.7x 31 August 2015 15-2218 GE Multilin F35 Multiple Feeder Protection System...
  • Page 510: Changes To The Manual

    Updated TYPE TESTS specifications section Update Updated VERTICAL UNITS sub-section 3-13 3-14 Update Updated CONTACT INPUTS AND OUTPUTS section Update Updated USING SETTINGS FILES section Update Updated SECURITY section 5-21 5-21 Update Updated IEC 61850 PROTOCOL sub-section F35 Multiple Feeder Protection System GE Multilin...
  • Page 511 Manual part number to 1601-0106-S3 2-13 2-13 Update Updated COMMUNICATIONS specifications section 2-14 2-14 Update Updated INTER-RELAY COMMUNICATIONS specifications section Update Updated REAR TERMINAL LAYOUT section 3-46 Added ETHERNET SWITCH SELF-TEST ERRORS section GE Multilin F35 Multiple Feeder Protection System...
  • Page 512 Table F–9: MAJOR UPDATES FOR F35 MANUAL REVISION R3 PAGE PAGE CHANGE DESCRIPTION (R2) (R3) Title Title Update Manual part number to 1601-0106-R3 Added EXTENDED ENERVISTA UR SETUP FEATURES section 6-23 6-23 Update Updated MODEL INFORMATION section F35 Multiple Feeder Protection System GE Multilin...
  • Page 513 Updated PROTECTION ELEMENTS specifications section 3-20 3-20 Update Updated CPU MODULE COMMUNICATIONS WIRING diagram to 842765A2 6-17 6-17 Update Updated TRACKING FREQUENCY section 6-18 Added IEC 61850 GOOSE ANALOG VALUES section Update Updated SELF-TEST ERROR MESSAGES table GE Multilin F35 Multiple Feeder Protection System...
  • Page 514 F.1 CHANGE NOTES APPENDIX F Table F–12: MAJOR UPDATES FOR F35 MANUAL REVISION P2 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (P1) (P2) Update Updated FLEXANALOG PARAMETERS table F35 Multiple Feeder Protection System GE Multilin...
  • Page 515: Abbreviations

    AE ....Accidental Energization, Application Entity FWD....Forward AMP ....Ampere ANG ....Angle G .....Generator ANSI....American National Standards Institute GE....General Electric AR ....Automatic Reclosure GND....Ground ASDU ..... Application-layer Service Data Unit GNTR....Generator ASYM ..... Asymmetry GOOSE...General Object Oriented Substation Event AUTO .....
  • Page 516 RSTR ..... Restrained RTD ....Resistance Temperature Detector X ....Reactance RTU ....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR..... Transformer s ..... second Z..... Impedance, Zone S..... Sensitive F35 Multiple Feeder Protection System GE Multilin...
  • Page 517: Warranty

    F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 518 F.3 WARRANTY APPENDIX F F-10 F35 Multiple Feeder Protection System GE Multilin...
  • Page 519 Modbus registers ............B-18 AUXILIARY VOLTAGE METERING ........6-16 network ................. 5-16 overview ................ 1-16 RS232 ................3-23 RS485 ............3-23, 3-25, 5-15 settings ......5-16, 5-17, 5-22, 5-32, 5-33, 5-35 BANKS ............. 5-6, 5-68, 5-69 GE Multilin F35 Multiple Feeder Protection System...
  • Page 520 DATA LOGGER settings ................ 5-164 clearing ..............5-14, 7-2 DISCONNECT SWITCH Modbus ................B-7 FlexLogic™ operands .............5-92 Modbus registers ..........B-10, B-20 logic ................5-79 settings ................. 5-41 Modbus registers ............B-30 specifications..............2-11 settings ................5-77 F35 Multiple Feeder Protection System GE Multilin...
  • Page 521 ..............6-10 locking to a serial number ........4-9, 8-11 configuration ............3-44, 3-45 FLEXLOGIC™ hardware ............... 3-43 editing with EnerVista UR Setup ........4-2 Modbus registers ............B-19 equation editor ............. 5-100 GE Multilin F35 Multiple Feeder Protection System...
  • Page 522 AC current ............2-12, 5-68 AC voltage ............2-12, 5-69 G.703 ............ 3-31, 3-32, 3-33, 3-36 contact inputs .......... 2-12, 5-154, 5-178 GE TYPE IAC CURVES ..........5-109 dcmA inputs ............2-13, 3-22 GROUND CURRENT METERING ........6-15 direct inputs ..............2-13 GROUND IOC IRIG-B ..............
  • Page 523 Modbus ................B-6 store multiple settings ............B-5 Modbus registers ..........B-15, B-20 store single setting ............B-4 settings ................. 5-39 supported function codes ..........B-3 specifications ..............2-11 user map ............. 5-35, B-10, B-23 GE Multilin F35 Multiple Feeder Protection System...
  • Page 524 ............... 5-111 REPAIR ................F-9 specifications..............2-9 REPLACEMENT MODULES ........2-6, 2-7, 2-8 PHASE UNDERVOLTAGE RESETTING ............5-93, 5-163 FlexLogic™ operands ............ 5-91 REVISION HISTORY ............F-1 logic ................5-121 RF IMMUNITY ..............2-17 F35 Multiple Feeder Protection System GE Multilin...
  • Page 525 SINGLE LINE DIAGRAM ..........2-1, 2-2 phase ................5-111 SITE LIST, CREATING ............4-1 specifications ..............2-9 SNTP PROTOCOL TRACEABILITY error messages ............... 7-7 data ............. 4-11, 4-12, 8-13, 8-14 Modbus registers ............B-20 overview ............... 4-10, 8-12 GE Multilin F35 Multiple Feeder Protection System...
  • Page 526 WEB SERVER PROTOCOL ..........5-32 USER-PROGRAMMABLE LEDs WEBSITE ................1-1 custom labeling ............. 4-22 defaults ................. 4-16 description............4-15, 4-16 Modbus registers ............B-20 settings ................. 5-46 ZERO SEQUENCE CORE BALANCE .........3-13 specifications ..............2-10 USER-PROGRAMMABLE PUSHBUTTONS viii F35 Multiple Feeder Protection System GE Multilin...

Table of Contents