Operating hours counter

8.1

How the operating hours counter works

Introduction
The AI Energy Meter 480VAC ST provides one operating hours counter for each phase,
which counts the operating hours of the load connected to a phase when there is current
greater than the configurable "Low limit for measuring current". The operating hours counter
for the entire module is calculated from the sum of the operating hours of the individual
phases. The operating hours counter has a value range from 0 to 3.4 x 10
stored retentively in the module and can be read via the data record 143 (energy counter
data record) and data record 150 (measured value for extended measuring and status
values).
Configuring
You configure the following operating hours counter settings in STEP 7:
● Activation of the gate for the operating hours counter
Changing properties in RUN
The following table shows the supported control information:
Control information
Open / close operating hours counter
Set initial value
Reset operating hours counter
Effective only with enabled gate
1
Only module-wide resetting is supported in module version "2 I / 2 Q".
2
See also
Resetting energy counters and overflow counters (Page 48)
Module version "2 I / 2 Q" (Page 122)
Structure for energy counters (DS 143) (Page 159)
Measured value data record for advanced measurement and status values (DS 150)
(Page 170)
62
Default value
Closed
1
0
0
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
. The values are
38
Available in
Module version starting at
2 bytes of output data
Data record 143
Module version starting at
2 bytes of output data
2
Manual, 12/2015, A5E36061895-AA
8

Hide quick links:

Table of Contents
loading

Table of Contents