Configuration / address space
4.2 Selecting the module versions
Result
The user data variant is switched with the next cycle.
Note
Information about user data changeover
The parameterized user data variant is set in the following cases:
• A "0" is written in byte 0 in the output data of a user data variant.
• Byte 0 in the output data of a user data variant contains an invalid value:
– Coding of the user data variant not available
– Available address space is not sufficient for the selected user data variant.
4.2.4

Recommendations for selecting the module version

The following table shows which module version is suitable for a given purpose.
Module version
2 I / 2 Q
EE@Industry measu-
rement data profile
E0 / E1 / E2 / E3
32 I / 12 Q
User-specific
With GSD configuration
32 I / 12 Q
64 I / 12 Q
128 I / 12 Q
256 I / 12 Q
30
or
Application
Use of many AI Energy Meter
480VAC ST in an ET 200SP
or little address space is
available
Cyclic measurement per
phase
Supplied measured values in
accordance with the
EE@Industry measured data
profile
Cyclic measurement per
phase
Flexibility by switching prede-
fined user data variants
Cyclic measurement of up to
64 measured values configu-
rable
Flexibility by switching prede-
fined user data variants
Note
Read the measured values solely via the RDREC instruc-
tion from a measured value data record.
Quality information about the measured values is always
available.
Available measured values depend on the configured
measurement data profile.
The user data are fixed and cannot be changed dynami-
cally. Alternatively, read the measured values acyclically
from a measured value data record via the RDREC in-
struction.
No quality information
Quality information about the measured values is always
available.
Depending on the user data variant, you must convert
the measured values in the CPU to physical values using
the supplied scaling factor.
One cycle elapses for each user data changeover.
Measured values from the next user data variant are thus
supplied with a slight time offset.
Alternatively, read the measured values acyclically from
a measured value data record via the RDREC instruc-
tion. Consistent measured values of a measuring cycle
are supplied.
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA