Huawei SUN2000-8KTL Quick Installation Manual
Huawei SUN2000-8KTL Quick Installation Manual

Huawei SUN2000-8KTL Quick Installation Manual

Solar inverter network
Hide thumbs Also See for SUN2000-8KTL:
SUN2000 (8KTL-28KTL)

Quick Installation Guide

0
Issue: 13
Part Number: 31505445
Date: 2015-08-03
HUAWEI TECHNOLOGIES CO., LTD.
Table of Contents
loading

Summary of Contents for Huawei SUN2000-8KTL

  • Page 1: Quick Installation Guide

    SUN2000 (8KTL-28KTL) Quick Installation Guide Issue: 13 Part Number: 31505445 Date: 2015-08-03 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2: Determine The Installation Position

    Determine the installation position. Unit: mm Install the SUN2000 in a position where the liquid crystal display (LCD) is easy to view and operate. Upside down Vertical Backward Forward Horizontal Copyright © Huawei Technologies Co., Ltd. 2015. All rights reserved.
  • Page 3 Installing an Inverter (support-mounting is used as an example) Determine the hole positions on the support Drill holes. based on rear panel dimensions. Unit: mm Secure the rear panel. Mount the inverter on the rear panel. M10 (3 PCS) 30 N· m Tighten hexagon bolts.
  • Page 4: Electrical Connection

    To enhance the corrosion resistance performance of the PE terminals, apply silica gel on them after connecting the ground cable. 2. Install AC output power cables. Cross-sectional Area of the Cable Inverter Model (Recommended) SUN2000-8KTL/10KTL/12KTL 4.0 mm (12 AWG) SUN2000-15KTL/17KTL/20KTL/23KTL/28KTL 6.0 mm (10 AWG) / 10.0 mm...
  • Page 5 sealing Cable Socket cover Large handle Auxiliary screwdriver connector (recommended) NOTICE The N cable is inserted into hole 4. Do not insert L1/L2/L3 into Click Notch NOTE To quickly connect the AC output connector to the AC output terminal of the inverter, keep the notch of the connector facing exactly to the operator.
  • Page 6 Positive and negative metal terminals: Positive metal terminal (female) Negative metal terminal (male) Positive metal terminals Recommended: H4TC0001 (Amphenol) Negative metal terminals Ensure that cables cannot Common PV cables with a cross- sectional area of 4 mm² in the be removed after crimped. industry are recommended.
  • Page 7: Installation Verification

    Install an RS485 communications cable. Color Pin Definition The side without buckles White and RS485A, and RS485 orange differential signal+ RJ45 Matching nut connector Orange RS485B, and RS485 Sealing with differential signal- Plastic washer shielding base functions White and green PGND Cable sealing nut...
  • Page 8 Main Second- Third-Level Fourth-Level Menu Setting Menu Level Menu Menu Wizard Language Set based on site requirements. Date&Time Date Set based on site requirements. Time Set based on site requirements. China medium-voltage power grid, Grid Code choose CHINA-MV480. China low-voltage power grid, choose NB/T 32004.
  • Page 9 Appendix: Power Grid Standard Code Mapping Table Power Grid Power Grid Country and Condition Country and Condition Standard Code Standard Code China medium-voltage IEC61727- IEC medium-voltage power CHINA-MV480 power grid MV480 grid China low-voltage power VDE 0126-1-1- Bulgaria low-voltage power NB/T 32004 grid grid...
  • Page 10 HUAWEI TECHNOLOGIES CO., LTD. Huawei Industrial Base Bantian Longgang Shenzhen 518129 People's Republic of China www.huawei.com...