3. System remote controller
Environment specification
Item
Connected Equipment
Number of Units
Neuron CHIP
Network Transceiver
Average communication capacity
Performance
Peak communication capacity
The proper communication is not obtainable when communication intervals exceed its performance, assure sufficient intervals.
ACK Service is recommended for the network service.
Detailed specifications for the L
Transceiver Data Book" by Echelon Corporation.
Please obtain the Network Variables Specification for details from your dealer.
(*9, 10, 11)
Notes
*1: "n" of the network variable shows M-NET
address of indoor units.
*2: It may be unable to be used by the system
configuration of air-conditioners units.
*3: It is possible to use with an "MA or ME" remote controller.
*4: For the use of this function, turn ON the switch (SW1-1) on
LM ADAPTER. (Factory setting "OFF")
*5: For the use of this function, turn ON the switch (SW1-8) on
LM ADAPTER. (Factory setting "OFF")
*6: For the use of this function, turn ON the switch (SW1-4) on
LM ADAPTER. (Factory setting "OFF")
*7: It is possible to use with other system controller.
*8: This function is available only for the conventional indoor
units which don't support the dual setpoint.
*9: These functions are available for the units which support
the dual setpoint.
*10: This function is available for the DOAS was manufactured
in October, 2012 or later, when it uses for the DOAS.
*11: This function is available when the auto mode should be
controlled by single set point like the conventional one,
even when the dual set point is valid.
MITSUBISHI ELECTRIC
LM-AP can control 50 indoor units (including LOSSNAY)
TMPN3150/FT3150-P20 (10MHz)
FTT-10A/FT-X1 (Free Topology 78kbps)
2.5 inputs/second
50 inputs/second (for one second)
®
W
network can be found in "FTT-10A Free Topology Transceiver User's Guide" or " FT3120/FT3150 Smart
ON
ORKS
nviOnOff_n
nv1n
SNVT_switch
nviMode_n
nv3n
SNVT_hvac_mode
nviSetP_n
(*8)
nv5n
SNVT_temp_p
nviCoolSetP_n
(*9)
nv7n
SNVT_temp_p
nviHeatSetP_n
(*9)
nv9n
SNVT_temp_p
nviAutoSetP_n
nv11n
SNVT_temp_p
nviFanSpeed_n
nv19n
SNVT_switch
nviProOnOff_n
(*2, 3, 4)
nv21n
SNVT_switch
nviProMode_n
(*2, 3, 4)
nv23n
SNVT_switch
nviProSetP_n
(*2, 3, 4)
nv25n
SNVT_switch
nviThermoOff_n
(*5)
nv27n
SNVT_switch
nviFiltReset_n
(*6)
nv29n
SNVT_switch
CONTROLLER
Description
Multiple split-type air conditioners
Heat recovery ventilators
( For details of the connectable models,please contact the dealer.)
Indoor[1]-[50]
Network Variables
HYBRID CITY MULTI
LOSSNAY
nvoOnOff_n
nv2n
SNVT_ switch
nvoMode_n
nv4n
SNVT_hvac_mode
nvoSetP_n
nv6n
SNVT_temp_p
nvoCoolSetP_n
nv8n
SNVT_temp_p
nvoHeatSetP_n
nv10n
SNVT_temp_p
nvoAutoSetP_n
nv12n
SNVT_temp_p
nvoFanSpeed_n
nv20n
SNVT_switch
nvoProOnOff_n
nv22n
SNVT_switch
nvoProMode_n
nv24n
SNVT_switch
nvoProSetP_n
nv26n
SNVT_switch
nvoThermoOff_n
nv28n
SNVT_switch
nvoOnTime_n
nv30n
SNVT_time_hour
nvoSpaceTemp_n
nv31n
SNVT_temp_p
nvoAlarm_n
nv32n
SNVT_switch
nvoErrCode_n
nv33n
SNVT_count
nvoErrAdrs_n
nv34n
SNVT_count
nvoThermoSt_n
nv35n
SNVT_state
nvoThermo_n
nv36n
SNVT_switch
nvoIcMdlSize_n
nv38n
SNVT_count
nvoGroupNo_n
nv39n
SNVT_count
(*8)
(*9)
(*9)
(*9, 10, 11)
(*2, 3, 4)
(*2, 3, 4)
(*2, 3, 4)
(*5)
(*6)
(*7)
3 - 55