Heating Operation - Fujitsu AS* A09LEC Service Instruction

Split type room air conditioner wall mounted type
Table of Contents

2. HEATING OPERATION

2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation speed of the compressor.
* If the room temperature is lower by
speed will attain to maximum performance.
* If the room temperature is higher
* When the room temperature is between
the compressor speed is controlled within the range shown in Table2.
However, the maximum speed is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor speed range )
ASYA09LEC
ASYA12LEC
( Fig.2 : Limit of maximum speed based on outdoor temperature )
When outdoor
temperature drops
C zone
17°C
B zone
12°C
A zone
5°C
AA zone
* The room temperature is controlled
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
3°C
than a set temperature, the compressor operation
2.5°C
than a set temperatire, the compressor will be stopped.
+2.5°C
Minimum
Maximum
speed
speed
18rps
119rps
18rps
119rps
When outdoor
temperature rises
09LEC
19°C
14°C
12LEC
7°C
2°C
higher than the setting temperature for 60 minutes
to
-3°C
of the setting temperature,
Hi
AA zone
119rps
A zone
119rps
B zone
119rps
C zone
119rps
AA zone
119rps
A zone
119rps
B zone
119rps
119rps
C zone
01-02
Me+
Me
Lo
119rps
85rps
64rps
119rps
85rps
64rps
119rps
85rps
64rps
119rps
85rps
64rps
119rps
96rps
80rps
119rps
96rps
80rps
119rps
96rps
80rps
119rps
96rps
80rps
Quiet
55rps
55rps
45rps
37rps
68rps
68rps
54rps
45rps