The cables must: 1) Protrude from the wall. 2) Come out at 120cm from ground (see Figure 1) (advised). cable tray cables Floor Figure 1: Wall Set Up for the Cable Trays Version: 1.0 EN Page 3 of 24...
The RTU is powered at low voltage (12VDC 160mA), preferably using a power supply module with battery backup (RTU-Qxx), or using an ordinary power supply having the same characteristics. The power cables must be dimensioned as indicated in the table below. The maximum allowable voltage drop on the power cable is 1V.
Page 5
If necessary, the repeater relays must be inserted inside the box for electrical locking commands and the signal light. 2-pole LON cable 4 mm diameter 2 metri 6,10 cm 10 pole cable 8.6mm diameter Figure 2: Position and dimensions of the non-removable cables 2 meters 4,20 cm Shunt Box...
• The L data cables must be double twisted-pair cables ORKS • In a free topology configuration, the overall length of the sections must not exceed 500m • In a bus configuration, the overall length of the sections must not exceed 2700m •...
Mount the bracket onto the wall as follows: 1. Placing the bracket against the wall to indicate the proper positions of the holes, make the holes for the two bolts that will go into the wall to hold the bracket (the bolts are included in the installation kit) 2.
1.5.3 Input Cable 1 – Door Contact The balanced input 1 is dedicated to door status control; the balancing resistances must be positioned near the clean sensor contact. IN1 (green / white) GND (black) Figure 7: Connection for Balanced Input 1 – Door Contact Page 10 of 24...
1.5.4 Input Cable 2 - Button Balanced input 2 is dedicated to status control of the Open button; the balancing resistances must be positioned near the clean contact of the button. IN2 (green / gray) Figure 8: Connection for Balanced Input 2 - Button Page 11 of 24...
1.5.5 Output Cable Relay 1- Door Open The Relay 1 output is used for door control. It makes both NO and NC contacts available. The external load can be powered directly by AC or DC, in accordance with the following limits: Minimum Load: 12VDC / 10mA Voltage Working Current Peak Current...
Page 13
1N4004 Diode Transient Suppressor Relay 1 Green = C Yellow = NC Gray = NO Figure 9: Connection for Output Relay 1 (NO) – Door Open – DC Voltage Mov75Vac Soppressore di transienti Rele 1 Green = C Yellow = NC Gray = NO Figure 10: Connection for Output Relay 1 (NO) –...
Page 14
1.5.5.1 Using an External Relay In case of excessive use or use under elevated current or voltage, you must insert a relay capable of supporting the load for a higher number of operations. The coil for the repeater relay must always be equipped with transient suppressors, as can be seen in Figures 9 and 10.
1.5.6 Output Cable Relay 2 – Signal Light Output Relay 2 is used for signaling the status of the door (gateway occupied / free ) and provides both NO and NC contacts. The external load can be powered directly from AC or DC power, in accordance with the following limits: Voltage Working Current...
Page 16
Relay 2 Brown = C White = NC Blue = Figure 12: Connection for Output Relay 2 (NO) – Resistive Load – AC/DC Voltage Transient Suppressor Vext AC = Mov75Vac Vext DC = diodo 1N4004 Mov x Vac Transient Suppressor Relay 2 Brown = C White = NC...
Figure 14: Mounting 1) The RTUL19 is positioned atop the wall bracket protrusion 2) The back part is aligned with the wall by rotating 3) The RTUL19 is mounted onto the bracket using screws Page 17 of 24...
ACTIVATION To identify the node, you can call the service pin using the relay-reed found inside the device (see Figure 15). Use the following steps for this procedure: 1. Place a small magnet as indicated in Figure 15 to call the service pin. The signal is linked to the yellow service LED (at the center), which will blink throughout the operation.
The label with the neuron ID that comes with the kit must be applied by the installer on the appropriate identification sheet. You also must indicate the location of the terminal in the appropriate box (see example in Table 3). Description of Location Entrance to Offices, First Floor, Stairway E Description of TemaServer...
2 TECHNICAL DATA Parameter Value ±15% Power Supply 100mA nominal (1.4W), 160mA max (2W) Weight 0.3 kg Dimensions 156 Lu x 40 La x 27 sp mm Degree of Protection IP55 -20 to 60 °C Operational Temperature -20 to 70 °C Storage Temperature 0 to 95 % without condensation Relative Humidity of...
In application of directive 2002/96/EC regarding electrical and electronic waste devices, in vigor from 13 August 2005, Honeywell engages, when requested by the customer, to the collection, treatment, recovery, and proper disposal of all devices produced. All users within the European Union are hereby informed of the requirement for the proper elimination of the product as regulated by laws, rules, and local procedures.